Plan Review Details - Permit 03021485
Plan Review Stops For Permit 03021485
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-03-11 Cont ID  
Sent By lsmith Date 2003-03-11 Time 16:19 Rev Time 0.00
Received By lsmith Date 2003-03-11 Time 16:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-03-28 Cont ID  
Sent By dpalmer Date 2003-03-28 Time 11:04 Rev Time 0.33
Received By dpalmer Date 2003-03-28 Time 11:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-03-26 Cont ID  
Sent By dpalmer Date 2003-03-26 Time 06:54 Rev Time 0.50
Received By dpalmer Date 2003-03-26 Time 06:54 Sent To  
Notes
2003-03-26 00:00:00************ UNSAT *****************
  
 1)NOTE: PLEASE SEE E-1, TITLE AT BOTTOM
 SHOWS EXSITNG? AND YET NEW IS SHOWN.
 NOTE FROM FIRST REVIEW, REQ`D ALL NEW
 WORK/CIRCUITING TO BE SHOWN? AND
 CORRELATE WITH SUBMITTED PANEL SCHEDULE?
  
 2)NOTE: PLEASE SEE SHEETS, AREAS ARE
 SHOWN W/ NOTES THAT SAY "NO NEW WORK"
 AND YET NEW WORK IS SHOWN?? PLEASE
 CLARFIY ON PLANS.
  
 3)NOTE: PLEASE SHOW CIRCUITING PER
 700-12E.
  
 4)NOTE: PLEASE CORRELATE E-1,E-2,E-3
 PLEASE REMOVE ALL OLD SHEETS AND INSERT
 NEW SHEETS INTO TWO COMPLETE SETS FOR
 REVIEW.
  
 5)NOTE: PLEASE SEE LETTER ATTACHED IN
 REFERENCE TO FS. 553.80(2)(B).
 FOR DESIGN PROFESSIONAL OF RECORD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION AND
 SEE NOTES FROM FIRST REVIEW. IF THERE
 ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-02-25 Cont ID  
Sent By dpalmer Date 2003-02-25 Time 06:37 Rev Time 0.33
Received By dpalmer Date 2003-02-25 Time 06:37 Sent To  
Notes
2003-02-25 00:00:00******************** UNSAT *************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED
 PANEL SCHEDULE.
 PANEL SCHEDULE IS SHOWN AS BLANK??
 PLEASE SHOW BOTH PANELS.
  
 2)NOTE: PLEASE SHOW CIRCUITING FOR
 EM/EXT LTS PER 700-12E
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-03-28 Cont ID  
Sent By mcarsill Date 2003-03-28 Time 13:13 Rev Time 0.00
Received By mcarsill Date 2003-03-28 Time 13:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-02-21 Cont ID  
Sent By mcarsill Date 2003-02-21 Time 14:38 Rev Time 0.00
Received By mcarsill Date 2003-02-21 Time 14:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-24 Cont ID  
Sent By sthyng Date 2003-03-24 Time 09:10 Rev Time 0.00
Received By sthyng Date 2003-03-24 Time 09:10 Sent To  
Notes
2003-03-24 00:00:00COMM BOARD #8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-20 Cont ID  
Sent By dpalmer Date 2003-02-20 Time 16:33 Rev Time 0.00
Received By dpalmer Date 2003-02-20 Time 16:33 Sent To  
Notes
2003-02-20 00:00:00TO COMM BOARD #25

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-04-10 Cont ID  
Sent By pkrauss Date 2003-04-10 Time 10:09 Rev Time 0.35
Received By pkrauss Date 2003-04-10 Time 09:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-03-10 Cont ID  
Sent By pkrauss Date 2003-03-10 Time 15:36 Rev Time 0.40
Received By pkrauss Date 2003-03-10 Time 15:05 Sent To  
Notes
2003-03-10 00:00:00DENIED:MECHANICAL PERMIT 03021487
  
 NO MECHANICAL PLANS SUBMITTED FOR REVIEW
 PLEASE PROVIDE SCOPE OF WORK.INDICATE
 IF EQUIPMENT WILL BE EXISTING OR NEW.
 PROVIDE OUTSIDE AIR CALCULATIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-04-11 Cont ID  
Sent By kstevens Date 2003-04-11 Time 18:08 Rev Time 0.75
Received By kstevens Date 2003-04-11 Time 17:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-03-11 Cont ID  
Sent By kstevens Date 2003-03-11 Time 16:05 Rev Time 1.00
Received By kstevens Date 2003-03-11 Time 16:04 Sent To  
Notes
2003-03-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-2 RENOVATED HDCP TOILET ROOM
 DOES NOT MEET CODE. MINIMUM OF 30" FROM
 THE CENTER OF A WATER CLOSET TO THE
 CENTER OF THE ADJACENT FIXTURE, (LAV).
 SECTION 405.3.1. 18" TO CENTER OF W/C
 OFF WALL - 30" TO CENTER OF LAV. - MIN.
 15" OFF WALL TO CENTER OF LAV. MINIMUM
 OF 5'3" ROOM REQUIRED.
 2) SHT A-2 DOOR TO TOILET ROOM BEHIND
 ELEVATOR SHALL NOT OPEN INTO THE CLEAR
 FLOOR SPACE OF ANY FIXTURE OR UNOBSTRUC-
 TED 5' TURNING RADIUS.
 3) PER 11-4.1.6(2) 20% ABOVE CONTRACT
 PRICE SHALL BE SPENT ON ACCESSIBILITY
 ISSUES. PLEASE INDICATE HOW $13,298 WILL
 BE SPENT ON THIS REMODEL
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377