Plan Review Details - Permit 03021342
Plan Review Stops For Permit 03021342
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-06-10 Cont ID  
Sent By hpiskura Date 2003-06-10 Time 08:11 Rev Time 0.00
Received By hpiskura Date 2003-06-10 Time 08:12 Sent To FIRE
Notes
2003-06-10 00:00:00ONLY ONE SET OF PLANS OWES ADDITIONAL
 FEE AND NOC

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-05-02 Cont ID  
Sent By hpiskura Date 2003-05-02 Time 14:49 Rev Time 0.00
Received By hpiskura Date 2003-05-02 Time 14:49 Sent To  
Notes
2003-05-02 00:00:00THE DESIGN WIND PRESSURES FOR THE NEW
 STOREFRONT DOOR ARE NOT SHOWN ON THE
 PLAN AS REQUESTED ON THE 3/1/03 LIST.
  
 THE REQUEST REGARDING HANDICAP
 ACCESSIBILITY HAS NOT BEEN ADDRESSED.
  
 THE GOLDBERG PLAN DATED 4/27/03
 ENUMERATES THREE ITEMS TO BE
 ACCOMPLISHED UNDER THIS PERMIT.THE
 PLAN SHOWS "NEW PLYWOOD ARCHES" THAT
 ARE NOT INCLUDED ON THE LIST.PLEASE
 CLARIFY THE SCOPE OF WORK.
  
 PROVIDE THE TEST AND/OR PRODUCT
 APPROVAL FOR THE STOREFRONT SYSTEM.
  
  
 AS PREVIOUSLY NOTED, $1500.00 IS TOO LOW
 FOR THIS WORK.PROVIDE A COPY OF THE
 SIGNED CONTRACT AND A DETAILED TAKEOFF
 TO JUSTIFY THIS ASSERTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-03-01 Cont ID  
Sent By hpiskura Date 2003-03-01 Time 07:30 Rev Time 0.00
Received By hpiskura Date 2003-03-01 Time 07:20 Sent To  
Notes
2003-03-01 00:00:00THE NEW DOOR SHOWN IN THE PACKAGE STORE
 APPEARS TO SWING OVER THE RIGHT OF WAY.
 SEE FBC 3203.
  
 SHOW THE WIND PRESSURE DESIGN FOR THE
 NEW DOOR.SEE FBC 1606.1.7 #5.
  
 PLEASE PROVIDE A SEATING PLAN WITH THE
 NECESSARY DIMENSIONS.SEE FBC 1003.1.2.
  
 PLEASE CLEARLY NOTE WHAT IS EXISTING AND
 WHAT IS TO BE ACCOMPLISHED UNDER THIS
 PERMIT APPLICATION.SEE FBC 104.2.1.
  
 SHOW THE HANDICAP ACCESIBILITY AT THE
 FRONT ENTRANCE AS EXISTING OR PROVIDE
 NEW. SEE FBC 11-4.1.6 (1) (B).
  
 WHAT PORTION OF THE WORK IS TO BE
 ACCOMPLISHED WITH THE DECLARED PERMIT
 VALUATION OF $1500.00?PLEASE PROVIDE
 A WRITTEN SCOPE OF WORK AND A COPY OF
 THE SIGNED CONTRACT.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-02-20 Cont ID  
Sent By dpalmer Date 2003-02-20 Time 14:11 Rev Time 0.25
Received By dpalmer Date 2003-02-20 Time 14:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-06-10 Cont ID  
Sent By nmccray Date 2003-06-10 Time 13:17 Rev Time 0.00
Received By nmccray Date 2003-06-10 Time 13:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2003-05-09 Cont ID  
Sent By hpiskura Date 2003-06-10 Time 08:12 Rev Time 0.00
Received By mcarsill Date 2003-05-09 Time 16:18 Sent To  
Notes
2003-05-09 00:00:001) PLEASE ANSWER ALL PREVIOUS COMMENTS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-02-21 Cont ID  
Sent By mcarsill Date 2003-02-21 Time 15:08 Rev Time 0.00
Received By mcarsill Date 2003-02-21 Time 15:08 Sent To  
Notes
2003-02-21 00:00:001) PLEASE INDICATE EMERGENCY LIGHTS AND
 EXIT SIGNS.
  
 2) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 3) PLEASE INDICATE OCCUPANT LOADS FOR
 THE TENANT SPACE.
  
 4) PLEASE INDICATE DOOR HARDWARE ON
 DOORS.
  
 5) PLEASE EXPLAIN EXITING CONCEPT. WHERE
 ARE THE REQUIRED EXITS FROM THE MAIN
 BAR, AND GENERAL SEATING AREA. IT WAS
 NOTED THAT SOME EXTERIOR DOORS ARE
 PRESENT FROM THE STORAGE ROOM AND
 PACKAGE STORE. EXITING IS NOT ALLOWED
 THRU STORAGE ROOMS. IT DOES APPEAR THAT
 A STAGE IS PRESENT AND TWO DOORS ARE
 PRESENT. IS THERE ANY CHANGE IN
 ELEVATION FROM THE FLOOR TO THE STAGE
 SINCE NO STAIRS ARE SHOWN. PLEASE
 ADVISE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-05 Cont ID  
Sent By shernand Date 2003-06-05 Time 10:54 Rev Time 0.00
Received By shernand Date 2003-06-05 Time 10:54 Sent To  
Notes
2003-06-05 00:00:00COMM BOARD #6

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-30 Cont ID  
Sent By shernand Date 2003-04-30 Time 14:18 Rev Time 0.00
Received By shernand Date 2003-04-30 Time 14:18 Sent To  
Notes
2003-04-30 00:00:00COMM BOARD #1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-20 Cont ID  
Sent By dpalmer Date 2003-02-20 Time 14:08 Rev Time 0.00
Received By dpalmer Date 2003-02-20 Time 14:08 Sent To  
Notes
2003-02-20 00:00:00TO COMM BOARD #24 B, FIRE,E