Plan Review Details - Permit 03021272
Plan Review Stops For Permit 03021272
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-05-02 Cont ID  
Sent By rmcdouga Date 2003-05-02 Time 16:35 Rev Time 2.00
Received By rmcdouga Date 2003-05-02 Time 16:34 Sent To  
Notes
2003-05-02 00:00:00BUILDING PROVISO
  
 1)SUBMIT PRODUCT APPROVAL FOR STRUCTURAL
 MULLIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-04-21 Cont ID  
Sent By pkrauss Date 2003-04-15 Time 12:31 Rev Time 2.00
Received By rmcdouga Date 2003-04-17 Time 16:30 Sent To  
Notes
2003-04-17 00:00:00BUILDING DENIED
  
 1) THE ENERGY CALCULATION FORM IS
 REQUIRED TO BE SIGNED AND DATED BY THE
 PREPARER AND THE OWNER/AGENT.
  
 2)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR THE SINGLE OUTSWING FRONT
 DOOR AND STRUCTURAL WINDOW MULLIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-03-18 Cont ID  
Sent By shernand Date 2003-04-04 Time 10:11 Rev Time 4.00
Received By rmcdouga Date 2003-03-18 Time 16:25 Sent To  
Notes
2003-03-18 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) THE INFORMATION ON THE ENERGY CALC.
 FORM DOES NOT MATCH THE PLANS. SOME OF
 THE INFORMATION IS MISSING AT THE TOP OF
 THE FORM SUCH AS PROJECT NAME, ADDRESS,
 OWNER, ETC. THE BUILDER LISTED ON THE
 FORM IS NOT THE SAME ONE THAT IS LISTED
 ON THE PERMIT APPLICATION. THE FORM
 PREPARER AND THE OWNER/AGENT ARE
 REQUIRED TO SIGN AND DATE THE FORM.
  
 3) INDICATE THE SIZE OF THE ATTIC ACCESS
 IN THE GARAGE. FBC 2309.6
  
 4) THE STRUCTURE IS LOCATED IN AN A-9
 FLOOD ZONE WITH A BASE FLOOD ELEVATION
 OF 13 FEET. THE CITY'S FLOOD ORDINANCE
 REQUIRES THE STRUCTURES LOWEST FLOOR TO
 BE 6" ABOVE BASE FLOOD ELEVATION.
 INDICATE MINIMUM FINISH FLOOR ELEVATION
 ON PLANS. AN ELEVATION CERTIFICATE WILL
 BE REQUIRED. THE FLOOD ZONE LISTED ON
 THE SURVEY IS INCORRECT.
  
 5) PROVIDE A SOIL BORING TEST REPORT AS
 REQUIRED BY FBC 1804.2.2.
  
 6) PROVIDE A WINDOW AND DOOR SCHEDULE.
 INDICATE TYPES AND SIZES.
  
 7) THE PERCENTAGE OF WALL AREA ALLOWED
 AS OPENINGS BY FBC TABLE 600 APPEARS TO
 BE EXCEEDED AT THE RIGHT SIDE. THE
 AREA ALLOWED AS OPENINGS IS 20%.
  
 8) INDICATE ADEQUATE ATTIC VENTILATION
 AS REQUIRED BY FBC 2309.7.
  
 9) PROVIDE EGRESS WINDOWS AT SLEEPING
 ROOMS. FBC 1005.4
  
 10) SAFETY GLASS IS REQUIRED IN BATHROOM
 WINDOW. FBC 2405.2
  
 11) THE DIMENSIONS GIVEN IN THE FOOTING
 NOTES ON A1 DO NOT AGREE WITH THE ONES
 ON THE DETAIL.
  
 12) PROVIDE A DETAIL OF THE 4" TUBE
 STEEL COLUMNS AT THE COVERED ENTRY.
 INDICATE THE STEEL THICKNESS, BASE, CAP,
 ANCHORS/FASTENERS, WELD TYPE, ETC.
  
 13) PROVIDE A BATHROOM WITH A DOOR THAT
 HAS A 29" CLEAR OPENING.
  
 14) PROVIDE DETAIL AT COVERED ENTRY
 INDICATING HOW ROOF WILL BE SUPPORTED.
  
 15) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - SLIDING GLASS DOOR (INFORMATION THAT
 WAS SUBMITTED IS NOT ACCEPTABLE)
 - EXTERIOR WINDOWS
 - SINGLE OUTSWING DOOR WITHOUT SIDELITES
  
 16) PROVIDE KEY PLAN AND INSTALLATION
 SCHEDULE FOR STORM PANELS AND INDICATE
 THE SPECIFIC TYPES OF ANCHORS THAT WILL
 BE USED. PROVIDE UPDATED COPIES OF SBCCI
 PRODUCT APPROVAL FOR STORM PANELS.
 (REPORT # 9748A IS THE CURRENT ONE)
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-04-29 Cont ID  
Sent By dpalmer Date 2003-04-29 Time 07:56 Rev Time 0.50
Received By dpalmer Date 2003-04-29 Time 07:56 Sent To P
Notes
2003-04-29 00:00:00************* NOTES REDLINED ********
  
 1)NOTE: PLEASE SEE KITCHEN COUNTERSPACE
 FOR, ALL RECEPTS TO BE GFI/GFI PROTECTED
 AS ORIG NOTED ON FIRST TWO REVIEWS.
  
 2)NOTE: PLEASE SEE BATHR ECEPT, TO BE W/
 IN 3' OF SINK.
 210-52D
  
 3)NOTE: PLEASE SEE MAX OCP FOR A/C COND
 UNIT. SHOWS 50A OCP W/ #10 .
  
 PLEASE NOTE, THESE WERE NOTES FROM
 OTHER REVIEWS.
  
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-04-09 Cont ID  
Sent By sthyng Date 2003-04-28 Time 12:54 Rev Time 0.50
Received By dpalmer Date 2003-04-09 Time 05:55 Sent To P
Notes
2003-04-09 00:00:00*********** UNSAT **************
  
 1)NOTE: PLEASE SEE FIRST SET OF REVIEW
 NOTES, NOT ALL NOTES WERE ADDRESSED.
  
 2)NOTE: PLEASE SEE MIN OCP FOR AHU @8KW
 TO BE 125% 424-3. SHOWN AS 40A.
  
 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULE
 PER 210-12
  
 4)NOTE: PLEASE CORRELATE RISER DIAGRAM
 SHOWN ON A-6 AND PLANS. PLANS SHOW A
 MAIN DISC OUTSIDE NEXT TO METER?
  
 5)NOTE : PLEASE SHOW ALL GARAGE RECEPTS
 PER 210-8 AS GFI..
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-03-12 Cont ID  
Sent By shernand Date 2003-04-04 Time 10:11 Rev Time 0.50
Received By dpalmer Date 2003-03-12 Time 06:13 Sent To B
Notes
2003-03-12 00:00:00************** UNSAT ***************
  
 1)NOTE : PLEASE SUBMIT AIC RATING FOR
 NEW SERVICE EQUIPMENT. MAINS/BRKRS/
 PANELS ARE ALL REQ`D TO BE RATED FOR THE
 AVAILABLE FAULT CURRENT. 110-9
  
 2)NOTE: PLEASE LIST THE REQ`D BATH
 CIRCUIT(S) PER 210-52D,210-11-C3
 20A/#12.
  
 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 CIRCUITS PER 210-12
  
 4)NOTE: PLEASE SHOW ALL DISC`S REQ`D FOR
 EQIPMENT/AHU/WATER HEATER.
 440-11
  
 5)NOTE: PLEASE SIZE OCP FOR LOAD ON AHU.
 PLEASE SEE 424-3. MIN 125%
  
 6)NOTE: PLEASE SEE NFPA-72, 8-1.4.2
 MISSING SD`S INSIDE AND OUTSIDE ALL
 SLEEPING ROOMS.
  
 7)NOTE: PLEASE SEE MISSING RECEPTS REQ`D
 PER 210-52.
  
 8)NOTE: PLEASE CHECK KITCHEN COUNTER-
 -SPACE FOR RECEPT SPACING PER 210-52-C1
  
 9)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 TO COLD WATER ALSO PER 250-50
  
 10)NOTE: PLEASE SEE MISSING EGRESS
 LIGHTING PER 210-70 FROM GARAGE DOOR.
  
 11)NOTE: PLEASE SEE 210-8 FOR REQ`D
 GFI RECEPTS IN GARAGE.
  
 PLEASE COMPLETE PLANS PER NEC.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-04-28 Cont ID  
Sent By sthyng Date 2003-04-28 Time 12:54 Rev Time 0.00
Received By sthyng Date 2003-04-28 Time 12:54 Sent To E
Notes
2003-04-28 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-04 Cont ID  
Sent By shernand Date 2003-04-04 Time 10:08 Rev Time 0.00
Received By shernand Date 2003-04-04 Time 10:07 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-19 Cont ID  
Sent By dpalmer Date 2003-02-19 Time 15:31 Rev Time 0.00
Received By dpalmer Date 2003-02-19 Time 15:31 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-05-02 Cont ID  
Sent By kstevens Date 2003-04-29 Time 10:26 Rev Time 0.30
Received By pkrauss Date 2003-05-02 Time 11:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-04-15 Cont ID  
Sent By pkrauss Date 2003-04-15 Time 12:27 Rev Time 0.35
Received By pkrauss Date 2003-04-15 Time 12:09 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-03-11 Cont ID  
Sent By jleech Date 2003-03-03 Time 20:18 Rev Time 0.50
Received By hmoser Date 2003-03-11 Time 19:35 Sent To E
Notes
2003-03-11 00:00:00PLAN DENIED
 1) NO EQUIPMENT SECHEDULE ON PLANS
 2) NO DUCT SIZE FOR RETURN AIR
 3) REFER TO SECTION 402.3.1 2001 FBC.
 (MECHANICAL)
 PLAN REVIEW BY HAROLD MOSER
 (651)659-8096 EXT.8221

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-04-29 Cont ID  
Sent By dpalmer Date 2003-04-29 Time 07:56 Rev Time 0.25
Received By kstevens Date 2003-04-29 Time 10:25 Sent To M
Notes
2003-04-29 00:00:00REVISION REQUIRED FOR RED LINE CHANGES.

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-04-15 Cont ID  
Sent By dpalmer Date 2003-04-09 Time 06:06 Rev Time 0.50
Received By kstevens Date 2003-04-15 Time 08:53 Sent To  
Notes
2003-04-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT A6 SANITARY RISER DIAGRAM DOES
 NOT REFLECT FLOOR PLAN. MASTER BATH HAS
 2 LAVS AND A SHOWER ON THE FLOOR PLAN
 THAT DOES NOT APPEAR ON THE RISER DIA-
 GRAM. - A CLEAN OUT IS REQUIRED ON WASH-
 MACHINE STACK, MIN 4' ABOVE FINISHED
 FLOOR. - TUB DRAINS SHALL TIE INTO BLDG
 DRAIN AND BRANCH DRAIN BELOW SLAB NOT
 ABOVE AS SHOWN.
 2) SHT A6 SANITARY RISER DIAGRAM, KIT-
 CHEN SINK SHALL NOT DRAIN INTO THE WET
 VENT OF THE BATHROOM GROUP. SEC 909.1
 BATHROOM GROUP SHALL BE TAKEN OFF SEPAR-
 ATELY FROM BLDG. DRAIN. (SEE RED LINE
 CORRECTIONS ON PLANS.)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-03-03 Cont ID  
Sent By sgraham Date 2003-02-25 Time 11:29 Rev Time 25.00
Received By jleech Date 2003-03-03 Time 20:18 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-02-25 Cont ID  
Sent By dpalmer Date 2003-02-19 Time 15:31 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***