| 2003-03-18 00:00:00 | DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) THE INFORMATION ON THE ENERGY CALC. |
| | FORM DOES NOT MATCH THE PLANS. SOME OF |
| | THE INFORMATION IS MISSING AT THE TOP OF |
| | THE FORM SUCH AS PROJECT NAME, ADDRESS, |
| | OWNER, ETC. THE BUILDER LISTED ON THE |
| | FORM IS NOT THE SAME ONE THAT IS LISTED |
| | ON THE PERMIT APPLICATION. THE FORM |
| | PREPARER AND THE OWNER/AGENT ARE |
| | REQUIRED TO SIGN AND DATE THE FORM. |
| | |
| | 3) INDICATE THE SIZE OF THE ATTIC ACCESS |
| | IN THE GARAGE. FBC 2309.6 |
| | |
| | 4) THE STRUCTURE IS LOCATED IN AN A-9 |
| | FLOOD ZONE WITH A BASE FLOOD ELEVATION |
| | OF 13 FEET. THE CITY'S FLOOD ORDINANCE |
| | REQUIRES THE STRUCTURES LOWEST FLOOR TO |
| | BE 6" ABOVE BASE FLOOD ELEVATION. |
| | INDICATE MINIMUM FINISH FLOOR ELEVATION |
| | ON PLANS. AN ELEVATION CERTIFICATE WILL |
| | BE REQUIRED. THE FLOOD ZONE LISTED ON |
| | THE SURVEY IS INCORRECT. |
| | |
| | 5) PROVIDE A SOIL BORING TEST REPORT AS |
| | REQUIRED BY FBC 1804.2.2. |
| | |
| | 6) PROVIDE A WINDOW AND DOOR SCHEDULE. |
| | INDICATE TYPES AND SIZES. |
| | |
| | 7) THE PERCENTAGE OF WALL AREA ALLOWED |
| | AS OPENINGS BY FBC TABLE 600 APPEARS TO |
| | BE EXCEEDED AT THE RIGHT SIDE. THE |
| | AREA ALLOWED AS OPENINGS IS 20%. |
| | |
| | 8) INDICATE ADEQUATE ATTIC VENTILATION |
| | AS REQUIRED BY FBC 2309.7. |
| | |
| | 9) PROVIDE EGRESS WINDOWS AT SLEEPING |
| | ROOMS. FBC 1005.4 |
| | |
| | 10) SAFETY GLASS IS REQUIRED IN BATHROOM |
| | WINDOW. FBC 2405.2 |
| | |
| | 11) THE DIMENSIONS GIVEN IN THE FOOTING |
| | NOTES ON A1 DO NOT AGREE WITH THE ONES |
| | ON THE DETAIL. |
| | |
| | 12) PROVIDE A DETAIL OF THE 4" TUBE |
| | STEEL COLUMNS AT THE COVERED ENTRY. |
| | INDICATE THE STEEL THICKNESS, BASE, CAP, |
| | ANCHORS/FASTENERS, WELD TYPE, ETC. |
| | |
| | 13) PROVIDE A BATHROOM WITH A DOOR THAT |
| | HAS A 29" CLEAR OPENING. |
| | |
| | 14) PROVIDE DETAIL AT COVERED ENTRY |
| | INDICATING HOW ROOF WILL BE SUPPORTED. |
| | |
| | 15) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - SLIDING GLASS DOOR (INFORMATION THAT |
| | WAS SUBMITTED IS NOT ACCEPTABLE) |
| | - EXTERIOR WINDOWS |
| | - SINGLE OUTSWING DOOR WITHOUT SIDELITES |
| | |
| | 16) PROVIDE KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR STORM PANELS AND INDICATE |
| | THE SPECIFIC TYPES OF ANCHORS THAT WILL |
| | BE USED. PROVIDE UPDATED COPIES OF SBCCI |
| | PRODUCT APPROVAL FOR STORM PANELS. |
| | (REPORT # 9748A IS THE CURRENT ONE) |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |