| 2003-03-14 00:00:00 | *************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SHOW ALL CIRCUITING FOR |
| | BRANCH WIRING. NOTE MENTIONS SEE HEAD- |
| | BOARD DETAIL FOR CIRCUIT DETAIL? PLEASE |
| | CLARIFY WHERE THIS IS? |
| | |
| | 2)NOTE: PLEASE SEE 220-13 FOR LOADING |
| | OF BRANCH CIRCUITS(KVA PER RECEPT) |
| | PLEASE SEE POWER SHEETS, PLEASE CLARIFY |
| | CIRCUITS WHICH SEEM TO EXCEED LOADING |
| | PERMITTED IN NEC. SOME ARE SHOWN WITH |
| | MORETHAN ONE CIRCUIT? PLEASE EITHER NOTE |
| | ON PLANS: MAX # PERMITTED OR PLEASE |
| | DIVIDE CIRCUITS. |
| | |
| | 3)NOTE: PLEASE CLARIFY RECEPTS REQ`D FOR |
| | ROOFTOP EQUIPMENT. 210-63 |
| | |
| | 4)NOTE: PLEASE SEE DETAILS SHOWN FOR |
| | GROUNDING, PLEASE NOTE, CODES SHOWN ARE |
| | FROM "96" NEC. WE ARE CURRENTLY UNDER |
| | THE 99 NEC. PLEASE CORRELATE. |
| | PLEASE ALSO SHOW COLD WATER PIPE AS |
| | PART OF THE GROUNDING ELECTRODE SYSTEM. |
| | 250-50/250-32 |
| | |
| | 5)NOTE: PLEASE SEE 225-31 FOR MEANS OF |
| | DISCONNECT REQ`D COMING FROM GENERATOR |
| | TO MAIN BLDG. PLEASE SEE 230-76/ 230-79 |
| | FOR DISCONNECTING REQUIREMENTS. PLEASE |
| | NOTE, THAT SHUNT TRIPS WILL NOT BE |
| | PERMITTED BY THE AHJ. |
| | PLEASE ALSO PROVIDE INFORMATION WHERE |
| | 2HR FIRE RATED SEPARATION FORM EXISTING |
| | BLDG W/ EXISTING ELECTRICAL SERVICE |
| | IS FED FROM. PLEASE NOTE COMPLETE |
| | SEPARATION OF THESE NEW AND OLD WILL BE |
| | REQ`D DUE TO FACT THEY ARE FED FROM TWO |
| | SEPARATE ELECTRICAL SERVICES. PLEASE |
| | ALSO NOTE, LABELING AND COMPLETE SIGNAGE |
| | WILL BE REQ`D W/ A MIN OF 1" LETTERING |
| | ON A CONTRASTING BACKGROUND. |
| | |
| | 6)NOTE: PLEASE ALSO SEE 96 NEC REF |
| | ON LINE DIAGRAM. |
| | |
| | 7)NOTE: PLEASE SEE SIZING SHOWN FOR |
| | TRANSFER SWITCH "LS", MISPRINT AT 260A`S |
| | |
| | 8)NOTE: PLEASE CLARIFY 3000A SWITCHBOARD |
| | W/TWO 1600A MAINS? 3200A? PLEASE CLARIFY |
| | HOW MAINS CNA EXCEED RATING OF SWITCH- |
| | -BOARD? |
| | |
| | 9)NOTE: PLEASE CORRELATE RISER DIAGRAM |
| | AND SW BRD ES-1. CRBR SHOWS 600A ON |
| | RISER AND 800A ON PANEL SCHEDULE. |
| | |
| | 10)NOTE: PLEASE COMPLETE RISER DIAGRAM |
| | W/ ALL CONDUIT AND WIRE SIZES. PLEASE |
| | SUBMIT A FEEDER SCHEDULE, SEEMS TO HAVE |
| | #`S ON RISER?? SUBMIT ALL WIRE SIZES ON |
| | PANEL SCHEDULES ALSO. |
| | 11)NOTE: PLEASE COMPLETE LOAD CALCULAT- |
| | -IONS. PLEASE SHOW FINAL AMPERAGE ON |
| | EACH PANEL AND ON MAIN SERVICE. |
| | PLEASE SHOW LOAD CALC PER 220-3,220-10 |
| | 220-11,220-13, PLEASE ALSO SHOW ALL |
| | CONTINUOUS LOADS AT 125% 215-3/230-42ETC |
| | |
| | 12)NOTE: PLEASE PROVIDE GROUNDING FOR |
| | ALL TRANSFORMERS PER 250-30 |
| | PLEASE SHOW DETAIL. |
| | |
| | 13)NOTE: PLEASE SEE RISER DIAGRAM, |
| | 1CHEM1, SHOWS THREE TRANSFORMERS FEEDING |
| | TWO PANELS? 2-45 KVA'S AND ONE 75KVA TO |
| | THE SAME PANEL? PLEASE CLARFIY HOW TWO |
| | X-FORMERS ARE FEEDING ONE PANEL. PLEASE |
| | ALSO CLARIFY PANEL SCHEDULE. |
| | |
| | 14)NOTE: PLEASE SUBMIT ALL PANEL |
| | SCHEDULES, SOME ARE MISSING. |
| | |
| | 15)NOTE: PLEASE SEE PANEL 1 ELEM1, OTHER |
| | PANSL SHOWN ON SECONDARY SIDE OF X-FORM- |
| | -ERS ? 240-21/384-16 |
| | |
| | PLEASE NOTE A COMPLETE PLAN REVIEW CAN |
| | NOT BE DONE AT THIS TIME. PLEASE SUBMIT |
| | THE ABOVE INFORMATION FOR REVIEW AND |
| | PLEASE ALSO NOTE THERE MAY BE FURTHER |
| | COMMENTS AFTER INFORMATION FOR REVIEW |
| | IS SUBMITTED. |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |
| | |
| | PLEASE NOTE, IN ADDTION TO ABOVE COMMENT |
| | -S , PLEASE ALSO SEE 571-17 FOR GFI |
| | PROTECTION. |