Plan Review Details - Permit 03021082
Plan Review Stops For Permit 03021082
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-07-09 Cont ID  
Sent By hpiskura Date 2003-07-09 Time 11:23 Rev Time 0.00
Received By hpiskura Date 2003-07-09 Time 11:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-05-13 Cont ID  
Sent By hpiskura Date 2003-05-13 Time 13:02 Rev Time 0.00
Received By hpiskura Date 2003-05-13 Time 12:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-03-01 Cont ID  
Sent By hpiskura Date 2003-03-01 Time 09:58 Rev Time 0.00
Received By hpiskura Date 2003-03-01 Time 09:04 Sent To  
Notes
2003-03-01 00:00:00THE EXIT ACCESS CORRIDOR SHOWN AS "HALL"
 ON THE PLANS IS REQUIRED TO BE ONE HOUR
 FIRE RATED IN ACCORDANCE WITH FBC
 704.2.4.PLEASE REVISE AS NECESSARY.
  
 PROVIDE A SPECIFIC FRAMING AND FASTENING
 DETAIL FOR THE SUSPENDED LOBBY SOFFIT
 SHOWN ON SHEET A1.3.SEE FBC 104.2.
  
 SHOW THE WIND PRESSURE FOR THE NEW
 EXTERIOR WINDOWS AND STOREFRONT SYSTEM.
 SEE FBC 1606.1.7
  
 SOME OF THE DOORS SWINGING INTO THE
 CORRIDOR IE; ROOM 140A AND 134, DO NOT
 COMPLLY WITH FBC 1012.1.4.
  
 SHOW SAFETY GLASS FOR THE INTERIOR
 GLAZING ADJACENT TO THE DOORS AS
 PROVIDED FOR IN FBC 2405.2.1 #3.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2003-10-20 Cont ID  
Sent By dpalmer Date 2003-10-20 Time 08:57 Rev Time 0.50
Received By dpalmer Date 2003-10-20 Time 08:04 Sent To  
Notes
2003-10-20 00:00:00************ UNSAT *****************
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002,
 PLEASE SEE MISSING CA #.
 PLEASE ALSO SEE THAT ONE SET OF PLANS
 ARE NOT SEALED AND DATED. THEY APPEAR
 TO BE SIGNED ONLY.
 FS 471.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-08-04 Cont ID  
Sent By csiegber Date 2003-10-15 Time 14:07 Rev Time 0.25
Received By dpalmer Date 2003-08-04 Time 11:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-07-03 Cont ID  
Sent By alange Date 2003-07-30 Time 11:36 Rev Time 0.50
Received By dpalmer Date 2003-07-03 Time 06:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-05-12 Cont ID  
Sent By dpalmer Date 2003-05-12 Time 13:36 Rev Time 0.75
Received By dpalmer Date 2003-05-12 Time 12:40 Sent To  
Notes
2003-05-12 00:00:00*********** PROVSIO/NOTE***********
  
 PLEASE SEE NOTE FROM FIRST REVIEW.
 PLEASE SHOW LOAD CALCS AND SHOW CONT
 @ 125%
  
 PLEASE REVISE LOAD CALCS BEFORE ROUGH.
  
 IF THERE ARE ANY QUESTION, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-03-04 Cont ID  
Sent By dpalmer Date 2003-03-04 Time 16:37 Rev Time 0.75
Received By dpalmer Date 2003-03-04 Time 16:34 Sent To  
Notes
2003-03-04 00:00:00*************** UNSAT ****************
  
  
 1)NOTE: PLAN E-1 SHOWS SECONDARY METHOD
 OF FEEDING MDP. PLEASE SHOW ON RISER
 THIS METHOD AS OPT.
  
 2)NOTE: PLEASE SUBMIT AIC RATING FOR
 NEW 800A MAIN DISC. 110-9
  
 3)NOTE: PLEASE SHOW LOAD CALCUALTIONS
 AND SHOW ALL CONTINUOUS LOADS AT 125%
 INCLUDING LIGHTING LOADS. 215-3/230-42
 ETC.
  
  
 4)NOTE: PLEASE SHOW FEEDER AND CONDUIT
 SIZE FROM MAIN TO MDP.
  
 PLEASE ALSO SEE FIRE REVIEW COMMENTS
 THAT WILL AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-07-09 Cont ID  
Sent By nmccray Date 2003-07-09 Time 11:52 Rev Time 0.00
Received By nmccray Date 2003-07-09 Time 11:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-06-05 Cont ID  
Sent By nmccray Date 2003-06-05 Time 15:05 Rev Time 0.00
Received By nmccray Date 2003-06-05 Time 15:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-02-26 Cont ID  
Sent By nmccray Date 2003-02-26 Time 13:40 Rev Time 0.00
Received By nmccray Date 2003-02-26 Time 13:39 Sent To  
Notes
2003-02-26 00:00:001) DOORS (140A & 140C) MUST COMPLY WITH
 CHAPTER 7.2.1.4 OF NFPA 101 LIFE SAFETY
 CODE 2000 EDITION.
  
 2) BOARDROOM OCCUPANT LOAD MUST COMPLY
 WITH CHAPTER 7.3.1.2 OF NFPA 101 LIFE
 SAFETY CODE 2000 EDITION.
  
 3) SEPARATE PLAN AND PERMIT ARE REQUIRED
 FOR FIRE ALARM SYSTEM.
  
 4) ADDITIONAL HORN/STROBE MAYBE NEEDED
 IN HALL 150.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT 8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 7 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By csiegber Date 2003-10-15 Time 14:07 Sent To  
Notes
2003-10-15 00:00:00TO DP DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-10-15 Cont ID  
Sent By csiegber Date 2003-10-15 Time 09:32 Rev Time 0.00
Received By csiegber Date 2003-10-15 Time 09:32 Sent To M
Notes
2003-10-15 00:00:00TO HAROLD MOSER DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-07-30 Cont ID  
Sent By alange Date 2003-07-30 Time 11:36 Rev Time 0.00
Received By alange Date 2003-07-30 Time 11:36 Sent To E
Notes
2003-07-30 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-07-09 Cont ID  
Sent By shernand Date 2003-07-09 Time 14:32 Rev Time 0.00
Received By shernand Date 2003-07-09 Time 14:32 Sent To Z
Notes
2003-07-09 00:00:00REMOVED FROM BOARD, GAVE TO ZONING.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-18 Cont ID  
Sent By shernand Date 2003-06-18 Time 16:53 Rev Time 0.00
Received By shernand Date 2003-06-18 Time 16:53 Sent To  
Notes
2003-06-18 00:00:00COMM BOARD #46

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-07 Cont ID  
Sent By shernand Date 2003-05-07 Time 13:38 Rev Time 0.00
Received By shernand Date 2003-05-07 Time 13:38 Sent To  
Notes
2003-05-07 00:00:00COMM BOARD #25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-26 Cont ID  
Sent By dpalmer Date 2003-02-26 Time 14:20 Rev Time 0.00
Received By dpalmer Date 2003-02-26 Time 14:20 Sent To  
Notes
2003-02-26 00:00:00TO #15 ON COMM BOARD.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2003-10-29 Cont ID  
Sent By hmoser Date 2003-10-29 Time 17:17 Rev Time 0.75
Received By hmoser Date 2003-10-29 Time 17:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-10-22 Cont ID  
Sent By hmoser Date 2003-10-22 Time 16:41 Rev Time 0.50
Received By hmoser Date 2003-10-22 Time 16:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-07-07 Cont ID  
Sent By csiegber Date 2003-10-15 Time 09:32 Rev Time 0.40
Received By pkrauss Date 2003-07-07 Time 06:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-05-13 Cont ID  
Sent By pkrauss Date 2003-05-13 Time 14:56 Rev Time 0.50
Received By pkrauss Date 2003-05-13 Time 14:47 Sent To  
Notes
2003-05-13 00:00:00DENIED:
  
 REVISED PLAN INDICATES THE PENETRATION
 BETWEEN 132A & 131 HAS A 1 HR RATING.
 PLEASE PROVIDE FIRE DAMPER ON THE 20" X
 16" SUPPLY DUCT AND THE 18" X 16" RETURN
 DUCT.ALSO SUPPLY & RETURN DUCTS AT THE
 MENS RM (135).PLEASE NOTE AS PER
 2001 FBC(M) 607.1.3 #3. 1-4 EXCEPTIONS,
 DUCTS SHALL MEET ALL REQUIREMENTS IN
 ITEMS 1-4 UNDER ITEM 3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-03-04 Cont ID  
Sent By pkrauss Date 2003-03-04 Time 09:17 Rev Time 1.00
Received By pkrauss Date 2003-03-03 Time 15:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-07-02 Cont ID  
Sent By kstevens Date 2003-07-02 Time 12:29 Rev Time 0.75
Received By kstevens Date 2003-07-02 Time 12:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-05-29 Cont ID  
Sent By kstevens Date 2003-05-29 Time 18:24 Rev Time 1.00
Received By kstevens Date 2003-05-29 Time 18:24 Sent To  
Notes
2003-05-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A1.0 UNABLE TO LOCATE SERVICE
 SINK INDICATED IN CODE ANALYSIS AND RE-
 VIEW "E". PLEASE INDICATE LOCATION.
 SERVICE SINK USED TO MOP FLOORS AND
 GENERAL CLEAN-UP.
 2) SHT A1.0 IF URNALS ARE PROVIDED THEN
 AT LEAST ONE SHALL COMPLY WITH 11-4.18.
 SUBMIT DETAILS THAT SHOW HEIGHT 11-4.18.
 2, CLEAR FLOOR SPACE 11-4.18.3, FLUSH
 CONTROLS 11-4.18.4.
 3) SHT A1.0 PLEASE SUBMIT DETAILS FOR
 SHOWER IN COMPLIANCE WITH 11-4.21 AND
 ALL SUBSECTIONS. 11-4.21.4 GRAB BARS,
 11-4.21.5 CONTROLS, 11-4.21.6 SHOWER
 UNIT, & 11-4.21.7 CURBS.
 4) SHT A1.0 SINKS IN ROOMS #141 & 143,
 SHOW CLEAR FLOOR SPACE AS REQUIRED IN
 SECTION 11-4.24.5.
 5) SHTS P-1, P-2, & P-3 RELIEF VALVE
 DISCHARGE PIPE STILL SHOWS BEING TRAPPED
 SECTION 504.7.1
 6) PER FBC ADMINISTRATIVE CODE, CHAPTER
 1 AND AMENDMENTS SECTION 104.2.1TWO OR
 MORE COPIES OF SPECIFICATIONS AND OF
 DRAWINGS DRAWN TO SCALE WITH SUFFICIEDN
 CLAIRTY AND DETAIL TO INDICATE THE NAT-
 URE AND CHARACTER OF THE WORK SHALL
 ACCOMPANY THE APPLICATION FOR PERMIT.
 SUCH INFORMATION SHALL BE SPECIFIC, AND
 THE TECHNICAL CODES SHALL NOT BE CITED
 AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-03-11 Cont ID  
Sent By kstevens Date 2003-03-11 Time 11:02 Rev Time 1.50
Received By kstevens Date 2003-03-11 Time 11:02 Sent To  
Notes
2003-03-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-1.0 UNABLE TO FIND DRINKING
 FOUNTAINS AND SERVICE SINK REFERED TO IN
 CODE REVIEW AND ANALYSIS"E".
 2) SHT A-1.0 IF TOILET ROOM ARE PROVIDED
 THEN EACH PUBLIC AND COMMON USE TOILET
 ROOM SHALL COMPLY WITH 11-4.22. IF BATH-
 ING ARE PROVIDED, THEN EACH PUBLIC AND
 COMMON USE BATHROOM SHALL COMPLY WITH
 11-4.23 - PLEASE SHOW DETAILS FOR EACH
 TOILET ROOM AND BATHROOM PER THESE SECT-
 IONS AND ALL SUBSECTIONS.
 3) SHT A-1.0 IF TOILET STALLS ARE PRO-
 VIDED, THEN AT LEAST ON SHALL BE A
 STANDARD TOILET STALL COMPLYING WITH
 11-4.17. SEC 11-4.22.4
 4) SHT A-1.0 IF URNALS ARE PROVIDED THEN
 AT LEAST ONE SHALL COMPLY WITH 11-4.18
 AND ALL SUBSECTIONS.
 5) SHT A-1.01 PLEASE SUBMIT DETAILS FOR
 SHOWER IN COMPLIANCE WITH 11-4.21 AND
 ALL SUBSECTIONS.
 6) SHT A-1.0 ALL DOORS SHALL NOT SWING
 INTO THE CLEAR FLOOR SPACE OF ANY FIX-
 TURE. ALSO 5' TURNING CIRCLE SHALL BE
 UNOBSTRUCTED.
 7) SHT A-1.0 SINKS IN ROOMS #141 & 143
 SHALL COMPLY WITH 11-4.24 AND ALL SUB-
 SECTIONS. PLEASE PROVIDE DETAILS.
 8) SHT P-1 RELIEF VENTS REQUIRED AS
 CONDENSATE LINES EXIT BLDG. - CONDENSATE
 SHALL DRAIN OUTSIDE BLDG SEPARATE FROM
 STORM. (SEE ROOM #134) PLEASE CLAIRFY.
 9) SHT P-1 KEYNOTE #6. MANUF INFORMATION
 REQUIRED.
 10) SHT P-2 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS REQUIRED AT ICE MAKERS
 (REFRIDGERATORS) SEC 406.9
 11) SHTS P-1, P-2, & P-3 RELIEF VALVE
 (P/T) FROM WATER HEATER SHALL NOT BE
 TRAPPED. SEC 504.7.1
 12) SEPARATE PERMIT REQD FOR IRRIGATION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2003-07-14 Cont ID  
Sent By shernand Date 2003-07-09 Time 14:32 Rev Time 0.00
Received By shernand Date 2003-07-14 Time 15:56 Sent To  
Notes
2003-07-14 00:00:00SGRAHAM PASSED