Review Stop P PLUMBING
Rev No 1 Status P Date 2003-03-03 Cont ID  
Sent By kstevens Date 2003-03-03 Time 07:33 Rev Time 0.75
Received By kstevens Date 2003-03-03 Time 07:33 Sent To  
Notes
2003-03-03 00:00:00PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.
  
  
 DRYER ROOM IS A CONFINED SPACE - 1,100
 CUBIC FEET REQUIRED FOR 22,000 BTU'S -
 569 CUBIC FEET PROVIDED - 2 OPENINGS
 ARE REQUIRED PER SECTION 304.3.1