Plan Review Details - Permit 03020523
Plan Review Stops For Permit 03020523
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-11 Cont ID  
Sent By dpalmer Date 2003-02-11 Time 11:56 Rev Time 0.00
Received By dpalmer Date 2003-02-11 Time 11:56 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-02-14 Cont ID  
Sent By pschmitz Date 2003-02-14 Time 15:57 Rev Time 0.66
Received By pschmitz Date   Time   Sent To  
Notes
2003-02-14 00:00:00REVISION, APPR, PES.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-02-07 Cont ID  
Sent By dpalmer Date 2003-02-11 Time 11:56 Rev Time 0.33
Received By kstevens Date 2003-02-07 Time 13:19 Sent To  
Notes
2003-02-07 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 2. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304. DRYER REQUIRES
 1,100 CU. FT. OF SPACE OR OPENINGS SHALL
 BE REQUIRED PER SECTION 304.3.1. MIN.
 100 SQ. IN. OPENINGS.
 3. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377