Plan Review Details - Permit 03020458
Plan Review Stops For Permit 03020458
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-03-24 Cont ID  
Sent By rmcdouga Date 2003-03-24 Time 10:00 Rev Time 3.00
Received By rmcdouga Date 2003-03-24 Time 10:00 Sent To  
Notes
2003-03-24 00:00:00PROVISO
  
 1) SUBMIT A SOIL BORING TEST REPORT AS
 REQUIRED BY FBC 1804.1.
  
 2)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - OUTSWING GLAZED DOUBLE DOORS WITH
 SIDELITES.
 - OUTSWING GLAZED SINGLE DOOR
 - OVAL FIXED GLASS WINDOW
  
 3) SUBMIT THE SBCCI ESI REPORT FOR THE
 STORM PANELS THAT ACCOMPANIES THE
 DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-03-03 Cont ID  
Sent By btrobaug Date 2003-03-21 Time 17:19 Rev Time 4.00
Received By rmcdouga Date 2003-03-03 Time 17:09 Sent To  
Notes
2003-03-03 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PROVIDE A SOIL BEARING TEST REPORT AS
 REQUIRED BY FBC 1804.1.1.
  
 4) REVISE CONSTRUCTION TYPE TO VI UNDER
 GENERAL NOTES ON C1.
  
 5) INDICATE THE INTERNAL PRESSURE
 COEFFICENT WITH THE DESIGN CRITERIA ON
 C1. SEE FBC 1606.1.7.
  
 6) THE BOLLARD NOTE ON A2 REFERS TO
 DETAIL #54. THIS DETAIL DOES NOT APPEAR
 ON THE PLANS.
  
 7) SPECIFY ON THE PLANS THAT THE DOOR
 BETWEEN THE GARAGE AND THE CONDITIONED
 SPACE IS A SOLID CORE OR INSULATED STEEL
 DOOR AS REQUIRED BY FBC CHAPTER 13. ALSO
 INDICATE THAT THIS WALL IS INSULATED ON
 THE PLANS.
  
 8) THE EXTERIOR WALLS ARE INCORRECTLY
 LISTED AS WOOD FRAME ON THE ENERGY
 CALCULATIONS.
  
 9) THE DETAILS ON A4 ARE MISLABELED AS
 A3.
  
 10) INDICATE AT THE SLIDING GLASS DOOR
 BUCK DETAIL ON A4 THAT THE ANCHORS ARE
 REQUIRED TO BE FASTENED THROUGH BUCKS
 LESS THAN 1-1/2" AND INTO THE SUBSTRATE.
 SEE FBC 1707.4.4.2.
  
 11) ON SHEET A6 TWO DETAILS ARE LABELED
 AS #1. ONE OF THEM SHOULD BE #7. PLEASE
 CORRECT.
  
 12) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - DOUBLE OUTSWING FRENCH DOORS WITH
 SIDELITES ASSEMBLY.
 - SINGLE OUTSWING FRENCH DOOR
  
 13) THE GLASS BLOCK SIZE SPECIFIED ON
 THE PLANS EXCEEDS THE MAXIMUM SIZE
 ALLOWED BY THE PRODUCT APPROVAL THAT WAS
 SUBMITTED.
  
 14) SUBMIT THE MANUFACTURER'S SPECS. AND
 UL LISTING INFORMATION FOR THE ONE HOUR
 FIRE RATED GLASS BLOCK.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-03-21 Cont ID  
Sent By btrobaug Date 2003-03-21 Time 17:19 Rev Time 0.50
Received By btrobaug Date 2003-03-21 Time 17:08 Sent To B
Notes
2003-03-21 00:00:00TO ROB M./WRT

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-02-25 Cont ID  
Sent By sthyng Date 2003-03-18 Time 16:47 Rev Time 0.50
Received By btrobaug Date 2003-02-25 Time 07:09 Sent To B
Notes
2003-02-25 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 TO THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SIZE THE GROUNDING ELECTRODE
 CONDUCTOR PER 250-66.(400 AMPS=400 MCM
 PER 310-15(B)(6),400 MCM= 1/0 CU PER
 250-66)
  
 2} PLEASE PROVIDE A PANEL SCHEDULE FOR
 PANEL "B" AND SHOW LOCATION ON DRAWING.
  
 3} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 4} THE LAUNDRY CIRCUIT IS INCORRECTLY
 CALCULATED AT 1.0 KVA. THIS CIRCUIT IS
 REQUIRED TO BE 1500 VA MINIMUM PER
 220-16(B).
  
 5} PLEASE NOTE THAT SMOKE DETECTORS ARE
 NOT TO BE LOCATED WITHIN 3'OF THE
 KITCHEN PER 8-1.4.2 NFPA-72.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-18 Cont ID  
Sent By sthyng Date 2003-03-18 Time 16:47 Rev Time 0.00
Received By sthyng Date 2003-03-18 Time 16:47 Sent To E
Notes
2003-03-18 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-06 Cont ID  
Sent By dpalmer Date 2003-02-06 Time 17:16 Rev Time 0.00
Received By dpalmer Date 2003-02-06 Time 17:16 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-02-22 Cont ID  
Sent By jleech Date 2003-02-19 Time 20:16 Rev Time 0.50
Received By hmoser Date 2003-02-22 Time 12:58 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-02-19 Cont ID  
Sent By sgraham Date 2003-02-07 Time 16:14 Rev Time 0.25
Received By jleech Date 2003-02-19 Time 20:15 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-02-07 Cont ID  
Sent By dpalmer Date 2003-02-06 Time 17:16 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***