Plan Review Details - Permit 03020452
Plan Review Stops For Permit 03020452
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-03-24 Cont ID  
Sent By shernand Date 2003-05-06 Time 08:51 Rev Time 3.00
Received By rmcdouga Date 2003-03-24 Time 08:34 Sent To  
Notes
2003-03-24 00:00:00PROVISO
  
 1) SUBMIT A SOIL BORING TEST REPORT AS
 REQUIRED BY FBC 1804.1.1.
  
 2) SUBMIT THE MANUFACTURER'S SPECS. AND
 LISTING INFORMATION FOR THE ONE HOUR
 FIRE RATED GLASS BLOCK.
  
 3) SUBMIT THE ESI REPORT FOR THE STORM
 PANELS TO ACCOMPANY THE DRAWINGS THAT
 WERE SUBMITTED.
  
 4) SUBMIT (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - DOUBLE OUTSWING GLAZED DOORS WITH
 SIDELITES
 - SINGLE OUTSWING GLAZED DOOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-02-28 Cont ID  
Sent By dpalmer Date 2003-03-21 Time 08:57 Rev Time 4.00
Received By rmcdouga Date 2003-02-28 Time 08:37 Sent To  
Notes
2003-02-28 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PROVIDE A SOIL BORING TEST REPORT AS
 REQUIRED BY FBC 1804.1.1.
  
 4) PLEASE REVISE #1 UNDER GENERAL NOTES
 ON C-1. THE CONSTRUCTION IS TYPE VI.
  
 5) INDICATE THE INTERNAL PRESSURE
 COEFFICENT WITH THE DESIGN CRITERIA ON
 C-1. SEE FBC 1606.1.7.
  
 6) THE CONNECTION DETAIL 7 ON A-6 IS
 MISLABELED AS 1 ON A-6. PLEASE CORRECT.
  
 7) ON A-2 DETAIL 15 IS INCORRECTLY
 SPECIFIED FOR FOOTING TE-1. PLEASE
 CORRECT.
  
 8) THE NOTE AT THE BOLLARD ON A-2 REFERS
 TO DETAIL #54. THIS DETAIL DOES NOT
 APPEAR TO BE ON THE DRAWINGS.
  
 9) THE ENERGY CALCULATIONS LIST THE
 EXTERIOR WALLS AS WOOD FRAME AND THE
 PLANS INDICATE CBS. PLEASE CORRECT.
  
 10) SPECIFY THAT THE DOOR BETWEEN THE
 GARAGE AND CONDITIONED SPACE IS SOLID
 CORE.
  
 11) INDICATE ON THE PLANS THAT THE WALL
 BETWEEN CONDITIONED SPACE AND THE
 GARAGE IS INSULATED.
  
 12) REVISE THE SLIDING GLASS DOOR DETAIL
 ON A-4 TO INDICATE THAT THE ANCHORS ARE
 REGUIRED TO BE FASTENED THROUGH BUCKS
 LESS THAN 1-1/2" THICK AND INTO THE
 CONCRETE SUBSTRATE. SEE FBC 1707.4.4.2.
  
 13) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - DOUBLE FRENCH DOOR WITH SIDELITES
 ASSEMBLY
 - SINGLE FRENCH DOOR
  
 14) THE PRODUCT APPROVAL FOR THE GLASS
 BLOCK LIMITS THE OPENING SIZE TO A
 MAXIMUM OF 6'X6'. THE OPENING SIZE IS
 GIVEN AS 6'8"X 6' ON A-1. PLEASE CORRECT
  
 15) THE FRONT ELEVATION SHOWS TWO OVAL
 WINDOWS AT THE DEN AND THE FLOOR PLAN ON
 A-3 SPECIFIES SINGLE HUNG WINDOWS.
 PLEASE CLARIFY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-03-21 Cont ID  
Sent By dpalmer Date 2003-03-21 Time 08:57 Rev Time 0.50
Received By dpalmer Date 2003-03-21 Time 08:57 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-02-26 Cont ID  
Sent By sthyng Date 2003-03-19 Time 09:06 Rev Time 0.25
Received By dpalmer Date 2003-02-26 Time 06:42 Sent To B
Notes
2003-02-26 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE LIST THE REQ`D BATH
 CIRCUIT PER 210-52D/ 210-11-C-3
 20A/#12
  
 2)NOTE: PLEASE SEE MIN SIZE FOR WASHER
 PER 220-16B
  
 3)NOTE: PLEASE SEE NFPA-72 8-1.4.2
 SD NOT PERMITTED IN KITCHEN. IF INSTALL-
 ED, MUST BE A MIN OF 3' AWAY
  
 4)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 PER MIN SERVICE ENTRANCE CONDUCTORS
 250-66. SHOWN AS 400A SERVICE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-05-06 Cont ID  
Sent By shernand Date 2003-05-06 Time 08:51 Rev Time 0.00
Received By shernand Date 2003-05-06 Time 08:51 Sent To B
Notes
2003-05-06 00:00:00RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-04-28 Cont ID  
Sent By sthyng Date 2003-04-28 Time 09:42 Rev Time 0.00
Received By sthyng Date 2003-04-28 Time 09:42 Sent To B
Notes
2003-04-28 00:00:00TO RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-19 Cont ID  
Sent By sthyng Date 2003-03-19 Time 09:06 Rev Time 0.00
Received By sthyng Date 2003-03-19 Time 09:06 Sent To E
Notes
2003-03-19 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-10 Cont ID  
Sent By dpalmer Date 2003-02-10 Time 10:46 Rev Time 0.00
Received By dpalmer Date 2003-02-10 Time 10:46 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-02-22 Cont ID  
Sent By jleech Date 2003-02-19 Time 19:09 Rev Time 0.50
Received By hmoser Date 2003-02-22 Time 12:47 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-02-19 Cont ID  
Sent By sgraham Date 2003-02-11 Time 07:55 Rev Time 0.25
Received By jleech Date 2003-02-19 Time 19:09 Sent To M
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2003-05-06 Cont ID  
Sent By rmcdouga Date 2003-05-06 Time 09:17 Rev Time 0.50
Received By rmcdouga Date 2003-05-06 Time 09:16 Sent To  
Notes
2003-05-06 00:00:00REVISION IS THE SAME AS THE ONE THAT WAS
 OKED ON 4-28-03. BOTH SETS OF DRAWINGS
 THAT WERE SUBMITTED WERE RETURNED TO
 THE CONTRACTOR UNSTAMPED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2003-04-28 Cont ID  
Sent By rmcdouga Date 2003-04-28 Time 17:53 Rev Time 1.00
Received By rmcdouga Date 2003-04-28 Time 17:53 Sent To  
Notes
2003-04-28 00:00:00REVISION TO ELIMINATE (2) WINDOWS IS
 OK

Review Stop Z ZONING
Rev No 1 Status P Date 2003-02-11 Cont ID  
Sent By dpalmer Date 2003-02-10 Time 10:46 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***