Plan Review Details - Permit 03020451
Plan Review Stops For Permit 03020451
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-04-23 Cont ID  
Sent By shernand Date 2003-05-29 Time 16:54 Rev Time 3.00
Received By sthyng Date 2003-04-22 Time 18:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-02-28 Cont ID  
Sent By hpiskura Date 2003-02-28 Time 13:27 Rev Time 0.00
Received By hpiskura Date 2003-02-28 Time 11:36 Sent To  
Notes
2003-02-28 00:00:00PAID PLAN REVIEW NOT A PERMIT
 APPLICATION
  
  
 THE ATTIC ACCESS IS NOT SHOWN AS
 REQUIRED BY FBC 2309.6
  
 THIS BUILDING WILL BE LOCATED IN AN AO
 FLOOD ZONE.SHOW THE FINISH FLOOR
 REALTIVE TO NGVD 1929.
  
 HOW WERE THE WIND DESIGN PRESSURES
 DETERMINED?WAS THE BUILDING DESIGNED
 AS ENCLOSED OR PARTIALLY ENCLOSED?SEE
 FBC 1606.1.1 AND NOTE IF 1606.2, ASCE
 7-98 SECTION 6.5 WAS USED.
  
 HOW WAS THE ROOF TILE NAILING SPECIFIED
 ON SHEET AM 11 DETERMINED?SEE FBC
 1507.4 AND FBC 1606.3.2.
  
 1

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2004-03-03 Cont ID  
Sent By dpalmer Date 2004-03-03 Time 06:44 Rev Time 0.50
Received By dpalmer Date 2004-03-03 Time 06:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2004-02-25 Cont ID  
Sent By dpalmer Date 2004-02-25 Time 09:02 Rev Time 0.75
Received By dpalmer Date 2004-02-25 Time 09:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2004-02-19 Cont ID  
Sent By dpalmer Date 2004-02-19 Time 16:31 Rev Time 0.33
Received By dpalmer Date 2004-02-19 Time 16:31 Sent To  
Notes
2004-02-19 00:00:00*********** ON HOLD **************
  
 ** CALLED, MR ROMAN AT ENGINEERS OFFICE,
 IN REF TO OCP FOR AHU.
 NEW SHEET TO BE ISSUED.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-02-12 Cont ID  
Sent By dpalmer Date 2004-02-12 Time 06:33 Rev Time 0.33
Received By dpalmer Date 2004-02-12 Time 06:24 Sent To  
Notes
2004-02-12 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE SEE OCP SHOWN FOR 9KW
 AHU HEAT. SHOWN AT 45A'S, PLEASE VERIFY
 KW RATING AND PLEASE SEE 424.3B FOR
 MIN OCP TO BE 125%.
  
 2)NOTE: PLEASE SEE AHU, SHOWS A "J" BOX
 WHERE A DISC IS REQ'D PER 440.11.
 PLEASE INDICATE DISC MEANS.
  
 3)NOTE: PLEASE INDICATE CONDUCTORS FROM
 METER TO MAINS AND FROM MAIN TO PANEL.
 310.16
  
 4)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO PANEL.
 250.110,250.24, SIZE PER 250.122
 PLEASE ALSO INDICATE COLD WATER AS PART
 OF GROUNDING ELECTRODE SYSTEM. 250.50
 (IF METAL/COPPER).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-08-14 Cont ID  
Sent By csiegber Date 2004-02-06 Time 09:02 Rev Time 0.50
Received By btrobaug Date 2003-08-14 Time 12:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-04-17 Cont ID  
Sent By dbaxter Date 2003-08-12 Time 12:52 Rev Time 0.75
Received By dpalmer Date 2003-04-17 Time 13:00 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-02-26 Cont ID  
Sent By dpalmer Date 2003-02-26 Time 13:09 Rev Time 0.25
Received By dpalmer Date 2003-02-26 Time 13:08 Sent To  
Notes
2003-02-26 00:00:00*********** UNSAT *************
  
 1)NOTE: PLEASE ONLY SUBMIT PLANS
 PERTAINING TO THE CABANNA.
  
 2)NOTE: PLEASE SHOW ALL CONTINUOUS
 LOADS AT 125% 215-3,230-42
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2003-02-10 Cont ID  
Sent By mamini Date 2003-02-10 Time 09:04 Rev Time 0.50
Received By mamini Date 2003-02-10 Time 09:04 Sent To  
Notes
2003-02-10 00:00:00PASSED:
 1. SEE PERMIT # 02121237 FOR UNDERGROUND
 UTILITIES AND SITE WORKS.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-04-18 Cont ID  
Sent By nmccray Date 2003-04-18 Time 14:35 Rev Time 0.00
Received By nmccray Date 2003-04-18 Time 14:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-03-11 Cont ID  
Sent By nmccray Date 2003-03-11 Time 14:54 Rev Time 0.00
Received By nmccray Date 2003-03-11 Time 14:54 Sent To  
Notes
2003-03-11 00:00:001) ACCESS CONTROLLED EGRESS DOORS MUST
 COMPLY WITH CH 7.2.1.6.2 OF NFPA 101
 LIFE SAFETY CODE 2000 EDITION.
  
 2) PLEASE INDICATE AS TO WHAT WILL BE
 STORED IN THE STORAGE ROOM.
  
 3) SEPARATE PLAN AND PERMIT REQUIRED FOR
 THE FIRE ALARM SYSTEM.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT 8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-02-06 Cont ID  
Sent By csiegber Date 2004-02-06 Time 09:02 Rev Time 0.00
Received By csiegber Date 2004-02-06 Time 09:02 Sent To E
Notes
2004-02-06 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-10-17 Cont ID  
Sent By csiegber Date 2003-10-17 Time 12:59 Rev Time 0.00
Received By csiegber Date 2003-10-17 Time 12:59 Sent To M
Notes
2003-10-17 00:00:00TO PK BOX/A/C REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-08-12 Cont ID  
Sent By dbaxter Date 2003-08-12 Time 12:52 Rev Time 0.00
Received By dbaxter Date 2003-08-12 Time 12:52 Sent To E
Notes
2003-08-12 00:00:00TO ELEC. BOX

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-07-28 Cont ID  
Sent By alange Date 2003-07-28 Time 07:58 Rev Time 0.00
Received By alange Date 2003-07-28 Time 07:58 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-05-29 Cont ID  
Sent By shernand Date 2003-05-29 Time 16:53 Rev Time 0.00
Received By shernand Date 2003-05-29 Time 16:53 Sent To B
Notes
2003-05-29 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-14 Cont ID  
Sent By sgraham Date 2003-04-23 Time 15:06 Rev Time 0.00
Received By shernand Date 2003-04-14 Time 15:16 Sent To  
Notes
2003-04-14 00:00:00COMM BOARD #38

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-10 Cont ID  
Sent By sgraham Date 2003-02-11 Time 09:40 Rev Time 0.00
Received By dpalmer Date 2003-02-10 Time 09:31 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-10-21 Cont ID  
Sent By pkrauss Date 2003-10-21 Time 07:38 Rev Time 0.45
Received By pkrauss Date 2003-10-21 Time 07:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-08-09 Cont ID  
Sent By csiegber Date 2003-10-17 Time 12:59 Rev Time 0.30
Received By pkrauss Date 2003-08-09 Time 08:35 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-04-21 Cont ID  
Sent By alange Date 2003-07-28 Time 07:58 Rev Time 1.00
Received By hmoser Date 2003-04-21 Time 16:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-04-21 Cont ID  
Sent By kstevens Date 2003-04-18 Time 08:09 Rev Time 1.00
Received By hmoser Date 2003-02-25 Time 10:09 Sent To  
Notes
2003-02-25 00:00:00DENIED:
  
 1.PLEASE REVISE OUTSIDE AIR CALCULATIONS
 TO INCLUDE CHILD CARE ROOM.
  
 2.PLAN SHEET AM-11 INDICATES 13 PERSONS
 AND OUTSIDE AIR CALCULATIONS ONLY SHOW
 8 PEOPLE.PLEASE CLARIFY.
  
 3.INDICATE WHAT WILL BE KEPT IN THE
 STORAGE ROOMS.
  
 4.CLOSETS CANNOT BE USED AS PLENUMS
 WITH THE CONDENSATE OVERFLOW TERMINATING
 IN THE AUXILIARY DRAIN PAN.
  
 5.CONDENSATE SECONDARY DRAIN SHALL
 TERMINATE AT A CONSPICUOUS POINT NOT
 IN THE AUXILIARY DRAIN PAN.
  
 6.PROVIDE SCHEDULE FOR EXHAUST FANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-04-18 Cont ID  
Sent By kstevens Date 2003-04-17 Time 14:52 Rev Time 0.75
Received By kstevens Date 2003-04-17 Time 14:52 Sent To M
Notes
2003-04-17 00:00:00HEALTH DEPT. APPROVAL TO BE WITH POOL
 PLANS.- MANUF. INFO. REQUIRED AT FINAL
 PLUMBING INSPECTION.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-03-04 Cont ID  
Sent By dpalmer Date 2003-04-17 Time 13:00 Rev Time 0.50
Received By kstevens Date 2003-03-04 Time 14:46 Sent To  
Notes
2003-03-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) PLEASE ROUTE PLANS TO HEALTH DEPT.
 901 EVERNIA ST WPB.
 2) SHT AMP-11 INSTA HOT SHALL BE LISTED.
 PLEASE PROVIDE MANUF. INFORMATION.
 3) SHT AMP-11 DRINKING FOUNTAIN - PLEASE
 PROVIDE FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING PER SECTION 11-4.1.3
 (10)(A)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 2 Status P Date 2003-04-23 Cont ID  
Sent By sgraham Date 2003-04-23 Time 15:06 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-02-11 Cont ID  
Sent By dpalmer Date 2003-02-10 Time 09:31 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
2003-02-11 00:00:00DENIED, NEED TO AMEND PLANS TO MATCH
 APPROVED SITE PLAN


Account Summary | Usage Policy | Privacy Policy