Plan Review Details - Permit 03020428
Plan Review Stops For Permit 03020428
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-03-12 Cont ID  
Sent By rbrown Date 2003-03-12 Time 14:40 Rev Time 0.00
Received By rbrown Date 2003-03-12 Time 14:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-02-25 Cont ID  
Sent By rbrown Date 2003-02-25 Time 11:51 Rev Time 0.00
Received By rbrown Date 2003-02-25 Time 11:51 Sent To  
Notes
2003-02-25 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC 11-4.13.6WHEELCHAIR MANEUVERING
 CLEARANCES AT DOORS.THE PULL SIDE OF
 THE DOORS TO OFFICE 1 TO 6, 11 TO 18, 20
 TO 21, 'ADMINISTRATOR' AND 'BREAK ROOM'
 SHALL HAVE A MINIMUM OF 18" CLEARANCE
 BETWEEN THE LEADING EDGE OF THE DOOR AND
 THE ADJACENT PERPENDICULAR WALL.NOTE:
 SHEET T-1 GENERAL DETAILS 'ACCESSIBILITY
 CLEARANCES' SHOW THE REQUIRED DIMENSION
 BUT THE RECESSES ON SHEET A-2 DO NOT
 APPEAR TO PROVIDE SUFFICIENT CLEARANCE
 WITH THE PROPOSED DOOR WIDTH.AMEND
 SHEET A-2 TO DIMENSION THE MINIMUM 18"
 CLEARNCE REQUIREMENT.
  
 2) FBC 2405.2THE GLASS CONFERENCE ROOM
 DOOR IS IN A 'HAZARDOUS LOCATION' AND IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).AMEND THE DOOR SCHEDULE OR
 PLANS TO DEMONSTRATE COMPLIANCE.
  
 3) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-04-14 Cont ID  
Sent By dpalmer Date 2003-04-14 Time 08:13 Rev Time 0.33
Received By dpalmer Date 2003-04-14 Time 08:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-03-11 Cont ID  
Sent By dpalmer Date 2003-03-11 Time 13:50 Rev Time 0.25
Received By dpalmer Date 2003-03-11 Time 13:50 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-02-25 Cont ID  
Sent By dpalmer Date 2003-02-25 Time 18:09 Rev Time 0.50
Received By dpalmer Date 2003-02-25 Time 18:09 Sent To  
Notes
2003-02-25 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE CLARIFY IF PANELS ARE
 NEW OR EXISTING? PANEL DETAIL MENTIONS,
 AIC RATING TO MATCH EXISTING? DOES THIS
 MEAN THEY ARE NEW? IF SO PLEASE PROVIDE
 INFORMATION ON HOW "5PB" IS BEING FED.
  
  
 2)NOTE: PLEASE SEE NOTES, WRONG CODES
 ARE BEING REFERENCED. SHOWS SBC-1999 AND
 2002 NEC. WE ARE UNDER 2001 FBC AND
 1999 NEC.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 THAT MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-03-06 Cont ID  
Sent By mcarsill Date 2003-03-06 Time 16:14 Rev Time 0.00
Received By mcarsill Date 2003-03-06 Time 16:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-02-28 Cont ID  
Sent By mcarsill Date 2003-02-28 Time 08:54 Rev Time 0.00
Received By mcarsill Date 2003-02-28 Time 08:54 Sent To  
Notes
2003-02-28 00:00:001) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM OR ANY FIRE SPRINKLER
 WORK.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-11 Cont ID  
Sent By shernand Date 2003-04-11 Time 09:47 Rev Time 0.00
Received By shernand Date 2003-04-11 Time 09:47 Sent To  
Notes
2003-04-11 00:00:00COMM BOARD #27

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-03-06 Cont ID  
Sent By dpalmer Date 2003-03-11 Time 13:50 Rev Time 0.25
Received By pkrauss Date 2003-03-06 Time 13:29 Sent To  
Notes
2003-03-06 00:00:00COMMENTS ADDRESSED ON PLAN (O.A. CALCS
 SUBMITTED, VAV'S EXISTING ADDED 1 HEAT
 STRIP).PLANS NEED TO BE STAMPED

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-02-20 Cont ID  
Sent By pkrauss Date 2003-02-20 Time 09:25 Rev Time 0.55
Received By pkrauss Date 2003-02-20 Time 09:25 Sent To  
Notes
2003-02-20 00:00:00DENIED:
 PLEASE CLARIFY THE FOLLOWING INFORMATION
  
 1. INDICATE NEW OR EXISTING VAV'S.
 2. PROVIDE SCHEDULE FOR NEW VAV'S.
 3. PROVIDE OUTSIDE AIR CALCS SHOWING
 COMPLIANCE WITH 2001 FBC(M) TABLE 403.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-03-04 Cont ID  
Sent By kstevens Date 2003-03-04 Time 13:37 Rev Time 0.33
Received By kstevens Date 2003-03-04 Time 13:35 Sent To  
Notes
2003-03-04 00:00:00PASSED/PROVISO
  
 SINK IN VENDING ROOM SHALL COMPLY WITH
 11-4.24.2, SHALL BE MAXIMUM 34" HIGH AFF
 PASSED/PROVISO
  
 SINK IN VENDING ROOM SHALL COMPLY WITH
 11-4.24.2 - MAXIMUM 34" AFF


Account Summary | Usage Policy | Privacy Policy