| Plan Review Stops For Permit 03020428 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2003-03-12 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2003-03-12 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2003-03-12 |
Time |
14:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-02-25 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2003-02-25 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2003-02-25 |
Time |
11:51 |
Sent To |
|
|
| Notes |
| 2003-02-25 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | | | 1) FBC 11-4.13.6WHEELCHAIR MANEUVERING | | | CLEARANCES AT DOORS.THE PULL SIDE OF | | | THE DOORS TO OFFICE 1 TO 6, 11 TO 18, 20 | | | TO 21, 'ADMINISTRATOR' AND 'BREAK ROOM' | | | SHALL HAVE A MINIMUM OF 18" CLEARANCE | | | BETWEEN THE LEADING EDGE OF THE DOOR AND | | | THE ADJACENT PERPENDICULAR WALL.NOTE: | | | SHEET T-1 GENERAL DETAILS 'ACCESSIBILITY | | | CLEARANCES' SHOW THE REQUIRED DIMENSION | | | BUT THE RECESSES ON SHEET A-2 DO NOT | | | APPEAR TO PROVIDE SUFFICIENT CLEARANCE | | | WITH THE PROPOSED DOOR WIDTH.AMEND | | | SHEET A-2 TO DIMENSION THE MINIMUM 18" | | | CLEARNCE REQUIREMENT. | | | | | | 2) FBC 2405.2THE GLASS CONFERENCE ROOM | | | DOOR IS IN A 'HAZARDOUS LOCATION' AND IS | | | REQUIRED TO BE SAFETY GLASS SATISFYING | | | THE REQUIREMENTS OF THE CONSUMER PRODUCT | | | SAFETY COMMISSION 16, CODE OF FEDERAL | | | REGULATIONS, PART 1201 (CPSC 16-CFR, | | | PART 1201).AMEND THE DOOR SCHEDULE OR | | | PLANS TO DEMONSTRATE COMPLIANCE. | | | | | | 3) IF NEW PLAN SHEETS ARE REQUIRED, IN | | | ORDER TO ADDRESS THE ABOVE COMMENTS, THE | | | OLD SHEETS SHALL BE REMOVED AND THE NEW | | | SHEETS INSERTED.ONE COPY OF EACH OLD | | | SHEET SHALL BE INCLUDED WITH THE | | | RESUBMITTAL FOR COMPARISON OF REVISIONS. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL: | | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2003-04-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-04-14 |
Time |
08:13 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-04-14 |
Time |
08:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2003-03-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-03-11 |
Time |
13:50 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2003-03-11 |
Time |
13:50 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-02-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-25 |
Time |
18:09 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-02-25 |
Time |
18:09 |
Sent To |
|
|
| Notes |
| 2003-02-25 00:00:00 | ************* UNSAT ****************** | | | | | | 1)NOTE: PLEASE CLARIFY IF PANELS ARE | | | NEW OR EXISTING? PANEL DETAIL MENTIONS, | | | AIC RATING TO MATCH EXISTING? DOES THIS | | | MEAN THEY ARE NEW? IF SO PLEASE PROVIDE | | | INFORMATION ON HOW "5PB" IS BEING FED. | | | | | | | | | 2)NOTE: PLEASE SEE NOTES, WRONG CODES | | | ARE BEING REFERENCED. SHOWS SBC-1999 AND | | | 2002 NEC. WE ARE UNDER 2001 FBC AND | | | 1999 NEC. | | | | | | PLEASE SEE COMMENTS FROM OTHER REVIEWERS | | | THAT MAY AFFECT ELECTRICAL PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2003-03-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-03-06 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-03-06 |
Time |
16:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2003-02-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-02-28 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-02-28 |
Time |
08:54 |
Sent To |
|
|
| Notes |
| 2003-02-28 00:00:00 | 1) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | 2) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE ALARM OR ANY FIRE SPRINKLER | | | WORK. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-04-11 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-11 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-11 |
Time |
09:47 |
Sent To |
|
|
| Notes |
| 2003-04-11 00:00:00 | COMM BOARD #27 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2003-03-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-03-11 |
Time |
13:50 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2003-03-06 |
Time |
13:29 |
Sent To |
|
|
| Notes |
| 2003-03-06 00:00:00 | COMMENTS ADDRESSED ON PLAN (O.A. CALCS | | | SUBMITTED, VAV'S EXISTING ADDED 1 HEAT | | | STRIP).PLANS NEED TO BE STAMPED |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2003-02-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-02-20 |
Time |
09:25 |
Rev Time |
0.55 |
| Received By |
pkrauss |
Date |
2003-02-20 |
Time |
09:25 |
Sent To |
|
|
| Notes |
| 2003-02-20 00:00:00 | DENIED: | | | PLEASE CLARIFY THE FOLLOWING INFORMATION | | | | | | 1. INDICATE NEW OR EXISTING VAV'S. | | | 2. PROVIDE SCHEDULE FOR NEW VAV'S. | | | 3. PROVIDE OUTSIDE AIR CALCS SHOWING | | | COMPLIANCE WITH 2001 FBC(M) TABLE 403.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2003-03-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-03-04 |
Time |
13:37 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2003-03-04 |
Time |
13:35 |
Sent To |
|
|
| Notes |
| 2003-03-04 00:00:00 | PASSED/PROVISO | | | | | | SINK IN VENDING ROOM SHALL COMPLY WITH | | | 11-4.24.2, SHALL BE MAXIMUM 34" HIGH AFF | | | PASSED/PROVISO | | | | | | SINK IN VENDING ROOM SHALL COMPLY WITH | | | 11-4.24.2 - MAXIMUM 34" AFF |
|
|