Plan Review Details - Permit 03020418
Plan Review Stops For Permit 03020418
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-02-18 Cont ID  
Sent By hpiskura Date 2003-02-18 Time 11:10 Rev Time 0.00
Received By hpiskura Date 2003-02-18 Time 10:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-02-13 Cont ID  
Sent By dpalmer Date 2003-02-13 Time 12:51 Rev Time 0.50
Received By dpalmer Date 2003-02-13 Time 12:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-02-28 Cont ID  
Sent By mcarsill Date 2003-02-28 Time 09:04 Rev Time 0.00
Received By mcarsill Date 2003-02-28 Time 09:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-02-07 Cont ID  
Sent By mcarsill Date 2003-02-07 Time 13:41 Rev Time 0.00
Received By mcarsill Date 2003-02-07 Time 13:41 Sent To  
Notes
2003-02-07 00:00:001) DOOR SCHEDULE DOES NOT INDICATE THAT
 DOOR # 9 IS FIRE RATED. DOOR IS
 REQUIRED TO BE FIRE RATED.
  
 2) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 3) AN EXIT SIGN IS NOTED IN THE RETAIL
 STORAGE AREA. PLEASE REVISE ROOM NAME
 AS EXITING IS NOT ALLOWED THRU STORAGE
 ROOMS,KITCHENS,ETC.
  
 MIKE CARSILLO,ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-02-27 Cont ID  
Sent By dpalmer Date 2003-02-27 Time 17:38 Rev Time 0.00
Received By dpalmer Date 2003-02-27 Time 17:38 Sent To  
Notes
2003-02-27 00:00:00TO COMM BOARD #51

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-06 Cont ID  
Sent By btrobaug Date 2003-02-06 Time 12:13 Rev Time 0.00
Received By btrobaug Date 2003-02-06 Time 12:12 Sent To  
Notes
2003-02-06 00:00:00COM BOARD #28./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-03-05 Cont ID  
Sent By pkrauss Date 2003-03-05 Time 15:44 Rev Time 0.40
Received By pkrauss Date 2003-03-05 Time 15:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-02-13 Cont ID  
Sent By pkrauss Date 2003-02-13 Time 13:32 Rev Time 0.35
Received By pkrauss Date 2003-02-13 Time 13:25 Sent To  
Notes
2003-02-13 00:00:00DENIED:
  
 PROVIDE OUTSIDE AIR CALCULATIONS AS PER
 2001 FBC(M) TABLE 403.3 OR ASHRAE 62-89.
 INDICATE SIZE, DUCT MATERIAL, AND LAYOUT
 OF OUTSIDE AIR DUCT. (NEW OR EXISTING)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-03-20 Cont ID  
Sent By kstevens Date 2003-03-20 Time 12:24 Rev Time 0.50
Received By kstevens Date 2003-03-20 Time 12:24 Sent To  
Notes
2003-03-20 00:00:00PASSED-PROVISO
  
 FLOOR SINKS REQUIRED FOR ALL INDIRECT
 WASTE.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-02-08 Cont ID  
Sent By kstevens Date 2003-02-08 Time 06:43 Rev Time 0.33
Received By kstevens Date 2003-02-08 Time 06:43 Sent To  
Notes
2003-02-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) DEMO NOTES: ALL CAPPED PLUMBING PIPES
 SHALL BE INSPECTED PRIOR TO COVERING.
 2) TABLE 403.1 DRINKING FOUNTAIN REQUIR-
 ED. ALSO SEE 410.1 (ARI-1010)
 3) SHT MP-2 ALL INDIRECT WASTE SHALL
 DRAIN TO A FLOOR SINK SEC 802.3 WITH
 A TRAP PRIMER.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377