Plan Review Details - Permit 03020200
Plan Review Stops For Permit 03020200
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-04-09 Cont ID  
Sent By btrobaug Date 2003-04-09 Time 12:08 Rev Time 1.00
Received By btrobaug Date 2003-04-09 Time 11:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-02-12 Cont ID  
Sent By shernand Date 2003-04-04 Time 13:39 Rev Time 1.00
Received By btrobaug Date 2003-02-11 Time 11:47 Sent To FIRE
Notes
2003-02-11 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 TO PLANS AND RESUBMIT FOR REVISIONS.
  
 1} THE RISER DIAGRAM INDICATES A 600 AMP
 METER AND 800AMP MAIN DISCONNECT,PLEASE
 CLARIFY.
  
 2} THE BOND SHOWN FROM THE METER
 ENCLOSURE TO THE GEC WOULD CREATE A
 PARALLEL GROUND PATH WITH THE GROUNDED
 NEUTRAL IN THE DISCONNECT,AND IS NOT
 NECESSARY AS THE NEUTRAL IS BONDED AT
 BOTH PIECES OF EQUIPMENT.
  
 3} PANEL "IL" IS NOT MARKED ON THE RISER
  
 4} NOTING THAT THERE ARE SPRAY BOOTHS ON
 THE PLANS ,PLEASE INDICATE CLASS &
 DIVISION FOR ALL LOCATIONS AFFECTED BY
 ARTICLES 500 THROUGH 516.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-04-25 Cont ID  
Sent By mcarsill Date 2003-04-25 Time 12:41 Rev Time 0.00
Received By mcarsill Date 2003-04-25 Time 12:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-02-20 Cont ID  
Sent By btrobaug Date 2003-02-12 Time 13:09 Rev Time 0.00
Received By nmccray Date 2003-02-20 Time 11:00 Sent To  
Notes
2003-02-20 00:00:001) PLEASE PROVIDE LIFE SAFETY PLANS FOR
 INDUSTRIAL OCCUPANCY TO COMPLY WITH
 NFPA 101 2000 EDITION.
  
 2) FIRE PROTECTION SYSTEM IS REQUIRED
 FOR SPRAY BOOTHS.
  
 3) ALL SPRAY BOOTHS OR SPRAYING OF
 FLAMMABLE LIQUIDS OR COMUSTIBLE MATERIAL
 MUST COMPLY WITH NFPA 33.
  
 4) MECHANICAL PLANS AND PERMITS ARE
 REQUIRED FOR VENTILATION AND MAKE-UP AIR
  
 5) ONLY 120 GAL OF FLAMMABLE LIQUIDS CAN
 STORED IN A UL LISTED CABINET.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT 8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-04 Cont ID  
Sent By shernand Date 2003-04-04 Time 13:39 Rev Time 0.00
Received By shernand Date 2003-04-04 Time 13:39 Sent To  
Notes
2003-04-04 00:00:00COMM BOARD #64