Plan Review Details - Permit 03020200
| Plan Review Stops For Permit 03020200 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2003-04-09 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-04-09 |
Time |
12:08 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2003-04-09 |
Time |
11:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-02-12 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-04 |
Time |
13:39 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2003-02-11 |
Time |
11:47 |
Sent To |
FIRE |
|
| Notes |
| 2003-02-11 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE ANY NECESSARY CHANGES | | | TO PLANS AND RESUBMIT FOR REVISIONS. | | | | | | 1} THE RISER DIAGRAM INDICATES A 600 AMP | | | METER AND 800AMP MAIN DISCONNECT,PLEASE | | | CLARIFY. | | | | | | 2} THE BOND SHOWN FROM THE METER | | | ENCLOSURE TO THE GEC WOULD CREATE A | | | PARALLEL GROUND PATH WITH THE GROUNDED | | | NEUTRAL IN THE DISCONNECT,AND IS NOT | | | NECESSARY AS THE NEUTRAL IS BONDED AT | | | BOTH PIECES OF EQUIPMENT. | | | | | | 3} PANEL "IL" IS NOT MARKED ON THE RISER | | | | | | 4} NOTING THAT THERE ARE SPRAY BOOTHS ON | | | THE PLANS ,PLEASE INDICATE CLASS & | | | DIVISION FOR ALL LOCATIONS AFFECTED BY | | | ARTICLES 500 THROUGH 516. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2003-04-25 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-04-25 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-04-25 |
Time |
12:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2003-02-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-02-12 |
Time |
13:09 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-02-20 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2003-02-20 00:00:00 | 1) PLEASE PROVIDE LIFE SAFETY PLANS FOR | | | INDUSTRIAL OCCUPANCY TO COMPLY WITH | | | NFPA 101 2000 EDITION. | | | | | | 2) FIRE PROTECTION SYSTEM IS REQUIRED | | | FOR SPRAY BOOTHS. | | | | | | 3) ALL SPRAY BOOTHS OR SPRAYING OF | | | FLAMMABLE LIQUIDS OR COMUSTIBLE MATERIAL | | | MUST COMPLY WITH NFPA 33. | | | | | | 4) MECHANICAL PLANS AND PERMITS ARE | | | REQUIRED FOR VENTILATION AND MAKE-UP AIR | | | | | | 5) ONLY 120 GAL OF FLAMMABLE LIQUIDS CAN | | | STORED IN A UL LISTED CABINET. | | | | | | NATE MCCRAY, CAPTAIN | | | 659-8096, EXT 8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-04-04 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-04 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-04 |
Time |
13:39 |
Sent To |
|
|
| Notes |
| 2003-04-04 00:00:00 | COMM BOARD #64 |
|
|
|