Plan Review Details - Permit 03020062
Plan Review Stops For Permit 03020062
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2003-06-02 Cont ID  
Sent By sthyng Date 2003-06-02 Time 15:54 Rev Time 1.50
Received By sthyng Date 2003-06-02 Time 15:54 Sent To E
Notes
2003-06-02 00:00:00SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 I HAVE REVIEWED THE DOCUMENTATION
 PROVIDED FOR THE TWO DOORS.
  
 IF A DOOR HAS GLASS, IT NEEDS TO BE
 PROTECTED.
  
 THE JELD WEN DOOR PACKAGE HAS A PRODUCT
 APPROVAL IN IT.IF YOU WISH TO USE
 THIS DOOR, SUBMIT TWO LEGIBLE COPIES.
  
 THE DESIGNER CLASSICS DOOR WOULD
 REQUIRE A SITE SPECIFIC PRODUCT
 APPROVAL.A FORM IS ATTACHED.IT NEEDS
 TO BE SIGNED AND SEALED IN BOTH BOXES
 AT THE BOTTOM, TWO COPIES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2003-05-21 Cont ID  
Sent By shernand Date 2003-05-29 Time 08:08 Rev Time 1.00
Received By sthyng Date 2003-05-21 Time 11:55 Sent To  
Notes
2003-05-21 00:00:00*****CORRECTIONS******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)GIVE DIMENSION OF THE WINDOW IN
 BEDROOM #1.REQUIRED TO HAVE EMERGENCY
 EGRESS FBC 1005.4.
  
 2.)PROVIDE A FRAMING DETAIL FOR THE
 NEW FRENCH DOORS.IF THE FRENCH DOORS
 ARE EXTERIOR, PROVIDE PRODUCT APPROVALS.
  
 3.)STUCCO ON METAL PLASTER BASE
 REQUIRED TO BE 7/8", FBC 2504.2,
 ASTM C 926.
  
 4.)GIVE SPACING FOR BOTTOM PLATE
 ATTACHMENT.
  
 5.)SPECIFY INSULATION IN WALLS, NOT
 "AS REQUIRED".

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-04-02 Cont ID  
Sent By btrobaug Date 2003-05-21 Time 07:52 Rev Time 3.50
Received By sthyng Date 2003-04-01 Time 19:54 Sent To P
Notes
2003-04-01 00:00:00PROVISOS -
  
 1.)SUBMIT PRODUCT APPROVALS FOR
 EITHER IMPACT WINDOWS ON 2ND STORY
 OR HURRICANE PROTECTION THAT CAN BE
 OPENED FROM THE INSIDE.
  
 2.)SUBMIT PRODUCT APPROVALS FOR
 MULLIONS.
  
 3.)SUBMIT SOIL REPORT FOR NEW SLAB
 SHOWING BEARING VALUE.
  
 4.)DOOR 004 TO HAVE 29" CLEAR
 OPENING PER FBC 11-11 (1).

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-03-27 Cont ID  
Sent By btrobaug Date 2003-04-01 Time 17:40 Rev Time 5.00
Received By sthyng Date 2003-03-27 Time 13:27 Sent To  
Notes
2003-03-27 00:00:00**********CORRECTIONS************
  
 1.)IMPACT FEES ARE FOR 642 SF,
 ADDITION IS 1284 SF.PLEASE REVISE
 WITH THE COUNTY.
  
 2.)SITE DATA (SHEET 1.1) STATES A
 BUILDING HEIGHT OF 1739 SF.PLEASE
 CORRECT.
  
 3.)PROVIDE OPENING SIZE FROM THE
 MANUFACTURER FOR WINDOWS #8 AND #9 ON
 THE WINDOW SCHEDULE.
 THEY ARE INDICATED AS EGRESS WINDOWS
 BUT DO NOT APPEAR TO MEET THE OPENING
 MEET THE OPENING REQUIREMENTS AS PER
 BC 1005.4.IF A DIFFERENT TYPE OF
 WINDOW IS TO BE USED OTHER THAN A
 SINGLE HUNG, SUBMIT A PRODUCT APPROVAL
 FOR THAT WINDOW.
  
 4.)THE ARCHITECT ADDRESSED COMMENT
 #3 IN REGARDS TO 2ND STORY WINDOWS TO
 BE EITHER IMPACT OR SHUTTERS REMOVEABLE
 FROM THE INSIDE.PLEASE SUBMIT A
 PRODUCT APPROVAL FOR EITHER THE IMPACT
 GLASS WINDOW OR A STORM SHUTTER THAT
 IS OPERABLE FROM THE INSIDE.
  
 5.)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 6.)SEPARATE PERMITS REQUIRED FOR
 FENCE AND GAS.
  
 7.)ADDITIONAL FEES REQUIRED; CAN PAY
 WHEN PERMIT IS ISSUED.
  
 8.)SUBMIT SOIL REPORT FOR NEW SLAB
 SHOWING BEARING VALUE (CAN SUBMIT LATER)
  
 9.)PROVIDE PRODUCT APPROVALS FOR
 THE MULLIONS.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-659-8096, EXTENSION 8340

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-03-06 Cont ID  
Sent By pkrauss Date 2003-02-28 Time 09:44 Rev Time 2.50
Received By lsmith Date 2003-03-06 Time 08:18 Sent To  
Notes
2003-03-06 00:00:00****************FAILED****************
 ALL CONSTRUCTION MUSTCOMPLY WITH THE
 FBC 2001 & MEET 140 MPH WIND ZONE
  
 1. SUBMIT PRODUCT APPROVALS FOR THE
 FOLLOWING:
 A. WINDOWS
 B. WINDOW MULLIONS
 B. DOORS
 C. HURRICANE PANELS*
 D. ROOF MATERIALS
 2. SUBMIT 2ND COPY OF ENERGY CALCS.
 3. IF 2ND FLOOR WINDOWS ARE NOT IMPACT
 SHUTTERS MUST BE CAPABLE OF BEING
 INSTALLED FROM INTERIOR.
 4. SEPARATE PERMITS REQUIRED FOR FENCE
 AND GAS.
 5. SUBMIT SOIL REPORT FOR NEW SLAB
 SHOWING BEARING VALUE.
 6. PLANS MUST BE TAKEN TO PBC BUILDING
 DEPARTMENT AND STAMPED AND IMPACT
 FEES PAID BEFORE PERMIT CAN BE ISSUED
 7. ADDITIONAL FEES REQUIRED; CAN PAY
 WHEN PERMIT IS ISSUED.
 8. PROVIDE A WINDOW SCHEDULE PRIOR TO
 INSTALLATION.INDICATE ALL EXISTING
 BEDROOM WINDOWS ON THE PLAN SHOWING
 SIZES AS PER FBC 1005.4.
 9. DRAFTSTOPPING IS REQUIRED BETWEEN
 FLOORS AS PER FBC 2305.2.2.
 10.HUGHES STRAPS SPECIFIED ARE NOT
 AVAILABLE.PLEASE REVISE.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 PHONE: 805-6713

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2003-06-02 Cont ID  
Sent By btrobaug Date 2003-06-02 Time 17:06 Rev Time 0.33
Received By btrobaug Date 2003-06-02 Time 17:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-05-21 Cont ID  
Sent By sthyng Date 2003-06-02 Time 16:09 Rev Time 0.50
Received By btrobaug Date 2003-05-21 Time 07:39 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-04-01 Cont ID  
Sent By shernand Date 2003-05-19 Time 14:25 Rev Time 0.50
Received By btrobaug Date 2003-04-01 Time 16:38 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-03-17 Cont ID  
Sent By dpalmer Date 2003-03-17 Time 07:49 Rev Time 0.75
Received By dpalmer Date 2003-03-17 Time 07:49 Sent To P
Notes
2003-03-17 00:00:00**************** UNSAT ****************
  
 PLEASE SEE PLANS, A COMPETELY NEW
 RISER DIAGRAM IS SUBMITTED. PLEASE
 SEE COMMENTS.
  
 PLEASE SEE SOME NOTES FROM FIRST REVIEW
 WERE NOT ADDRESSED.
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 NEW MAIN DISC SHOWN. PLEASE ALSO NOTE
 AIC RATING FOR PANEL WAS ON ORIG PLANS
 AND NOT SHOWN ON NEW? 110-9/215-5
  
 2)NOTE: PLEASE SEE PANEL SCHEDULE, THERE
 ARE STILL MANY ITEMS THAT DO NOT
 CORRELATE. PLEASE SEE OCP AND AWG.
  
 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULE FOR
 BEDRROMS. 210-12, PLEASE VERIFY ARD
 FAULT NOW SHOWN FOR LIVING ROOM?
  
 4)NOTE: PLEASE SEE LOAD CALCULATIONS,
 PLEASE DO CALCS PER NEC 220.
  
 5)NOTE: PLEASE SEE ORIG NOTES, WE ARE
 UNDER 99 NEC.
  
 6)NOTE: PLEASE SEE 2-POLE BRKR SHOWN FOR
 SM APPL CIRCUIT?
  
 7)NOTE: RISER NOW SHOWS A NEW MAIN DISC,
 PLEASE SEE PANEL STILL SHOWS A 200A MAIN
 BEING INSTALLED. PLEASE NOTE, IF A MAIN
 IS USED, A MCB IS NOT REQ`D AND MAY 'USE
 MLO?
  
  
 PLEASE SEE ATTACHED LETTER PER FS/ FAC
 553-80(2) (B).
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-02-20 Cont ID  
Sent By sthyng Date 2003-03-14 Time 14:13 Rev Time 1.00
Received By dpalmer Date 2003-02-20 Time 13:10 Sent To P
Notes
2003-02-20 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE CORRELATE ELECTRICAL
 RISER DIAGRAM AND PANEL DETAIL.
 THERE ARE MANY ITEMS THAT DO NOT MATCH,
 CONDUCTORS, CONDUITS ETC.
  
 2)NOTE:PLEASE SEE PANEL SCHEDULE, THERE
 ARE MANY ITEMS, PLEASE SEE OCP AND AWG
 240-3, PLEASE SEE 20A BRKRS ON #14 AWG?
  
 3)NOTE: PLEASE SEE 210-52 FOR MIN REQ`D
 SMALL APPL CIRCUITS, PLANS SHOW NEW
 KITCHEN AND PANEL SCHEDULE ONLY SHOWS
 ONE EXISTING SM APPL CIRCUIT?? 210-11
 PLEASE ALSO SEE OTHER CIRCUTIS SHOWN
 AS EXISTING AND SHOWN AS NEW ON PLAN.
  
 4)NOTE: PLEASE LIST THE REQ`D BATH
 CIRCUITS AS #12 AND 20, 210-11-C-3
 SHOWN AS #14.
  
 5)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS PER 210-12
  
 6)NOTE: PLANS/RISER SHOWS AN EQUIPMENT
 GROUNDING CONDUCTOR BEING INSTALLED
 BETWEEN METER AND PANEL. PLEASE SEE
 250-24, ONLY AFTER THE FIRST MEANS OF
 DISC.
  
 7)NOTE: PLEASE INCLUDE BLDG FOOTER
 STEEL AS PART OF GROUNDING ELECTRODE
 SYSTEM. 250-50.
  
 8)NOTE: PLEASE SEE NOTES LISTED, REF TO
 A 2001 NEC?
 THE 99 NEC AND THE NEXT NEC WILL BE
 2002.
  
 9)NOTE: SD MISSING AT THE BOTTOM OF
 STAIR, REQ`D PER NFPA-72 8-1.4.2
  
 10)NOTE: PLEASE RE-CONFIGURE LOAD
 CALCULATIONS TO MEET NEC ART 220.
 PLEASE NOTE, A/C LOADS MAY NOT BE
 DERATED @40% WITH LIGHTING LOADS.
  
  
 11)NOTE: PLEASE SEE 210-52D FOR OUTLET
 SPACING WITHIN 3" OF SINKS IN BATHS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-05-29 Cont ID  
Sent By shernand Date 2003-05-29 Time 08:07 Rev Time 0.00
Received By shernand Date 2003-05-29 Time 08:07 Sent To B
Notes
2003-05-29 00:00:00STHYNG DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-05-19 Cont ID  
Sent By shernand Date 2003-05-19 Time 14:25 Rev Time 0.00
Received By shernand Date 2003-05-19 Time 14:25 Sent To E
Notes
2003-05-19 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-03-14 Cont ID  
Sent By sthyng Date 2003-03-14 Time 14:13 Rev Time 0.00
Received By sthyng Date 2003-03-14 Time 14:13 Sent To E
Notes
2003-03-14 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-02-20 Cont ID  
Sent By dpalmer Date 2003-02-20 Time 08:45 Rev Time 0.00
Received By dpalmer Date 2003-02-20 Time 08:45 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-04 Cont ID  
Sent By dpalmer Date 2003-02-04 Time 08:47 Rev Time 0.00
Received By dpalmer Date 2003-02-04 Time 08:47 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-03-26 Cont ID  
Sent By pkrauss Date 2003-03-26 Time 13:38 Rev Time 0.35
Received By pkrauss Date 2003-03-26 Time 13:16 Sent To  
Notes
2003-03-26 00:00:00MECHANICAL PERMIT 03020063

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-02-28 Cont ID  
Sent By kstevens Date 2003-03-24 Time 06:53 Rev Time 0.40
Received By pkrauss Date 2003-02-28 Time 09:40 Sent To B
Notes
2003-02-28 00:00:00PROVISO:MECHANICAL PERMIT 03020063
  
 EXHAUST FAN REQUIRED IN SHOWER AREA AS
 WELL AS TOILET ROOM AS PER 2001 FBC(M)
 402.3.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-04-02 Cont ID  
Sent By sthyng Date 2003-04-02 Time 18:14 Rev Time 0.25
Received By kstevens Date 2003-04-02 Time 13:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-03-24 Cont ID  
Sent By sthyng Date 2003-04-01 Time 19:55 Rev Time 0.33
Received By kstevens Date 2003-03-24 Time 06:41 Sent To M
Notes
2003-03-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE. (2ND NOTICE) WATER LINES SHALL NOT
 TIE INTO SANITARY LINES. WASHER REQUIRES
 A 2" STANDPIPE AND NEES TO BE SHOWN ON
 THE RISER DIAGRAM. REMOVE DISHWASHER AND
 REFERENCE TO REFRIGERATOR AND ICE MAKER
 FROM RISER DIAGRAM. LAV NOT VENTED IN
 MASTER BATH.
  
 2) PLEASE SUBMIT COMPLETE SETS OF PLANS.
 REMOVE ALL OLD SHEET AND INSERT NEW
 SHEETS FOR REVIEW AND STAMPING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-02-27 Cont ID  
Sent By dpalmer Date 2003-03-17 Time 07:50 Rev Time 0.50
Received By kstevens Date 2003-02-27 Time 15:58 Sent To M
Notes
2003-02-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS. WATER LINES SHALL NOT
 TIE INTO SANITARY LINES. WASHER NEEDS A
 2" STANDPIPE AND REQUIRES VENTING. KIT.
 SINK NOT VENTED. DISHWASHER SHALL TIE IN
 TO TAILPIECE UPSTREAM OF TRAP. 3" VTR
 SHALL TIE INTO DRAIN UPSTREAM OF W/C IN
 2ND FLOOR BATH.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 2 Status P Date 2003-02-06 Cont ID  
Sent By sgraham Date 2003-02-06 Time 16:13 Rev Time 0.00
Received By sgraham Date   Time   Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-02-05 Cont ID  
Sent By dpalmer Date 2003-02-04 Time 08:47 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-02-05 00:00:00DENIED, NEED A SITE PLAN