Plan Review Details - Permit 03012458
Plan Review Stops For Permit 03012458
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2003-12-12 Cont ID  
Sent By rbrown Date 2003-12-12 Time 16:36 Rev Time 0.00
Received By rbrown Date 2003-12-12 Time 16:36 Sent To  
Notes
2003-12-12 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 SUBMITTAL ON 12/9/03, FOR WINDOW AND
 DOOR PRODUCT APPROVAL.
  
 1) THE DOOR SCHEDULE SPECIFIES DOOR
 MARK #3 AS A 2'-8"X 6'-8" DOOR.THE
 SUBMITTED SITE SPECIFIC PRODUCT APPROVAL
 SUBMITTAL FORM SPECIFIES 2'-6"X 6'-8"
 AND IS THEREFORE NOT APPLICABLE.ALSO,
 THE SUBMITTED FORM DOES NOT STATE THE
 'JOB/SITE LOCATION', IN THE SPACE
 ALLOCATED, BELOW THE SIGNATURE OF THE
 DESIGNER OF RECORD (BOTTOM RIGHT CORNER)
  
 2) NO PRODUCT APPROVAL HAS BEEN
 SUBMITTED FOR THE PROPOSED DOUBLE DOOR
 MARK #1
  
 3) CARADCO WOOD CASEMENT WINDOW PRODUCT
 APPROVAL NOA# 01-0814.05.THE SUBMITTED
 PRODUCT APPROVAL SHEETS ARE POOR COPIES
 AND CANNOT BE READ.THE DESIGN LOAD
 CAPACITY TABLES ON DRAWING SHEETS 1 AND
 5 OF 5 ARE ALMOST ENTIRELY ILLEGIBLE.
 SUBMIT LEGIBLE COPIES.ALSO, NOTE THAT
 THE PRODUCT APPROVAL SHEETS SHALL BE
 MARKED, AS APPROPRIATE TO IDENTIFY WHICH
 PRODUCT OPTIONS/MATERIALS/SIZES ARE TO
 BE USED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-10-07 Cont ID  
Sent By csiegber Date 2003-12-09 Time 10:11 Rev Time 0.50
Received By sthyng Date 2003-10-03 Time 17:17 Sent To  
Notes
2003-10-03 00:00:00****CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SUBMIT ALL PRODUCT APPROVALS
 AT ONE TIME (DOORS, WINDOWS, IMPACT
 PROTECTION).ANY ITEMS NOT INCLUDED
 IN THE NEXT SUBMITTAL WILL REQUIRE
 SEPARATE PERMITS FOR THOSE ITEMS.
  
 2.)SUBMIT A PRODUCT APPROVAL, SITE
 SPECIFIC PRODUCT APPROVAL (ATTACHED) OR
 OTHER APPROVED TEST REPORT AS PER
 FBC CHAPTER 17 FOR THE WOOD DOOR.
  
 3.)THE PERSONAL SEAL, SIGNATURE AND
 DATE OF THE ARCHITECT SHALL APPEAR ON
 ARCHITECTURAL DOCUMENTS TO BE FILED
 FOR PUBLIC RECORD, FAC61G1-16.003.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-03-05 Cont ID  
Sent By csiegber Date 2003-10-01 Time 09:56 Rev Time 2.00
Received By sthyng Date 2003-03-05 Time 10:16 Sent To  
Notes
2003-03-05 00:00:00PASSED PER LS
  
 PROVISO
 1.)SUBMIT PRODUCT APPROVALS FOR
 DOORS, WINDOWS, MULLIONS AND HURRICANE
 SHUTTERS.
  
 2.)INSPECTION REQUIRED AFTER
 SUBFLOORS ARE REMOVED.
  
 3/5/03

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-03-04 Cont ID  
Sent By btrobaug Date 2003-03-04 Time 15:27 Rev Time 2.50
Received By sthyng Date 2003-02-24 Time 16:04 Sent To  
Notes
2003-02-24 00:00:00**********CORRECTIONS************
  
 1.)PLEASE PROVIDE PRODUCT APPROVALS
 FOR ALL WINDOWS, EXTERIOR DOORS, AND
 HURRICANE SHUTTERS (2 COPIES OF EACH).
 CLEARLY MARK ATTACHMENTS TO BE USED.
  
 2.)PLEASE PROVIDE A DETAIL FOR THE
 NEW CONCRETE LANDING AND STEPS.
  
 3.)INSPECTION REQUIRED AFTER SUBFLOOR
 ON 2ND STORY IS REMOVED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 LEA SMITH OR SAMANTHA THYNG
 561-659-8096, EXTENSION 8340

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-03-04 Cont ID  
Sent By btrobaug Date 2003-03-04 Time 15:26 Rev Time 1.00
Received By btrobaug Date 2003-03-04 Time 15:26 Sent To B
Notes
2003-03-04 00:00:00TO SAMANTHA./WRT

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-02-20 Cont ID  
Sent By btrobaug Date 2003-02-28 Time 17:25 Rev Time 1.00
Received By btrobaug Date 2003-02-14 Time 11:06 Sent To B
Notes
2003-02-20 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATIONMAKE NECESSARY CORRECTIONS
 ON PLANS AND RESUBMIT FOR REVIEW.
  
 1} THE RISER SHOWS # 6 GEC,A #4 IS
 REQUIRED AND WAS SHOWN ON THE SERVICE
 CHANGERISER ON PREVIOUS PERMIT.
 PLEASE SHOW EXISTING RISER AS IT IS
 INSTALLED.
  
 2} CIRCUIT C-4 ON SHEET E-2 SHOWS # 14
 WIRE TO THE MASTER BATH,MUST COMPLY
 WITH 210-11(C)(3),20 AMP W/# 12 WIRE.
  
 3} CIRCUIT C-14 IN THE TOWER ROOM NOT
 SHOWN ON THE PANEL SCHEDULE.
  
 4} TOWER ROOM NEEDS A SMOKE DETECTOR TO
 COMPLY WITH 8-1.4.1.6.2(3),NFPA-72.
  
 5} MASTER BATH CIRCUITS LISTED AS C-7
 ONTHE PLAN AND BEDROOM ON PANEL
 SCHEDULE.PLAESE CORRELATE THE SCHEDULES
 WITH THE CIRCUIT LOCATIONS.
  
 6} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-12-09 Cont ID  
Sent By csiegber Date 2003-12-09 Time 10:11 Rev Time 0.00
Received By csiegber Date 2003-12-09 Time 10:11 Sent To B
Notes
2003-12-09 00:00:00TO ST DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-01 Cont ID  
Sent By csiegber Date 2003-10-01 Time 09:56 Rev Time 0.00
Received By csiegber Date 2003-10-01 Time 09:56 Sent To B
Notes
2003-10-01 00:00:00TO ST DESK/SUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-02-28 Cont ID  
Sent By btrobaug Date 2003-02-28 Time 17:25 Rev Time 0.00
Received By btrobaug Date 2003-02-28 Time 17:24 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-31 Cont ID  
Sent By btrobaug Date 2003-01-31 Time 17:41 Rev Time 0.00
Received By btrobaug Date 2003-01-31 Time 17:41 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-02-12 Cont ID  
Sent By kstevens Date 2003-02-11 Time 08:39 Rev Time 0.50
Received By hmoser Date 2003-02-12 Time 18:45 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-02-11 Cont ID  
Sent By kstevens Date 2003-02-11 Time 08:38 Rev Time 0.50
Received By kstevens Date 2003-02-11 Time 08:37 Sent To M
Notes
2003-02-11 00:00:00PASSED/PROVISO
  
 WATER HAMMER ARRESTORS - LOCATED NEAR
 THE FIXTURE NOT IN CEILING - PDI-WH 201
 & MANUF. INSTALL. INSTRUCTIONS

Review Stop Z ZONING
Rev No 1 Status P Date 2003-02-07 Cont ID  
Sent By btrobaug Date 2003-01-31 Time 17:47 Rev Time 0.00
Received By sgraham Date   Time   Sent To B
Notes
***NONE***