Plan Review Details - Permit 03012233
Plan Review Stops For Permit 03012233
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-03-15 Cont ID  
Sent By jwitmer Date 2003-03-15 Time 09:54 Rev Time 1.25
Received By jwitmer Date 2003-03-15 Time 09:54 Sent To  
Notes
2003-03-15 00:00:00 
  
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 03012233
 ADDRESS: 211 FOREST HILL BLVD
 CONT: JBS CONSTRUCTION INC
 TELL # (561)575-1977
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.104.2.1.2 ADMINISTRATIVE CODE.
  
 PROVISO: STORM SHUTTERS SHALL BE
 REQUIRED AND UNDER A SEPERATE PERMIT.
 A KEY PLAN, SCHEDULE AS W.P.B. SAMPLE
 REQUIRED WITH PRODUCT TESTING REPORTS
 EITHER SBCCI OR DADE COUNTY ARE ACCEPT-
 ABLE. STORM SHUTTER PERMIT TO BE ISSUED
 BEFORE ISSUANCE OF CERTIFICATE OF OCC-
 UPANCY.
 JIM WITMER
 BUILDING PLAN REVIEW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-02-24 Cont ID  
Sent By kstevens Date 2003-03-13 Time 10:29 Rev Time 1.75
Received By jwitmer Date 2003-02-24 Time 07:06 Sent To  
Notes
2003-02-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03012233
 ADD: 211 FOREST HILL BLVD
 CONT: JBS CONSTRUCTION
 TEL: (561)575-1977
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 DENIED:
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 SOILS REPORT COPY NOT SIGNED/ SEALED
  
 3)FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
 THE FL CODE ONLY RECONIZES FASTED MILE,
 TRUE THERE IS A CONVERSION FOR SUSTAINED
 WIND BUT WE USE FASTED MILE AS OF
 MARCH 1, 2002.
  
 4)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 MISSING INTERNAL PRESURE COEFFICIENT
  
 5)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.MISSING REPORTS:
 A) STORM SHUTTERS
  
 6) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 7)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 8)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 FOUNDATION PLAN NOTE:"G. C. TO VERIFY
 THE CONDITION OF EXISTING SLAB". WHAT
 SLAB ARE YOU REFERRING TO?
  
 9)2304.5 CLEARENCE BETWEEN WOOD SIDING
 & EARTH ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6" EXCEPT WHERE
 SIDING, SHEATHING AND FRAME WALL ARE OF
 APPROVED DURABLE WOOD OR APPROVED PRE-
 ERVATIVE TREATED WOOD. SHEET 3 SEC "A"
 INDICATES THE 6" ABOVE GRADE TO THE TOP
 OF THE P T PLATE, THE SHEATHING WOULD BE
 WITHIN THE 6" ABOVE GRADE ZONE.
  
 10) 1403.1.6 IN ORDER TO PROVIDE FOR IN-
 SPECTION FOR TERMITE INFESTATION, CLEAR-
 ENCE BETWEEN EXTERIOR WALL COVERINGS &
 FINAL EARTH GRADE ON EXTERIOR OF A BUILD
 ING SHALL NOT BE LESS THAN 6".
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-10-14 Cont ID  
Sent By btrobaug Date 2003-10-14 Time 13:00 Rev Time 0.33
Received By btrobaug Date 2003-10-14 Time 12:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-09-18 Cont ID  
Sent By csiegber Date 2003-10-03 Time 16:21 Rev Time 0.50
Received By btrobaug Date 2003-09-18 Time 12:05 Sent To  
Notes
2003-09-18 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATED AND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
  
 2} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110.9.
  
 3} PLEASE NOTE THAT SMOKE DETECTORS ARE
 TO BE INSTALLED PER 8-1.4.1.6.2 NFPA-72,
 SHOW SAME ON PLANS.
  
 4} INDICATE THE AMPERE RATING OF THE NEW
 SERVICE.
  
 5} PLEASE GIVE PANEL SCHEDULES FOR ALL
 PANELS AND LOAD CALCULATIONS FOR THE
 ENTIRE SERVICE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-03-11 Cont ID  
Sent By csiegber Date 2003-09-11 Time 10:48 Rev Time 0.50
Received By dpalmer Date 2003-03-11 Time 16:20 Sent To P
Notes
2003-03-11 00:00:00NOTES REDLINED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-02-12 Cont ID  
Sent By dpalmer Date 2003-03-11 Time 16:19 Rev Time 0.50
Received By dpalmer Date 2003-02-12 Time 14:40 Sent To B
Notes
2003-02-12 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE PROVIDE LOAD CALCULATIONS
 FOR NEW AND EXISTING. PLANS SHOWS NEWW
 AND NOTHING FOR SIZE OF EXSITING SERVICE
 OR LOAD. 220-3-C1
  
 2)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS PER 210-12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EX 8372

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-10-03 Cont ID  
Sent By csiegber Date 2003-10-03 Time 16:21 Rev Time 0.00
Received By csiegber Date 2003-10-03 Time 16:21 Sent To E
Notes
2003-10-03 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-11 Cont ID  
Sent By csiegber Date 2003-09-11 Time 10:47 Rev Time 0.00
Received By csiegber Date 2003-09-11 Time 10:47 Sent To E
Notes
2003-09-11 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-07 Cont ID  
Sent By dpalmer Date 2003-03-07 Time 16:19 Rev Time 0.00
Received By dpalmer Date 2003-03-07 Time 16:19 Sent To E
Notes
2003-03-11 00:00:00TO DVP`S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-29 Cont ID  
Sent By dpalmer Date 2003-01-29 Time 16:01 Rev Time 0.00
Received By dpalmer Date 2003-01-29 Time 16:01 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-02-07 Cont ID  
Sent By kstevens Date 2003-02-06 Time 17:15 Rev Time 0.35
Received By pkrauss Date 2003-02-07 Time 15:56 Sent To E
Notes
2003-02-07 00:00:00MECHANICAL PERMIT 03012237

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-03-13 Cont ID  
Sent By kstevens Date 2003-03-13 Time 10:28 Rev Time 0.33
Received By kstevens Date 2003-03-13 Time 10:28 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-02-06 Cont ID  
Sent By dpalmer Date 2003-03-11 Time 16:20 Rev Time 0.25
Received By kstevens Date 2003-02-06 Time 17:09 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2003-02-06 Cont ID  
Sent By sgraham Date 2003-02-06 Time 15:39 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-02-05 Cont ID  
Sent By dpalmer Date 2003-01-29 Time 16:01 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
***NONE***