Plan Review Details - Permit 03012088
Plan Review Stops For Permit 03012088
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-04-28 Cont ID  
Sent By dpalmer Date 2003-04-22 Time 08:34 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-03-12 Cont ID  
Sent By dpalmer Date 2003-02-25 Time 06:00 Rev Time 3.00
Received By lhatten Date 2003-03-08 Time 18:44 Sent To  
Notes
2003-03-12 00:00:001) NEEDS N.O.C.
 2) NEEDS IMPACT FEES PAID
 3) NEEDS PRODUCT APPROVALS FOR ALL
 EXTERIOR DOORS,SIDELITES,ARCH WINDOWS,
 GARAGE DOORS,MULL BARS AND SHUTTER
 LAYOUT FOR HOUSE
 4) ( 1 ) EXTRA COVER SHEET FROM ENERGY
 CALS.
 5) ROOFING PRODUCT APPROVALS
 6)DECORATIVE WOOD LOUVER-24"RADIUS

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-05-18 Cont ID  
Sent By dpalmer Date 2004-05-18 Time 15:19 Rev Time 0.50
Received By dpalmer Date 2004-05-18 Time 15:19 Sent To  
Notes
2004-05-18 00:00:00REDLINED 220.3B-4

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-05-08 Cont ID  
Sent By dpalmer Date 2004-05-08 Time 16:39 Rev Time 0.33
Received By dpalmer Date 2004-05-08 Time 16:39 Sent To  
Notes
2004-05-08 00:00:00****** UNSAT **********
  
 1)NOTE: PLEASE SEE FBC 104.2.1, PLANS
 MUST CONTAIN PRINTED NAME AND SIGNATURE
 OF PERSON RESPONSIBLE FOR PLANS.
 PRINTED NAME IS PLANS, HOWEVER, MR JUAN
 MOLINA NEEDS TO SIGN AND DATE.
  
 2)NOTE: PLEASE SEE MISSING RECEPT ON
 PLANS, ONE SHEET IS REDLINED.
  
 3 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-04-22 Cont ID  
Sent By csiegber Date 2004-05-06 Time 10:34 Rev Time 0.50
Received By dpalmer Date 2003-04-22 Time 08:34 Sent To B
Notes
2003-04-22 00:00:00PLANS REDLINED BY DESIGNER.
 OLD SHEETS STILL NEED TO BE TAKEN OUT OF
 SETS AND INSERT NEW SHEETS.
 SENT BACK TO LOU MARTINEZ.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-04-10 Cont ID  
Sent By dpalmer Date 2003-04-10 Time 05:53 Rev Time 0.33
Received By dpalmer Date 2003-04-10 Time 05:53 Sent To P
Notes
2003-04-10 00:00:00************** UNSAT *********
  
 PLEASE REMOVE ALL OLD SHEETS AND INSERT
 NEW SHEETS TO MAKE TWO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SEE THE FOLLOWING COMMENTS THAT
 STILL NEED TO BE ADDRESSED FROM FIRST
 REVIEW. MOST WERE DONE.
  
 1)NOTE: PLEASE SIZE SERVICE ENTRANCE
 CONDUCTORS PER 310-15 FOR A 350A SERVICE
 INTO GUTTER. THE CONDUCTORS SHOWN FROM
 GUTTER TO MAINS ARE OK.
  
 2)NOTE: PLEASE SEE MISSING RECEPT FOR
 KITCHEN COUNTERSPACE. 210-52C-1 AND
 PLEASE SHOW AS GFI/GFI PROTECTED.
 210-8A-6
 PLEASE SEE ONE SET W/ REDLINES.
  
 3)NOTE: PLEASE CALL IN REF TO PANEL "B"
 GROUNDING ELECTRODE, NOT REQ`D BUT IF
 SHOWN ON PLAN, IT WILL BE REQ`D TO BE
 INSTALLED. PLEASE CALL.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL. IF A VOICE MAIL IS LEFT,
 PLEASE LEAVE PHONE # FOR RETURN CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-02-25 Cont ID  
Sent By shernand Date 2003-04-08 Time 16:25 Rev Time 0.75
Received By dpalmer Date 2003-02-25 Time 05:59 Sent To B
Notes
2003-02-25 00:00:00****************** UNSAT ***********
  
 1)NOTE: PLEASE SIZE SEVICE ENTRANCE
 CONDUCTORS PER 310-15. 350A SERIVCE.
 SHOWN AS 3/0`S INTO GUTTER AND 250MCM
 IN GUTTER.
  
 2)NOTE: PLEASE ALSO SIZE FEEDERS FOR
 PANELS. SHOWN AS 1/0`S FOR 200A'S?
 AND #2 FOR 150A'S. PLEASE ALSO SEE
 310-15 FOR MIN SIZE. ALSO 310-16
  
 3)NOTE: PLEASE VERIFY GROUNDING ELEC-
 -TRODE SYSTEM AT PANEL "B". PLEASE CALL.
  
 4)NOTE: PLEASE SHOW MAINS NEXT TO METER
 ON PLANS (E-2) AS SHOWN ON RISER.
  
 5)NOTE: PLEASE SEE MISSING OUTLETS
 ON ISLAND AND COUNTERSPACES IN KITCHEN.
 PER 210-52-C1,2,3,4,&5,
 ALSOPENINSULAR.
  
 6)NOTE: PLEASE ALSO SHOW ALL COUNTER-
 -SPACE RECEPTS AS GFI/GFI PROTECTED
 PER 210-8-A-6
  
 7)NOTE: PLEASE NOTE ON PLANS , ALL
 SD'S TO BE A MIN OF 3' FROM BATHS PER
 NFPA-72 8-1.4.2
  
 8)NOTE: PLEASE SEE MISSING GFI RECEPT
 IN BATH #3. 210-52D
  
 9)NOTE: PLEASE SHOW A/C DISC'S PER
 440-11 (COND UNITS).
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-05-06 Cont ID  
Sent By csiegber Date 2004-05-06 Time 10:34 Rev Time 0.00
Received By csiegber Date 2004-05-06 Time 10:34 Sent To E
Notes
2004-05-06 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-05-09 Cont ID  
Sent By shernand Date 2003-05-09 Time 09:37 Rev Time 0.00
Received By shernand Date 2003-05-09 Time 09:37 Sent To P
Notes
2003-05-09 00:00:00KSTEVENS DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-08 Cont ID  
Sent By shernand Date 2003-04-08 Time 16:25 Rev Time 0.00
Received By shernand Date 2003-04-08 Time 16:20 Sent To E
Notes
2003-04-08 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-29 Cont ID  
Sent By sgraham Date 2003-02-12 Time 15:14 Rev Time 0.00
Received By dpalmer Date 2003-01-29 Time 13:43 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-04-16 Cont ID  
Sent By kstevens Date 2003-04-16 Time 08:37 Rev Time 0.40
Received By pkrauss Date 2003-04-16 Time 12:18 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-02-22 Cont ID  
Sent By jleech Date 2003-02-22 Time 08:19 Rev Time 0.50
Received By hmoser Date 2003-02-22 Time 13:24 Sent To E
Notes
2003-02-22 00:00:00PLAN DENIED
 NEED DUCT SIZE NO MECHANICAL PLAN.
 NEED GRILL SIZE AND CFM ON CANS.
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8221

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-05-20 Cont ID  
Sent By kstevens Date 2003-05-20 Time 10:58 Rev Time 1.00
Received By kstevens Date 2003-05-20 Time 10:58 Sent To  
Notes
2003-05-20 00:00:00PROVISO: NO HORIZONTAL DRY VENTS 905.3

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-04-16 Cont ID  
Sent By shernand Date 2003-05-09 Time 09:37 Rev Time 0.75
Received By kstevens Date 2003-04-16 Time 08:34 Sent To M
Notes
2003-04-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) PLEASE REMOVE ALL OLD SHEETS AND PUT
 NEW SHEETS FOR COMPLETE SETS TO REVIEW
 AND STAMP.
 2) SEE ALL RED LINE AND HIGHLIGHTED
 AREAS ON RISER DIAGRAM AND FLOOR PLAN
 FLAT DRAWING. PLEASE MAKE CORRECTIONS
 AND RESUBMIT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-02-22 Cont ID  
Sent By jleech Date 2003-02-22 Time 08:19 Rev Time 0.50
Received By jleech Date 2003-02-22 Time 08:19 Sent To M
Notes
2003-02-22 00:00:00DENIED;
 PLEASE SUBMIT A SANITARY RISER DIAGRAM.
 DRAWING ON PAGE P-1 DOES NOT MEET CODE.
 HORIZONTAL DRY VENTS.
 UNVENTED FIXTURES.
 PIPE NOT SIZED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8369

Review Stop Z ZONING
Rev No 1 Status P Date 2003-02-12 Cont ID  
Sent By dpalmer Date 2003-01-29 Time 13:44 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***