Plan Review Details - Permit 03011977
Plan Review Stops For Permit 03011977
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-03-07 Cont ID  
Sent By hpiskura Date 2003-03-07 Time 13:09 Rev Time 0.00
Received By hpiskura Date 2003-03-07 Time 12:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-02-11 Cont ID  
Sent By hpiskura Date 2003-02-11 Time 08:08 Rev Time 0.00
Received By hpiskura Date 2003-02-11 Time 08:08 Sent To  
Notes
2003-02-11 00:00:00WHAT IS THE NATURE AND QUANTITY OF THE
 COMMODITIES TO BE STORED?IF
 MANUFACTURING IS TO TAKE PLACE PLEASE
 PROVIDE A BRIEF DESCRIPTION OF THE
 PROCESS.SEE FBC 104.3.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-02-07 Cont ID  
Sent By dpalmer Date 2003-02-07 Time 06:57 Rev Time 0.50
Received By dpalmer Date 2003-02-07 Time 06:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-03-13 Cont ID  
Sent By mcarsill Date 2003-03-13 Time 15:48 Rev Time 0.00
Received By mcarsill Date 2003-03-13 Time 15:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-02-07 Cont ID  
Sent By mcarsill Date 2003-02-07 Time 11:05 Rev Time 0.00
Received By mcarsill Date 2003-02-07 Time 11:05 Sent To  
Notes
2003-02-07 00:00:001) ENSURE TENANT IDENTIFIER IS PRESENT
 FOR POLICE AND FIRE RESCUE.
  
 2) PLANS,PERMIT APPLICATION, AND PLAN
 REVIEW ALL LIST DIFFERENT ADDRESSES.
 PLEASE CORRECT.
  
 3) EMERGENCY LIGHTING NOT REQUIRED
 IN SMALL OFFICES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-05 Cont ID  
Sent By dpalmer Date 2003-03-05 Time 10:56 Rev Time 0.00
Received By dpalmer Date 2003-03-05 Time 10:56 Sent To  
Notes
2003-03-05 00:00:00TO COMM BOARD #21

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-03-12 Cont ID  
Sent By pkrauss Date 2003-03-12 Time 10:33 Rev Time 0.40
Received By pkrauss Date 2003-03-12 Time 10:33 Sent To  
Notes
2003-03-12 00:00:00PROVISO:
  
 EQUIPMENT LOCATED ON ROOFS AT A HEIGHT
 EXCEEDING 16 FT, SHALL HAVE A PERMANENT
 MEANS OF ACCESS.ACCESS SHALL NOT
 REQUIREDCLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30".
  
 CONDENSATE SHALL DISCHARGE TO ROOFDRAIN.
 CONDENSATE DUMPING ONTO THE ROOFTOP IS
 A SAFETY HAZARD.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-02-13 Cont ID  
Sent By pkrauss Date 2003-02-13 Time 08:38 Rev Time 0.35
Received By pkrauss Date 2003-02-13 Time 08:19 Sent To  
Notes
2003-02-13 00:00:00DENIED:MECHANICAL PERMIT 03011980
  
 PROVIDE INFORMATION FOR THE CONDENSATE
 (LINE SIZE & MATERIAL, LAYOUT AND
 TERMINATION POINT).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-03-26 Cont ID  
Sent By kstevens Date 2003-03-26 Time 10:46 Rev Time 2.00
Received By kstevens Date 2003-03-21 Time 09:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-02-05 Cont ID  
Sent By kstevens Date 2003-02-05 Time 10:01 Rev Time 0.75
Received By kstevens Date 2003-02-05 Time 10:01 Sent To  
Notes
2003-02-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-1 SEPARATE TOILET FACILITIES
 ARE REQUIRED PER SECTION 403.2
 2) SHT A-1 WATER COOLER SHALL COMPLY
 WITH ARI-1010 PER SECTION 410.1. MANUF.
 INFORMATION REQUIRED AT FINAL.
 3) SHT A-1 EMERGENCY EYE WASH/SHOWER,
 MANUF. INFORMATION REQUIRED FOR REVIEW.
 4) SHT P1 PLUMBING SPECIFICATIONS #7,
 AIR CHAMBERS NOT APPROVED. PLEASE DELETE
 FROM REFERENCE.
 5) SHT P1 WATER RISER, AIR CHAMBERS ARE
 NOT APPROVED. IF WATER HAMMER ARRESTORS
 ARE USED, (SEC 604.9), THEY SHALL BE
 LOCATED NEAR THE FIXTURE IN AN "EFFECT-
 IVE RANGE" NOT AT THE TOP OF THE DROP IN
 THE CEILING.
 6) SHT P1 SANITARY RISER & FLAT PLAN,
 ONLY THE FIXTURES WITHIN THE BATHROOM
 GROUP SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF
 THE WET VENT. SECTION 909.1 - THE JANIT-
 OR SINK SHOULD HAVE ITS OUN VENT LINE
 AND TIE IN DOWNSTREAM OF THE BATHROOM
 GROUP.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377