Plan Review Details - Permit 03011966
Plan Review Stops For Permit 03011966
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-04-16 Cont ID  
Sent By shernand Date 2003-05-13 Time 15:54 Rev Time 0.00
Received By hpiskura Date 2003-04-16 Time 14:31 Sent To  
Notes
2003-04-16 00:00:00REVISIONS A.S.I.-01 DATED 4/1/03 AND SK
 1,2 AND 3 DATED 3/27/03.
  
 ASI PLAN, PROVIDE DETAILS FOR THE
 CONSTRUCTION OF THE STAIRS, WALK WAY
 AND RAMP. WHAT WILL THE RAMP BE USED
 FOR?
  
 SK-1, WHERE WILL THE TEN FEET WIDE
 OPENING BE PLACED IN THE BUILDING?
  
 SK-3, WHERE WILL THE DOCK LEVELER BE
 PLACED?
  
 PAY PERMIT FEES ON THE CONTRACT VALUE OF
 THE ADDED WORK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-02-10 Cont ID  
Sent By hpiskura Date 2003-02-10 Time 11:00 Rev Time 0.00
Received By hpiskura Date 2003-02-10 Time 09:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-02-07 Cont ID  
Sent By dpalmer Date 2003-02-07 Time 14:44 Rev Time 0.00
Received By btrobaug Date 2003-03-20 Time 14:21 Sent To  
Notes
2003-02-07 00:00:00REDLINED EQUIPMENT GROUNDS TO AND FROM
 TRANSFORMER. SIZE PER 250-122

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-02-11 Cont ID  
Sent By nmccray Date 2003-02-11 Time 10:36 Rev Time 0.00
Received By nmccray Date 2003-02-11 Time 10:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-05-13 Cont ID  
Sent By shernand Date 2003-05-13 Time 15:54 Rev Time 0.00
Received By shernand Date 2003-05-13 Time 15:54 Sent To B
Notes
2003-05-13 00:00:00HP DESK.SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-04-08 Cont ID  
Sent By shernand Date 2003-04-08 Time 15:54 Rev Time 0.00
Received By shernand Date 2003-04-08 Time 15:54 Sent To  
Notes
2003-04-08 00:00:00COMM BOARD #32

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-06 Cont ID  
Sent By dpalmer Date 2003-03-06 Time 12:43 Rev Time 0.00
Received By dpalmer Date 2003-03-06 Time 12:43 Sent To  
Notes
2003-03-06 00:00:00TO COMM BOARD #18 B/P

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-27 Cont ID  
Sent By btrobaug Date 2003-01-27 Time 14:31 Rev Time 0.00
Received By btrobaug Date 2003-01-24 Time 14:31 Sent To  
Notes
2003-01-27 00:00:00COMM.BOARD # 16./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-06-09 Cont ID  
Sent By pkrauss Date 2003-06-09 Time 15:51 Rev Time 0.45
Received By pkrauss Date 2003-06-09 Time 15:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-02-03 Cont ID  
Sent By pkrauss Date 2003-02-03 Time 10:13 Rev Time 0.50
Received By pkrauss Date 2003-02-03 Time 10:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-03-06 Cont ID  
Sent By kstevens Date 2003-03-06 Time 13:41 Rev Time 0.50
Received By kstevens Date 2003-03-06 Time 13:41 Sent To  
Notes
2003-03-06 00:00:00PASSED/PROVISO
  
 MANUFACTURE INFORMATION REQUIRED AT
 FINAL FOR WATER COOLER - SHALL BE ARI-
 1010 COMPLIANT.
  
 REVISION REQUIRED FOR SANITARY RISER
 DIAGRAM - DRINKING FOUNTAINS ADDED

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-02-04 Cont ID  
Sent By kstevens Date 2003-02-04 Time 14:26 Rev Time 1.00
Received By kstevens Date 2003-02-04 Time 14:25 Sent To  
Notes
2003-02-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) WATER COOLER SHALL COMPLY WITH ARI-
 1010. MANUF INFORMATION REQUIRED BY
 FINAL INSPECTION
 2) SHT A1 TOILET ROOMS #109 & 110, DOORS
 SHALL NOT OPEN INTO THE CLEAR FLOOR
 SPACE OF ANY FIXTURE INCLUDING THE UN-
 OBSTRUCTED 5' TURNING RADIUS. SECTIONS
 11-4.22.2, 11-4.22.3
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377