| Plan Review Stops For Permit 03011941 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2003-04-15 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-04-15 |
Time |
13:32 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2003-04-15 |
Time |
13:32 |
Sent To |
|
|
| Notes |
| 2003-04-15 00:00:00 | PLANS W/REV DATED 2/20/03 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2003-03-19 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-03-19 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2003-03-19 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2003-03-19 00:00:00 | THE PLANS HAVING REVISION DATE 2/20/03 | | | ARE NOT SIGNED, SEALED AND DATED. | | | | | | THE OPENING PROTECTION FOR THE STAIRS AS | | | REQUIRED BY FBC 1006.2.4 HAS NOT BEEN | | | COMPLETELY ADDRESSED.SEE THE ATTACHED | | | CODE EXCERPT AND THE PORTION OF THE 97 | | | CODE COMMENTARY FOR CLARITY OF | | | APPLICATION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-02-10 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-02-10 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2003-02-10 |
Time |
13:58 |
Sent To |
Z |
|
| Notes |
| 2003-02-10 00:00:00 | WHAT ARE "NEEDLE BEAMS" SHOWN IN THE | | | SHORING SECTIONS? | | | | | | THE OPENINGS WITHIN TEN FEET OF THE | | | EXTERIOR STAIR ARE REQUIRED BY FBC | | | 1006.2.4 TO BE FIRE RATED. | | | | | | THE USE OF CDX SHEATHING IN EXTERIOR | | | WALLS IS TYPE VI CONSTRUCTION AND IS | | | PROHIBITTED IN THE DESIGNATED FIRE | | | DISTRICT.SEE FBC 102.1 AS AMENDED BY | | | THE CITY OF WEST PALM BEACH. | | | | | | PLEASE PROVIDE A SITE PLAN / SURVEY | | | SHOWING THE DISTANCE TO COMMON PROPERTY | | | LINES AND BUILDINGS LOCATED ON THE SAME | | | PROPERTY SO THAT COMPLIANCE WITH TABLE | | | 600 FOR THE NEW OPENINGS MAY BE | | | DETERMINED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2003-03-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-03-13 |
Time |
09:51 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2003-03-13 |
Time |
09:51 |
Sent To |
|
|
| Notes |
| 2003-03-13 00:00:00 | ORIG PLANS SUBMITTED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2003-03-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-03-13 |
Time |
08:53 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2003-03-13 |
Time |
08:53 |
Sent To |
|
|
| Notes |
| 2003-03-13 00:00:00 | ************ UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE ALL NEW PLANS HAVE | | | BEEN SUBMITTED W/ REVISIONS. PLANS | | | ARE NOT SIGNED AND SEALED BY THE ARCH OF | | | RECORD REQ`D PER FS/FAC 481.221/61G1-16 | | | .004 OR | | | PLEASE SUBMIT ORIG SHEETS THAT WERE | | | ALREADY SIGNED/STAMPED BY ELEC AND FIRE. | | | | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2003-02-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-07 |
Time |
06:52 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2003-02-07 |
Time |
06:52 |
Sent To |
|
|
| Notes |
| 2003-02-07 00:00:00 | NOTES ON PLANS. | | | EXTERIOR LTS AND BATH ELECTRICAL ONLY. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2003-04-23 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-04-23 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-04-23 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2003-04-23 00:00:00 | ***************PROVISO****************** | | | 1) PROVIDE PRODUCT APPROVAL ON THE ROLL | | | DOWN FIRE SCREEN ABOVE WINDOW @ INTERIOR | | | IS IT UL LISTED AND NFPA 80. | | | | | | NATE MCCRAY, CAPTAIN | | | 659-8096, 8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2003-02-06 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-02-06 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-02-06 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2003-02-06 00:00:00 | PROVISO | | | 1) FIRE OR FLAME RETARDANT SPEC'S FOR | | | VINYL AWNINGS. | | | | | | NATE MCCRAY, CAPTAIN | | | 659-8096, EXT 8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-04-09 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-09 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-09 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2003-04-09 00:00:00 | COMM BOARD #12 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-03-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-03-13 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2003-03-13 |
Time |
08:52 |
Sent To |
|
|
| Notes |
| 2003-03-13 00:00:00 | PLANS PUT ON COMM BOARD #4 | | | ALL NEW SHEETS, REVISED SINCE LAST | | | PLAN REVIEW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-02-28 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-02-28 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2003-02-28 |
Time |
15:52 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2003-02-10 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-02-10 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2003-04-23 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-04-23 |
Time |
17:06 |
Rev Time |
2.00 |
| Received By |
kstevens |
Date |
2003-04-23 |
Time |
17:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2003-03-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-03-13 |
Time |
08:18 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2003-03-13 |
Time |
08:15 |
Sent To |
|
|
| Notes |
| 2003-03-13 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) 61G1-16.003 THE PERSONAL SEAL, SIGN- | | | ATURE AND DATE OF THE ARCHITECT SHALL | | | APPEAR ON ALL ARCHITECTURAL DOCUMENTS. | | | 481.221 FS | | | 2) PREVIOUS COMMENTS ARE NOT ADDRESSED. | | | 3) PLEASE INDICATE IF THERE IS AN ELE- | | | VATOR FOR VERTICAL ACCESSIBILITY. | | | 4) PLEASE INDICATE IF THERE ARE ANY | | | TOILET ROOMS ON THE FIRST FLOOR. | | | 5) PLEASE INDICATE IF THERE IS A DRINK- | | | ING FOUNTAIN AS REQUIRED BY TABLE 403.1. | | | (SEE SECTION 410.1 ALSO) | | | 6) PLEASE INDICATE HOW COMMENTS ARE | | | ADDRESSED WITH WRITTEN ANSWERS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-02-04 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-02-28 |
Time |
15:52 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2003-02-04 |
Time |
13:13 |
Sent To |
|
|
| Notes |
| 2003-02-04 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) PLEASE INDICATE IF THERE IS AN | | | ELEVATOR FOR VERTICAL ACCESSIBILITY. | | | 2) PLEASE INDICATE IF THERE ARE ANY | | | TOILET ROOMS ON THE FIRST FLOOR. | | | 3) PLEASE INDICATE IF THERE IS A DRINK- | | | ING FOUNTAIN AS REQUIRED BY TABLE 403.1 | | | (SEE SECTION 410.1 ALSO). | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2003-02-11 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-02-10 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
I |
|
| Notes |
|
|