| 2003-01-31 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) GREASE TRAP SHALL BE SIZED BY RODNEY |
| | COMPO, ENVIRONMENTAL COMPLIANCE (561) |
| | 837-4074 PER WASTE ORD. #2938-96 |
| | 2) SHT P-1 ALL SINKS IN A FOOD PREP AREA |
| | SHALL DRAIN INDIRECTLY INTO A FLOOR SINK |
| | EXCEPT HAND SINKS. |
| | 3) SHTS P-1/P-2 WHAT WILL THE FLOOR |
| | TROUGH BE USED TO DRAIN? ALL INDIRECT |
| | WASTE (CONDENSATE) SHALL DRAIN TO A F.S. |
| | 4) SHT P-2 WATER RISER, A WATER HAMMER |
| | ARRESTOR IS REQUIRED AT THE ICE MACHINE. |
| | SEC 604.9 |
| | 5) SHT P-2 GREASE RISER, JANITOR SINK |
| | NOT SHOWN ON RISER. |
| | 6) SHT P-2 WATER HEATER DETAIL, FLOOR |
| | SINK IS REQUIRED FOR PAN DRAIN AND P/T |
| | DISCHARGE. |
| | 7) FOLLOWING INFORMATION REQUIRED FOR |
| | SEPARATE GAS PERMIT APPLICATION. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | F. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | H. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | I. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | J. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | 8) SHT P-2 DRINKING FOUNTAIN SHALL |
| | COMPLY WITH 11-4.15 AND ALL SUBSECTIONS. |
| | ALSO SEE 11-4.1.3.(10)(A) PROVISIONS |
| | SHALL BE MADE FOR THOSE WHO HAVE DIFFI- |
| | CULTY BENDING OR STOOPING. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |