Plan Review Details - Permit 03011631
Plan Review Stops For Permit 03011631
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-08-14 Cont ID  
Sent By jgomez Date 2003-08-14 Time 13:38 Rev Time 0.50
Received By jgomez Date 2003-08-14 Time 13:38 Sent To PC
Notes
2003-08-14 00:00:00REVISION CHECKLIST:
 1-NEED COMPLETE BATHROOM DOOR THAT
 ALLOWS 29" CLEAR OPENING(TYP. 2'-8"
 DOORS ARE THE ONES THAT WILL WORK)
 AS REQUIRED BY SECTION 11 OF CHAPTER
 11 FBC 2001.
 2-NEED TO ADDRESS ALL THE ITEMS LISTED
 ON PROVISO DATED 4/23/04 IN ORDER TO
 AVOID ANY DELAYS OR CONFLICTS.
 SEE ATTACHED COPY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-04-23 Cont ID  
Sent By kstevens Date 2003-08-09 Time 17:58 Rev Time 4.00
Received By jgomez Date 2003-04-23 Time 15:38 Sent To  
Notes
2003-04-23 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR ALL
 EXTERIOR DOORS AND WINDOWS, STOREFRONT
 SYSTEM AT LIVING ROOM, CUSTOM MADE
 ENTRY DOOR AND GARAGE DOORS UNDERA
 SEPARATE PERMIT.
 2-MAKE SURE THAT BEDROOM EGRESS WINDOWS
 HAVE 20" MIN. CLEAR WIDTH OPENING AS
 REQUIRED BY SEC. 1005.4 FBC 2001.
  
 3-PROVIDE COMPLETE UL LISTING AND SPECS
 FOR VENTLESS FIREPLACE.
 NEED TO MEET THE REQUIREMENTS OF UL127
 AS REQUIRED BY SEC. 2806.1 FBC 2001.
 4-THERE MUST BE A COMPLETE BATHROOM WITH
 DOOR ALLOWING 29" MIN. CLEAR OPENING.
 AS REQUIRED BY SEC. 11 CHAPTER 11 FBC.
 5-ENGINEERED FLOOR SYSTEM TO BE REVIEWED
 AND APPROVED BY ARCHITECT/ENGINEER OF
 RECORD (USE STANDARD REVIEW STAMP)
 PRIOR TO SUBMITTAL TO THIS OFFICE.
 6-PROVIDE DETAIL/SPECS FOR CONNECTIONS
 OF TOP OF STEEL COLUMN TO CONCRETE
 BEAM. SEE FRAMING PLANS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-REVISE STRUCTURAL 2X BUCK DETAIL TO
 COMPLY WITH SEC. 1707.4.4.2 FBC 2001.
 8-REVISE ROOF SHEATHING INSTALLATION
 SCHEDULE. SEE TABLE 2306.1 OF CITY
 AMENDEMNTS TO FBC 2001. NEED 8D RING
 SHANK NAILS ABOVE 25' FOR ZONE 3.
 9-SPECIFY 6MIL MINIMUM VAPOR BARRIER AT
 FOUNDATION PLAN AS REQUIRED BY SECTION
 1909.2 FBC 2001.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-01 Cont ID  
Sent By hmoser Date 2003-04-21 Time 15:18 Rev Time 4.50
Received By jgomez Date 2003-03-31 Time 15:03 Sent To  
Notes
2003-03-31 00:00:00BUILDING REVIEW CHECKLIST:
 1-HOUSE LOCATED ON FLOOD ZONE A5. FIN.
 FLOOR ELEVATION TO BE 7'-6" MIN. AS
 REQ'D BY CHAPTER 12 OF CITY CODE.
 CLEARLY SHOW ON SURVEY AND FLOOR PLANS
 THE PROPOSED FIN. FLOOR ELEVATION.
 2-SURVEY DOESN'T MATCH FLOOR PLANS.
 OUTDOOR ENTERTAINMENT IS NOT SEPARATED
 FROM THE HOUSE. SEE PLANS AND REVISE.
 3-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACK STAMPED DRAWINGS & RECEIPT.
 4-NEED RECORDED NOTICE OF COMMENCEMENT.
 5-PROVIDE SOIL TEST REPORTS W/ ORIGINAL
 SIGNATURES AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
 6-PROVIDE ALL INFORMATION AS REQUIRED BY
 SEC. 1606.1.7 FBC 2001. ***NOTE: THERE
 ARE 5 ITEMS LISTED. PROVIDE ALL FIVE.
 7-A)NEED COMPLETE INFORMATION FOR PILE
 SYSTEM TO BE USED. SEE SECTIONS 1805
 THRU 1813 FBC 2001 FOR REQ'D DESIGN
 INFORMATION AND INSTALLATION.
 B)ENGINEER TO SIGN ALL SHEETS AS REQ'D
 BY CHAPTER 471 FLORIDA STATUTES.
 C)DESIGNER OF RECORD TO REVIEW & APPROVE
 THIS DELEGATED DESIGN.(REVIEWED STAMP)
 D)PILING PLAN DOESN'T MATCH DESIGNER'S
 OF RECORD FOUNDATION PLAN. REVISE/
 CLARIFY AS REQUIRED.
 8-DOORS/WINDOWS ARE TO HAVE IMPACT GLASS
 OR STORM SHUTTERS. PROVIDE PRODUCT
 APPROVAL FOR DOORS/WINDOWS OR COMPLETE
 INFO. FOR STORM SHUTTERS INCLUDING KEY
 PLAN AND COMPLETE INSTALLATION SCHED.
 (SEE CITY SAMPLE). ALSO, MARK ON DWGS
 SPECIFIC MOUNTING CONDITIONS & ANCHOR
 TYPE AND SPACING ACCORDING TO DESIGN
 PRESSURES, EDGE DISTANCE, PANEL SPAN,
 CONNECTION TYPE AND STRUCTURE TO BE
 ATTACHED TO.
 9-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS. SEC. 2405.2 FBC 2001.
 10-BEDROOM EGRESS WINDOWS NEED 20" MIN.
 CLEAR WIDTH OPENING. CLARIFY IF CASE-
 MENT WINDOWS PROVIDE THIS CLEARANCE.
 11-PROVIDE PRODUCT APPROVAL FOR: A)ENTRY
 DOOR. 4'X11' WITH ROUND TOP AS SHOWN
 ON PLANS. B)ROOF TILE. C)FRENCH DOORS
 WITH TRANSOM ABOVE SINGLE ASSEMBLY AS
 SHOWN ON PLANS. D)CASEMENT WINDOWS.
 E)WINDOWS AND DOORS MULLIONS. F)BBQ
 UL LISTING AND SPECS. G)FIREPLACE UL
 LISTING AND SPECS. H)FIXED WINDOWS AS
 SHOWN ON PLANS. I)STOREFRONT SYSTEM AS
 SHOWN ON PLANS. J)ARCHED WINDOWS.
 K)ROUND WINDOWS.
 12-PROVIDE COMPLETE AHU HANGING DETAIL.
 SPECIFY BOLTS AND CHAIN SIZE. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 13-PROVIDE COMPLETE BATHROOM IN FIRST
 FLOOR WITH DOOR THAT ALLOWS 29" MIN.
 CLEAR OPENING. SEC. 11 OF CHAPTER 11
 FBC 2001.
 14-PROVIDE COMPLETE STAIR DETAILS AND
 SECTIONS. SEE SEC. 1007.8.3 FOR CIRCU-
 LAR STAIR REQUIREMENTS.
 **ALSO SEE SEC. 1007.5.1 AND 1015.3 FOR
 HEIGHT AND CLEARANCES.
 **SEE SEC. 1606.8.2 FOR RAILING DESIGN.
 15-PROVIDE SMOKE DETECTOR AT FIRST FLOOR
 BY THE STAIRWAY AS REQUIRED BY SECTION
 905.2.2 FBC 2001.
 16-PROVIDE COMPLETE ENGINEERING PACKAGE
 AND SPECIFICATIONS FOR HAMBRO FLOOR
 SYSTEM. NOTE: DESIGNER OF RECORD TO
 REVIEW ALL INFO. PRIOR TO SUBMITTAL
 17-PROVIDE ATTIC ACCESS AT SECONF FLOOR
 ROOF AND AT ROOF ABOVE GARAGE AS REQ'D
 BY SEC. 2309.6 FBC 2001.
 18-PROVIDE VENTILATION AT ATTIC AREA AS
 REQ'D BY SEC. 2309.7 FBC 2001.
 19-PROVIDE DETAILS/SPECS FOR CONNECTIONS
 AT TOP OF STEEL COLUMNS. SEE PLANS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 20-SHEET S-4: SPECIFY ALL BEAMS AND
 CONNECTORS. SEE PLANS FOR COMMENTS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 21-PROVIDE COMPLETE DETAILS & SPECS FOR
 STRUCTURAL LEDGERS. SEE PLANS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 22-PROVIDE COMPLETE FIREPLACE STRUCTURAL
 SECTION. INCLUDING CHIMNEY. SPECIFY
 ALL FASTENERS. SHOW CHIMNEY ON EXT.
 ELEVATIONS. SEC. 2804 FBC 2001 & SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 23-PROVIDE COMPLETE FRAMING DETAILS AND
 SPECS FOR WOOD TRELLIS.SPECIFY ALL
 FASTENERS. SEC. 104.2.1.2 CITY AMEND.
 24-PROVIDE COMPLETE DETAILS AND SPECS
 FOR CEILING INSTALLATION AT FRONT AND
 REAR PORCHES. SPECIFY FASTENERS AS
 REQ'D BY ASTM C-926 AND ASTM C-1063.
 25-REVISE 2X STRUCTURAL BUCK DETAIL FOR
 DOOR. SEE SEC. 1707.4.4.2 FBC 2001 FOR
 SPECIFIC INSTALLATION REQUIREMENTS.
 26-PROVIDE ROOF SHEATHING SCHEDULE. SEE
 SEC. 2306.1 CITY AMENDMENTS TO FBC.
 27-SPECIFY WWM SUPPORTS AND SPACING AS
 REQUIRED BY SEC. 1909.3 FBC 2001.
 28-OWES $497.64 FOR UPDATED VALUATION
 AND RADON FEES.
 29-SEE REVIEWED SET OF PLANS FOR ADDITIO
 NAL COMMENTS/CLARIFICATIONS AND RETURN
 REVIEWED SET AFTER CORRECTIONS ARE DONE
 TO ORIGINAL CAD DRAWINGS TO EXPEDITE
 THE REVIEW PROCESS.
 30-REVISE ENERGY CALCS: A)A/C AREA DOES
 NOT MATCH PLANS. B)WALL TYPE SPECIFIED
 IS INCORRECT. SEE PLANS FOR ADJACENT
 WALL. C)OWNER/AGENT TO SIGN AND DATE
 BOTTOM OF FORM AS WELL. D)COMPLETE ALL
 INFORMATION ON TOP OF FORM.
 31-IF TAKING CEILING FANS CREDIT, THEN
 NEED TO SHOW THEM IN PLANS. SEE TABLE
 6-6 OF CHAPTER 13 FBC 2001 FOR REQUIRED
 SIZES AND NUMBER.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-04-25 Cont ID  
Sent By btrobaug Date 2003-04-25 Time 11:37 Rev Time 1.00
Received By btrobaug Date 2003-04-25 Time 10:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-04-18 Cont ID  
Sent By btrobaug Date 2003-04-18 Time 09:41 Rev Time 1.00
Received By btrobaug Date 2003-04-18 Time 09:11 Sent To P
Notes
2003-04-18 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 THE FOLLOWING CORRECTIONS WERE NOT MADE
 FROM THE LAST REVIEW,PLEASE CORRECT
 AND RESUBMIT FOR REVIEW.
  
 1} THE GEC TO THE GROUND ROD IS THE
 CORRECT SIZE BUT MUST BE CONTINUOUS PER
 250-64,TO THE FOOTER STEEL,GROUND ROD
 AND COLD WATER PIPE.
  
 2} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 3} THE GFI IN THE MASTER BATH MUST
 COMPLY WITH 210-52(D).OR ADD ONE TO
 COMPLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-03-17 Cont ID  
Sent By shernand Date 2003-04-16 Time 13:25 Rev Time 1.00
Received By btrobaug Date 2003-03-17 Time 10:27 Sent To  
Notes
2003-03-17 00:00:00PROVISO
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 AND RESUBMIT FOR REVIEW PRIOR TO ROUGH
 ELECTRICAL INSPECTION.
  
 1} THE GEC IS INCORRECT FOR A 400 AMP.
 SERVICE,SEE 250-66.
  
 2} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
  
 3} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 4} THE RECEPTACLE IN THE CABANA BATH
 SHOULD BE GFI PER 210-8.
  
 5} PLEASE CORRECT THE CALCULATION FOR
 THE POOL PANEL,SHOWN AS 1.8 VA.
  
 6} PLEASE NOTE THE RECEPTACLE SPACING IN
 THE MUSIC ROOM NEEDS TO COMPLY WITH
 210-52.
  
 7} WHERE IS THE POOL EQUIPMENT PANEL
 LOCATED?
  
 8} THE GFI IN THE MASTER BATH MUST
 COMPLY WITH 210-52(D).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561-8096 EXT.8392

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-31 Cont ID  
Sent By alange Date 2003-07-31 Time 10:33 Rev Time 0.00
Received By alange Date 2003-07-31 Time 10:33 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-16 Cont ID  
Sent By shernand Date 2003-04-16 Time 13:25 Rev Time 0.00
Received By shernand Date 2003-04-16 Time 13:25 Sent To E
Notes
2003-04-16 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-25 Cont ID  
Sent By dpalmer Date 2003-02-25 Time 09:54 Rev Time 0.00
Received By dpalmer Date 2003-02-25 Time 09:54 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-04-21 Cont ID  
Sent By hmoser Date 2003-04-21 Time 15:18 Rev Time 1.00
Received By hmoser Date 2003-04-21 Time 15:18 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-03-19 Cont ID  
Sent By kstevens Date 2003-04-18 Time 15:54 Rev Time 0.50
Received By hmoser Date 2003-03-19 Time 15:38 Sent To B
Notes
2003-03-19 00:00:00PLAN DENIED
 NO PLANS,NO MANUAL (J)
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8221

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-12-07 Cont ID  
Sent By pschmitz Date 2004-12-07 Time 10:56 Rev Time 0.00
Received By pschmitz Date 2004-12-07 Time 10:56 Sent To  
Notes
2004-12-07 00:00:00PLUMBING REVISION ON U/G OK

Review Stop P PLUMBING
Rev No 3 Status N Date 2003-08-09 Cont ID  
Sent By kstevens Date 2003-08-09 Time 17:58 Rev Time 0.25
Received By kstevens Date 2003-08-09 Time 17:57 Sent To B
Notes
2003-08-09 00:00:00NO PLUMBING PLANS REVISED

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-04-18 Cont ID  
Sent By alange Date 2003-07-31 Time 10:33 Rev Time 0.50
Received By kstevens Date 2003-04-18 Time 15:52 Sent To M
Notes
2003-04-18 00:00:00PASSED/PROVISO
  
 REVISION REQUIRED - SANT. RISER SHALL
 REFLECT FLOOR PLAN.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-03-17 Cont ID  
Sent By btrobaug Date 2003-04-18 Time 09:41 Rev Time 0.75
Received By jleech Date 2003-03-17 Time 17:41 Sent To M
Notes
2003-03-17 00:00:00DENIED;
 1.THE WET VENT FOR THE BATHROOMS SHALL
 BE UPSTREAM OF THE FIXTURES BEING
 VENTED.
 2.POWDER ROOM WATER CLOSET IS NOT VENTED
 3.BIDET IN UNVENTED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop Z ZONING
Rev No 2 Status P Date 2003-03-04 Cont ID  
Sent By sgraham Date 2003-03-04 Time 15:33 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-01-24 Cont ID  
Sent By dpalmer Date 2003-02-25 Time 09:54 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-01-24 00:00:00DENIED BY ZONING
 1.NEED SURVEY
 2. SEPARATE PERMIT REQUIRED FOR WALL, TH
 THE MAX HEIGHT OF WALL IN FRONT SETBACK
 IS 4'.AN EASEMENT RELEASE IS REQUIRED
 FROM THE WATER DEPT
 3. TOTAL HEIGHT OF BLDG WITH THE
 ORNAMENT MAY NOT EXCEED 33', MEASURING
 FROM THE GRADE NOT FLOOR ELEVATION.