Plan Review Details - Permit 03011556
Plan Review Stops For Permit 03011556
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-03-19 Cont ID  
Sent By hpiskura Date 2003-03-19 Time 13:08 Rev Time 0.00
Received By hpiskura Date 2003-03-19 Time 13:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-02-10 Cont ID  
Sent By hpiskura Date 2003-02-10 Time 15:21 Rev Time 0.00
Received By hpiskura Date 2003-03-19 Time 13:08 Sent To  
Notes
2003-02-10 00:00:00PLEASE PROVIDE A SEATING PLAN WITH
 DIMENSIONS FOR THE PROPOSED TABLE
 LAYOUT IN THE REAR OF THE RESTAURANT.
 SEE FBC 1003.1.2

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-03-18 Cont ID  
Sent By dpalmer Date 2003-03-18 Time 08:42 Rev Time 0.50
Received By dpalmer Date 2003-03-18 Time 08:42 Sent To  
Notes
2003-03-18 00:00:00PROVISO
  
 PROVIDE LOAD CALCULATIONS AND PANEL
 SCHEDULES THAT CORRELATE W/ CIRCUITS
 ON PLANS.
 SUBMIT FOR REVIEW BEFORE FINAL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-01-28 Cont ID  
Sent By dpalmer Date 2003-01-28 Time 07:08 Rev Time 0.33
Received By dpalmer Date 2003-01-28 Time 07:04 Sent To  
Notes
2003-01-28 00:00:00**************** UNSAT ***************
  
 1)NOTE:PLEASE PROVIDE LOAD CALCULATION
 FOR NEW CIRCUITS/EQUIPMENT BEING ADDED.
 PLEASE SHOW NEW TRK LIGHTING PER 220-12
 AND SHOW ALL CONTINUOUS LOADS AT 125%
 215-3,230-42 ETC.
  
 2)NOTE: PLEASE PROVIDE A PANEL SCHEDULE
 TO CORRELATE WITH NEW CIRCUITS AND SHOW
 NEW CIRCUTIS ON PLANS/FLOOR LAYOUT.
  
 PLEASE SEE FIRE REVIEW COMMENTS THAT
 MAY OR MAY-NOT AFFECT ELECTRICAL PLANS.
 VERIFY EM LTS AND EXT LTS. 700-12E
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARENY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-03-19 Cont ID  
Sent By mcarsill Date 2003-03-19 Time 12:52 Rev Time 0.00
Received By mcarsill Date 2003-03-19 Time 12:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-01-23 Cont ID  
Sent By mcarsill Date 2003-01-23 Time 13:38 Rev Time 0.00
Received By mcarsill Date 2003-01-23 Time 13:38 Sent To  
Notes
2003-01-23 00:00:001) PROPOSED TABLE LAYOUT WILL NOT
 ALLOW FOR PROPER EXITING. NO AISLES
 OR EXIT ACCESS IS PROVIDED. TABLES
 AND CHAIRS ARE LOCATED DIRECTLY IN
 FRONT OF EXISTING EXIT DOORS.
  
 2) ENSURE ALL EXISTING EXIT SIGNS AND
 EMERGENCY LIGHTING FIXTURES ARE
 OPERATIONAL.
  
 3) ENSURE SEATING HAS BEEN PROVIDED FOR
 THE HANDICAPPED.
  
 4) SEPARATE PLANS AND PERMITS ARE
 REQUIRED FOR ANY NEW HOOD,DUCT,AND
 EXTINGUISHING SYSTEMS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-13 Cont ID  
Sent By sthyng Date 2003-03-13 Time 14:06 Rev Time 0.00
Received By sthyng Date 2003-03-13 Time 14:06 Sent To  
Notes
2003-03-13 00:00:00COMM BOARD #2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-22 Cont ID  
Sent By btrobaug Date 2003-01-22 Time 17:43 Rev Time 0.00
Received By btrobaug Date 2003-01-22 Time 17:43 Sent To  
Notes
2003-01-22 00:00:00COMM BOARD#4./WRT

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-03-25 Cont ID  
Sent By hmoser Date 2003-03-25 Time 16:07 Rev Time 0.25
Received By hmoser Date 2003-03-25 Time 16:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-02-04 Cont ID  
Sent By kstevens Date 2003-03-25 Time 11:49 Rev Time 0.35
Received By pkrauss Date 2003-02-04 Time 13:56 Sent To  
Notes
2003-02-04 00:00:00DENIED:
 PROVIDE OUTSIDE AIR CALCULATIONS AS PER
 2001 FBC(M) TABLE 403.3.
  
 PROVISO:
 ADDITIONAL PERMITS REQUIRED FOR HOOD &
 FIRE SUPRESSION.PLEASE PROVIDE PLANS
 WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-03-25 Cont ID  
Sent By kstevens Date 2003-03-25 Time 11:48 Rev Time 2.00
Received By kstevens Date 2003-03-22 Time 10:53 Sent To M
Notes
2003-03-25 00:00:00PASSED/PROVISO
  
 BIG DIPPER APPROVED BY R. COMPO UTILITY
 DEPT. ENVIRONMENTAL COMPLIANCE.
  
 SEPARATE GAS PERMIT REQUIRED

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-01-25 Cont ID  
Sent By kstevens Date 2003-01-25 Time 06:57 Rev Time 0.50
Received By kstevens Date 2003-01-25 Time 06:57 Sent To  
Notes
2003-01-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) ROUTE PLANS TO DEPT. OF BUSNIESS
 REGULATION HOTEL & RESTURANT DIVISION
 (954)956-5692 FOR REVIEW PRIOR TO RE-
 SUBMITTING TO WPB FOR REVIEW. PLANS
 SHALL HAVE HEALTH DEPT STAMP AND REVIEW
 SHEETS ATTACHED.
 2) SHT 3 PLEASE PROVIDE A SANITARY AND
 A WATER RISER DIAGRAM.
 3) SHT 3 GAS INFORMATION. ALL REFERENCES
 FOR GAS SHALL BE FBC-2001 FUEL GAS.
 PLEASE CHANGE ALL REFERENCES. TABLE
 402(3) UTILITY GAS WILL BE USED.
 4) SEPARATE GAS PERMIT REQUIRED. FOLLOW-
 ING IS GAS APPLICATION REQUIREMENT FOR
 PERMIT.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. TYPE OF GAS, (LP OR NATURAL)
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 D. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 5) SHT 3 DISHWASHER SHALL DRAIN TO SAN-
 ITARY NOT GREASE WASTE. UTILITY ORD.
 6) SHT 1 SHOW WATER AND SANITARY TO ALL
 NEW FIXTURES ON RISER DIAGRAMS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2003-03-25 Cont ID  
Sent By hpiskura Date 2003-02-10 Time 15:30 Rev Time 0.00
Received By kstevens Date 2003-02-10 Time 15:30 Sent To  
Notes
2003-02-10 00:00:00A SIDEWALK TABLE DINING PERMIT IS
 REQUIRED FOR THE PROPOSED TABLES TO BE
 PLACED ALONG OLIVE AVE. AND IS NOT
 INCLUDED WITH THIS PERMIT APPLICATION.
 PLEASE CONTACT JOSH LONG AT
 561-659-8031 FOR ADDITIONAL INFORMATION.