| Plan Review Stops For Permit 03011556 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2003-03-19 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-03-19 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2003-03-19 |
Time |
13:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-02-10 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-02-10 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2003-03-19 |
Time |
13:08 |
Sent To |
|
|
| Notes |
| 2003-02-10 00:00:00 | PLEASE PROVIDE A SEATING PLAN WITH | | | DIMENSIONS FOR THE PROPOSED TABLE | | | LAYOUT IN THE REAR OF THE RESTAURANT. | | | SEE FBC 1003.1.2 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2003-03-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-03-18 |
Time |
08:42 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-03-18 |
Time |
08:42 |
Sent To |
|
|
| Notes |
| 2003-03-18 00:00:00 | PROVISO | | | | | | PROVIDE LOAD CALCULATIONS AND PANEL | | | SCHEDULES THAT CORRELATE W/ CIRCUITS | | | ON PLANS. | | | SUBMIT FOR REVIEW BEFORE FINAL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-01-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-01-28 |
Time |
07:08 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-01-28 |
Time |
07:04 |
Sent To |
|
|
| Notes |
| 2003-01-28 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE:PLEASE PROVIDE LOAD CALCULATION | | | FOR NEW CIRCUITS/EQUIPMENT BEING ADDED. | | | PLEASE SHOW NEW TRK LIGHTING PER 220-12 | | | AND SHOW ALL CONTINUOUS LOADS AT 125% | | | 215-3,230-42 ETC. | | | | | | 2)NOTE: PLEASE PROVIDE A PANEL SCHEDULE | | | TO CORRELATE WITH NEW CIRCUITS AND SHOW | | | NEW CIRCUTIS ON PLANS/FLOOR LAYOUT. | | | | | | PLEASE SEE FIRE REVIEW COMMENTS THAT | | | MAY OR MAY-NOT AFFECT ELECTRICAL PLANS. | | | VERIFY EM LTS AND EXT LTS. 700-12E | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARENY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2003-03-19 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-03-19 |
Time |
12:52 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-03-19 |
Time |
12:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2003-01-23 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-01-23 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-01-23 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2003-01-23 00:00:00 | 1) PROPOSED TABLE LAYOUT WILL NOT | | | ALLOW FOR PROPER EXITING. NO AISLES | | | OR EXIT ACCESS IS PROVIDED. TABLES | | | AND CHAIRS ARE LOCATED DIRECTLY IN | | | FRONT OF EXISTING EXIT DOORS. | | | | | | 2) ENSURE ALL EXISTING EXIT SIGNS AND | | | EMERGENCY LIGHTING FIXTURES ARE | | | OPERATIONAL. | | | | | | 3) ENSURE SEATING HAS BEEN PROVIDED FOR | | | THE HANDICAPPED. | | | | | | 4) SEPARATE PLANS AND PERMITS ARE | | | REQUIRED FOR ANY NEW HOOD,DUCT,AND | | | EXTINGUISHING SYSTEMS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-03-13 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-13 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-13 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2003-03-13 00:00:00 | COMM BOARD #2 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-01-22 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-01-22 |
Time |
17:43 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2003-01-22 |
Time |
17:43 |
Sent To |
|
|
| Notes |
| 2003-01-22 00:00:00 | COMM BOARD#4./WRT |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2003-03-25 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2003-03-25 |
Time |
16:07 |
Rev Time |
0.25 |
| Received By |
hmoser |
Date |
2003-03-25 |
Time |
16:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2003-02-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-03-25 |
Time |
11:49 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2003-02-04 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2003-02-04 00:00:00 | DENIED: | | | PROVIDE OUTSIDE AIR CALCULATIONS AS PER | | | 2001 FBC(M) TABLE 403.3. | | | | | | PROVISO: | | | ADDITIONAL PERMITS REQUIRED FOR HOOD & | | | FIRE SUPRESSION.PLEASE PROVIDE PLANS | | | WITH PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2003-03-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-03-25 |
Time |
11:48 |
Rev Time |
2.00 |
| Received By |
kstevens |
Date |
2003-03-22 |
Time |
10:53 |
Sent To |
M |
|
| Notes |
| 2003-03-25 00:00:00 | PASSED/PROVISO | | | | | | BIG DIPPER APPROVED BY R. COMPO UTILITY | | | DEPT. ENVIRONMENTAL COMPLIANCE. | | | | | | SEPARATE GAS PERMIT REQUIRED |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-01-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-01-25 |
Time |
06:57 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-01-25 |
Time |
06:57 |
Sent To |
|
|
| Notes |
| 2003-01-25 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | | | | 1) ROUTE PLANS TO DEPT. OF BUSNIESS | | | REGULATION HOTEL & RESTURANT DIVISION | | | (954)956-5692 FOR REVIEW PRIOR TO RE- | | | SUBMITTING TO WPB FOR REVIEW. PLANS | | | SHALL HAVE HEALTH DEPT STAMP AND REVIEW | | | SHEETS ATTACHED. | | | 2) SHT 3 PLEASE PROVIDE A SANITARY AND | | | A WATER RISER DIAGRAM. | | | 3) SHT 3 GAS INFORMATION. ALL REFERENCES | | | FOR GAS SHALL BE FBC-2001 FUEL GAS. | | | PLEASE CHANGE ALL REFERENCES. TABLE | | | 402(3) UTILITY GAS WILL BE USED. | | | 4) SEPARATE GAS PERMIT REQUIRED. FOLLOW- | | | ING IS GAS APPLICATION REQUIREMENT FOR | | | PERMIT. | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. | | | B. TYPE OF GAS, (LP OR NATURAL) | | | C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2 | | | D. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | 5) SHT 3 DISHWASHER SHALL DRAIN TO SAN- | | | ITARY NOT GREASE WASTE. UTILITY ORD. | | | 6) SHT 1 SHOW WATER AND SANITARY TO ALL | | | NEW FIXTURES ON RISER DIAGRAMS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2003-03-25 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-02-10 |
Time |
15:30 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2003-02-10 |
Time |
15:30 |
Sent To |
|
|
| Notes |
| 2003-02-10 00:00:00 | A SIDEWALK TABLE DINING PERMIT IS | | | REQUIRED FOR THE PROPOSED TABLES TO BE | | | PLACED ALONG OLIVE AVE. AND IS NOT | | | INCLUDED WITH THIS PERMIT APPLICATION. | | | PLEASE CONTACT JOSH LONG AT | | | 561-659-8031 FOR ADDITIONAL INFORMATION. |
|
|