Rev No 4 Status P Date 2003-03-19 Cont ID  
Sent By hpiskura Date 2003-03-19 Time 07:27 Rev Time 0.00
Received By hpiskura Date 2003-03-19 Time 07:27 Sent To  
Notes
2003-03-19 00:00:00REVISIONS DATED 2/7/03 AND 2/12/03.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-03-05 Cont ID  
Sent By dpalmer Date 2003-03-17 Time 06:36 Rev Time 0.00
Received By hpiskura Date 2003-03-05 Time 07:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-02-27 Cont ID  
Sent By btrobaug Date 2003-02-28 Time 17:09 Rev Time 0.00
Received By hpiskura Date 2003-02-26 Time 16:13 Sent To  
Notes
2003-02-26 00:00:00THE ALBERT A. GARGIULO, PE PLAN S1
 DATED2/17/03 DOES NOT HAVE SUFFICIENT
 FOUNDATION INFORMATION.
  
 SECTION 1 CALLS FOR A 3000# CAPACITY
 TIEDOWN.NOTE 1 CALLS FOR 6200# MIN
 ULTIMATE.
  
 THE SCHEDULE SHOWS THREE PIER TYPES.
 NONE ARE SELECTED.THE PLANS DO NOT
 SHOW THE LOCATION, PLACEMENT, TYPE OR
 NUMBER OF PIERS TO BE USED.
  
 THE SCHEDULE SHOWS TWO SOIL BEARING
 VALUES AS A FUNCTION OF VERTICAL TIES
 TO BE INCORPORATED.NO SELECTION IS
 SHOWN.
  
 THE FOUNDATION ENGINEER SHOULD REVIEW
 THE NOTE UNDER "FOUNDATION" ON SHEET OF
 1 OF 3 OF THE IMS PLAN DATED 11/12/02
 AND CHAPTER 61G15-31 RESPONSIBILTY
 RULES FO PROFESSIONAL ENGINEER
 CONCERNING THE DESIGN OF STRUCTURES, OF
 THE FLORIDA ADMINISTRATIVE CODE.
  
 THE FOUNDATION NOTES ARE NOT VERY
 LEGIBLE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-02-05 Cont ID  
Sent By hpiskura Date 2003-02-05 Time 15:29 Rev Time 0.00
Received By hpiskura Date 2003-02-05 Time 15:28 Sent To  
Notes
2003-02-05 00:00:00PLEASE PROVIDE A FOUNDATION PLAN FOR THE
 RELOCATED MODULAR BUILDING.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-03-17 Cont ID  
Sent By dpalmer Date 2003-03-17 Time 06:36 Rev Time 0.25
Received By dpalmer Date 2003-03-17 Time 06:36 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-02-25 Cont ID  
Sent By lmartine Date 2003-03-13 Time 18:14 Rev Time 0.25
Received By dpalmer Date 2003-02-25 Time 13:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-02-20 Cont ID  
Sent By dpalmer Date 2003-02-20 Time 18:55 Rev Time 0.25
Received By dpalmer Date 2003-02-20 Time 18:55 Sent To  
Notes
2003-02-20 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SEE PLANS, PLANS HAVE
 A HANDWRITTEN NOTE THAT MENTIONS,PANEL
 TO BE REMOVED?? PLEASE CLARIFY HOW
 UNIT/BLDG IS GOING TO BE FED IF PANEL
 IS REMOVED? PLEASE ALSO NOTE, PER FS/FAC
 ALL CHANGES TO PLANS MUST BE DONE BY THE
 ARCH/ ENGINEER OF RECORD. 471.025/,
 481.221
  
 PLEASE SEE FIRST REVIEW NOTES AND SUBMIT
 THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-01-28 Cont ID  
Sent By dpalmer Date 2003-01-28 Time 06:12 Rev Time 0.33
Received By dpalmer Date 2003-01-28 Time 06:10 Sent To  
Notes
2003-01-28 00:00:00**********UNSAT ******************
  
 1)NOTE: PLEASE NOTE, PANEL IS SHOWN
 BEHIND DESK AREA ON PLAN. IT IS NOTED
 THAT "DESK IS MOVABLE" . PLEASE NOTE
 PER NEC 110-26 WORKING CLEARENCES ARE
 ALL THE TIME. PLEASE ADJUST FURNITURE
 LAYOUT TO MEET 110-26.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 2)NOTE: PLEASE SUBMIT/SHOW AIC RATING
 FOR NEW MAIN DISCONNECT. 110-9

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-02-10 Cont ID  
Sent By nmccray Date 2003-02-10 Time 11:12 Rev Time 0.00
Received By nmccray Date 2003-02-10 Time 11:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status   Date 2003-03-13 Cont ID  
Sent By lmartine Date 2003-03-13 Time 18:14 Rev Time 0.00
Received By lmartine Date   Time   Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-03-06 Cont ID  
Sent By sgraham Date 2003-03-13 Time 09:47 Rev Time 0.00
Received By dpalmer Date 2003-03-06 Time 14:23 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-02-28 Cont ID  
Sent By btrobaug Date 2003-02-28 Time 17:09 Rev Time 0.00
Received By btrobaug Date 2003-02-28 Time 17:09 Sent To B
Notes
2003-02-28 00:00:00TO HHP./WRT

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-02-20 Cont ID  
Sent By dpalmer Date 2003-02-20 Time 09:14 Rev Time 0.00
Received By dpalmer Date 2003-02-20 Time 09:14 Sent To  
Notes
2003-02-20 00:00:00TO COMM BOARD #21

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-27 Cont ID  
Sent By dpalmer Date 2003-01-27 Time 06:11 Rev Time 0.00
Received By dpalmer Date 2003-01-27 Time 06:11 Sent To  
Notes
2003-01-28 00:00:00TO COMM BOARD #9

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-23 Cont ID  
Sent By dpalmer Date 2003-01-23 Time 09:27 Rev Time 0.00
Received By dpalmer Date 2003-01-23 Time 09:27 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-03-05 Cont ID  
Sent By sgraham Date 2003-01-24 Time 16:04 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2003-03-13 Cont ID  
Sent By sgraham Date 2003-03-13 Time 09:46 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-01-24 Cont ID  
Sent By dpalmer Date 2003-03-06 Time 14:23 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved