Plan Review Details - Permit 03011360
Plan Review Stops For Permit 03011360
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-01-30 Cont ID  
Sent By btrobaug Date 2003-01-30 Time 08:05 Rev Time 0.50
Received By lsmith Date 2003-01-30 Time 11:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-02-12 Cont ID  
Sent By pschmitz Date 2003-02-20 Time 15:10 Rev Time 0.25
Received By btrobaug Date 2003-02-12 Time 15:54 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-01-30 Cont ID  
Sent By btrobaug Date 2003-02-12 Time 15:43 Rev Time 0.33
Received By btrobaug Date 2003-01-30 Time 08:00 Sent To B
Notes
2003-01-30 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE A LOAD CALCULATION
 SHOWING THE EXISTING LOAD AND ALL
 ADDITIONAL LOADS TO THE SERVICE.ALSO
 INDICATE THE SIZE OF THE ELECTRICAL
 SERVICE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-02-12 Cont ID  
Sent By btrobaug Date 2003-02-12 Time 15:43 Rev Time 0.00
Received By btrobaug Date 2003-02-12 Time 15:42 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-23 Cont ID  
Sent By dpalmer Date 2003-01-23 Time 10:31 Rev Time 0.00
Received By dpalmer Date 2003-01-23 Time 10:30 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-02-20 Cont ID  
Sent By btrobaug Date 2003-02-12 Time 15:54 Rev Time 1.00
Received By pschmitz Date   Time   Sent To E
Notes
2003-02-20 00:00:00REVISION, APPR. PES

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-01-29 Cont ID  
Sent By sgraham Date 2003-01-28 Time 10:50 Rev Time 0.33
Received By kstevens Date 2003-01-29 Time 09:23 Sent To E
Notes
2003-01-29 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 2) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 3) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 4) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 5) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 6) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 7) FBC-2001 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2003-01-28 Cont ID  
Sent By dpalmer Date 2003-01-23 Time 10:31 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***