Plan Review Details - Permit 03011308
Plan Review Stops For Permit 03011308
Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-01-23 Cont ID  
Sent By pkrauss Date 2003-01-23 Time 09:06 Rev Time 0.30
Received By pkrauss Date 2003-01-23 Time 09:06 Sent To  
Notes
2003-01-23 00:00:00PROVISO:
  
 AHU #1 IN THE ATTIC - 2001 FBC CHAPTER
 13 SECTION 610.1.ABC.3.5.2:
  
 1.THE SERVICE PANEL OF THE EQUIPMENT
 IS LOCATED WITHIN 6 FT OF AN ATTIC ACCES
  
 3.THE ATTIC OPENING IS OF SUFFICIENT
 SIZE TO REPLACE THE AIR HANDLER.
  
 4.A NOTICE IS POSTED ON THE ELECTRIC
 PANEL INDICATING TO THE HOMEOWNER THAT
 THE AIR HANDLER IS LOCATED IN THE ATTIC.
  
 AHU 2 IS REQUIRED TO HAVE A DRAIN PAN
 WITH OVERFLOW PROTECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.