| 2003-02-14 00:00:00 | **********CORRECTIONS************ |
| | |
| | 1.)INDICATE THE PROPOSED OCCUPANCY |
| | (STORAGE) ON THE PERMIT APPLICATION |
| | AS PER FBC 104.1.5. |
| | |
| | 2.)DRAWINGS ARE TO BE TO SCALE (MIN. |
| | 1/8) AS PER FBC 104.2. |
| | |
| | 3.)PLEASE PROVIDE DETAILS OF |
| | EXISTING CONDITIONS - WALL SECTION, |
| | FROM FOUNDATION THROUGH ROOF INCLUDING |
| | ATTACHMENTS. |
| | |
| | 4.)PLEASE PROVIDE ON PLAN: |
| | A.WALL SECTION FROM FOUNDATION |
| | THROUGH ROOF, INCLUDING |
| | ASSEMBLY AND MATERIALS |
| | B.CONNECTOR TABLES |
| | C.WIND REQUIREMENTS |
| | |
| | 5.)PLEASE PROVIDE ON PLAN THE |
| | SIZE, GRADE, TYPE AND LOCATION OF |
| | REINFORCEMENT, ANCHORS AND WALL TIES |
| | TO BE USED IN THE MASONRY WALL AS PER |
| | FBC 2101.2.OPENINGS (WINDOWS AND |
| | DOORS) SHALL HAVE LINTELS OF REINFORCED |
| | CONCRETE AS PER FBC 2121.2.11.2. |
| | |
| | 7.)PLEASE PROVIDE A FOOTER DETAIL |
| | INCLUDING SIZE OF PROPOSED FOOTER AND |
| | TYPE OF LOCATION OF REINFORCEMENT. |
| | ALSO PLEASE INCLUDE THE DEPTH THAT |
| | THE NEW REINFORCEMENT WILL PENETRATE |
| | INTO THE EXISTING FOOTERS. |
| | |
| | 8.)ALL WINDOWS, DOORS, AND HURRICANE |
| | SHUTTERS ARE REQUIRED TO HAVE PRODUCT |
| | APPROVALS. |
| | |
| | 9.)HURRICANE PROTECTION IS REQUIRED |
| | FOR WINDOWS AS PER FBC 2413.1. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | LEA SMITH OR SAMANTHA THYNG |
| | 561-659-8096, EXTENSION 8340 |