Plan Review Details - Permit 03011201
Plan Review Stops For Permit 03011201
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-04-01 Cont ID  
Sent By hmoser Date 2003-04-07 Time 15:16 Rev Time 0.00
Received By hpiskura Date 2003-04-01 Time 13:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-01-29 Cont ID  
Sent By hpiskura Date 2003-01-29 Time 14:29 Rev Time 0.00
Received By hpiskura Date 2003-01-29 Time 14:25 Sent To  
Notes
2003-01-29 00:00:00THE PLYWOOD SHEATHING AND WOOD FRAMING
 MEMBERS SHOWN IN SECTION IN VARIOUS
 PLACES ON THE PLANS IS NOT ALLOWED IN
 EXTERIOR WALLS OF TYPE V CONSTRUCTION.
 SEE FBC 607, WHICH IS THE MINIMUM
 CONSTRUCTION TYPE PERMITTED IN THE FIRE
 DISTRICT.PLEASE REVISE AS NECESSARY.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-10-14 Cont ID  
Sent By dpalmer Date 2003-10-14 Time 06:57 Rev Time 0.75
Received By dpalmer Date 2003-10-14 Time 06:56 Sent To  
Notes
2003-10-14 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE CORRELATE PLANS AND PANEL
 SCHEDULE.
 PLEASE SEE THAT PANEL "A" AND "C" SHOW
 A/C UNITS (#6).
 PLEASE ALSO SEE THAT PLANS ONLY SHOW
 5 A/C SYSTEMS AND PANEL SCHEDULES SHOW
 6? PLEASE CORRELATE AND/OR CLARIFY.
  
 2)NOTE: PLEASE PROVIDE ALL LICENSE
 INFORMATION ON TITLE BLOCK REQ'D UNDER
 FAC 61G15-23.002 AND FS 471
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-03-27 Cont ID  
Sent By dpalmer Date 2003-03-27 Time 05:46 Rev Time 0.33
Received By dpalmer Date 2003-03-27 Time 05:46 Sent To  
Notes
2003-03-27 00:00:00*************************************
  
 NOTE REDLINED FOR EXIT LT SHOWN ON
 PANEL SCHEDULE BEING CONTROLLED BY
 PHOTO CELL??
 700-12E.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-01-31 Cont ID  
Sent By dpalmer Date 2003-01-31 Time 09:28 Rev Time 0.50
Received By dpalmer Date 2003-01-31 Time 09:25 Sent To  
Notes
2003-01-31 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 THAT WILL AFFECT ELECTRICAL PLANS.
  
 2)NOTE: PLEASE SHOW LOAD CALCULATION
 AND SHOW CONTINUOUS @125%.
  
 PLEASE SUBMIT THE ABOVEINFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2003-09-17 Cont ID  
Sent By mamini Date 2003-09-17 Time 09:20 Rev Time 0.50
Received By mamini Date 2003-09-17 Time 09:20 Sent To  
Notes
2003-09-17 00:00:00PASSED:
 1. PROPOSAL AS SUBMITTED TO REPAIR THE
 CONCRETE PARKING LOT APPROVED.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2003-01-30 Cont ID  
Sent By mamini Date 2003-01-30 Time 08:37 Rev Time 1.00
Received By mamini Date 2003-01-30 Time 08:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-10-21 Cont ID  
Sent By nmccray Date 2003-10-21 Time 10:42 Rev Time 0.00
Received By nmccray Date 2003-10-21 Time 10:41 Sent To  
Notes
2003-10-21 00:00:00REVISION DATED 10-03-03

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-03-20 Cont ID  
Sent By mcarsill Date 2003-03-20 Time 12:47 Rev Time 0.00
Received By mcarsill Date 2003-03-20 Time 12:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-01-23 Cont ID  
Sent By mcarsill Date 2003-01-23 Time 14:39 Rev Time 0.00
Received By mcarsill Date 2003-01-23 Time 14:39 Sent To  
Notes
2003-01-23 00:00:001) THE NEW ROLLING CHAIN-LINK GATE
 WHEN OPENED MUST PROVIDE AT LEAST
 20 FEET IN CLEAR WIDTH.
  
 2) IT APPEARS THAT ADDITIONAL EXIT
 SIGNS WILL BE NEEDED. IN SOME LOCALES,
 EXIT SIGNS APPEAR TO BE BLOCKED
 VISUALLY BY WALLS.
  
 3) IF THE EAST ELEVATION IS THE ADDRESS
 SIDE OF THE BUILDING, THEN THE ADDRESS
 SHALL BE BE POSTED WITH A MINIMUM OF
 6" LETTERS.
  
 4) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-06 Cont ID  
Sent By csiegber Date 2003-10-06 Time 10:03 Rev Time 0.00
Received By csiegber Date 2003-10-06 Time 10:03 Sent To  
Notes
2003-10-06 00:00:00TO COMM BD#20

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-18 Cont ID  
Sent By sthyng Date 2003-03-18 Time 11:37 Rev Time 0.00
Received By sthyng Date 2003-03-18 Time 11:37 Sent To  
Notes
2003-03-18 00:00:00COMM BOARD #45

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-17 Cont ID  
Sent By btrobaug Date 2003-01-17 Time 18:14 Rev Time 0.00
Received By btrobaug Date 2003-01-16 Time 18:14 Sent To  
Notes
2003-01-17 00:00:00COMM BOARD#13./WRT

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-10-14 Cont ID  
Sent By pkrauss Date 2003-10-14 Time 11:34 Rev Time 0.40
Received By pkrauss Date 2003-10-14 Time 11:34 Sent To  
Notes
2003-10-14 00:00:00PROVISO:
 SECONDARY DRAIN FROM AUXILIARY DRAIN PAN
 SHALL TERMINATE AT A CONSPICUOUS POINT
 TO SERVE AS AN ALARM THAT THE PRIMARY
 DRAIN IS RESITRICTED OR UNIT SHALL SHUT
 DOWN BY MEANS OF A FLOAT SWITCH AS PER
 2001 FBC(M) 307.2.3 & 307.2.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-10-14 Cont ID  
Sent By pkrauss Date 2003-10-14 Time 08:44 Rev Time 0.45
Received By pkrauss Date 2003-10-14 Time 08:44 Sent To  
Notes
2003-10-14 00:00:00PROVISO:
 SECONDARY DRAIN FROM AUXILIARY DRAIN PAN
 SHALL TERMINATE AT A CONSPICUOUS POINT
 TO SERVE AS AN ALARM THAT THE PRIMARY
 DRAIN IS RESTRICTED OR UNIT SHALL SHUT
 DOWN BY A FLOAT SWITCH.2001 FBC(M)
 307.2.3 & 307.2.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-04-07 Cont ID  
Sent By hmoser Date 2003-04-07 Time 15:16 Rev Time 1.00
Received By hmoser Date 2003-04-07 Time 15:14 Sent To B
Notes
2003-04-07 00:00:00PASS PROVISO
 RETURN AIR IN ROONS 1,2 TWO SMALL
 REFER TO SECTION 601.4 FBC.BALANCED
 RETURN AIR
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8221

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-02-03 Cont ID  
Sent By pkrauss Date 2003-02-03 Time 10:38 Rev Time 1.00
Received By pkrauss Date 2003-02-03 Time 10:19 Sent To  
Notes
2003-02-03 00:00:00DENIED:MECHANICAL PERMIT 03011203
  
 1.PLAN SHEET M-1, CONFERENCE RM 1 & 2
 DOES NOT INDICATE RETURN AIR OR TRANSFER
 AIR.2001 FBC(M) 601.4
  
 2.FRESH AIR INTAKES SHALL BE LOCATED
 FROM ANY NOXIOUS CONTAMINANT, SUCH AS
 VENTS, STREETS, ALLEYS, OR PARKING LOTS.
 2001 FBC(M) 401.5.1
  
 3.EXHAUST OPENINGS SHALL BE LOCATED
 AS NOT TO CREATE A NUISANCE.EXHAUST
 AIR SHALL NOT BE DIRECTED ONTO WALKWAYS.
  
 4.PLAN SHEET M-1, INDICATES AHU-3 & 2
 SERVING THE SAME AREA, AS PER 2001 FBC
 (M) 606.2.2 - WHERE MULTIPLE AHU'S WITH
 A DESIGN CAPACITY GREATER THAN 2,000 CFM
 SHALL BE PROVIDED WITH DUCT SMOKE
 DETECTORS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 5 Status P Date 2003-10-20 Cont ID  
Sent By kstevens Date 2003-10-20 Time 12:51 Rev Time 0.75
Received By kstevens Date 2003-10-20 Time 12:51 Sent To  
Notes
2003-10-20 00:00:00REVISION OK - CHANGED FLOOR PLAN - SANT.
 RISER DIAGRAM

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-04-11 Cont ID  
Sent By kstevens Date 2003-04-11 Time 14:25 Rev Time 2.00
Received By kstevens Date 2003-04-11 Time 14:24 Sent To  
Notes
2003-04-11 00:00:00FORTH REVIEW-FEE WAIVED FOR THIRD
  
  
 PASSED/PROVISO
  
 SHT A2 TOILET ROOM 127 TO BE ACCESSIBLE
 11-4.22 - DOOR SHALL NOT OPEN INTO CLEAR
 FLOOR SPACE 11-4.22.2 - MINIMUM 5'3" IN-
 SIDE FINISH TOILET ROOM.
  
  
  
 SHT A4 REVISION REQUIRED SHOWING CLEAR
 FLOOR SPACE, GRAB BARS, ROOM DIMENSIONS
 CORRECTED DETAILS ECT.
 GAS WATER HEATER SHALL BE APPROVED FOR
 OUTSIDE USE OR COVERED.
  
  
  
 SHT P-1 REVISION REQUIRED - FLOOR PLAN
 DOES NOT MATCH FLOOR PLAN OF SHT A2/A4

Review Stop P PLUMBING
Rev No 3 Status F Date 2003-04-11 Cont ID  
Sent By kstevens Date 2003-04-11 Time 09:03 Rev Time 1.75
Received By kstevens Date 2003-04-11 Time 09:03 Sent To  
Notes
2003-04-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 1) SHT A3 CALCULATIONS FOR ROOF #2 ALSO
 REQUIRED. CALCULATIONS SHALL BE ON PLANS
 INDICATE SLOPE OF GUTTER TO DOWNSPOUT
 PER TABLE 1106.6
 2) ALL NEW TOILET/BATHING ROOMS SHALL
 COMPLY WITH 11-4.22/11-4.23. ROOM 127
 SHALL BE ACCESSIBLE BY CODE.
 3) SHT A4 DOOR SHALL NOT OPEN INTO CLEAR
 FLOOR SPACE. 11-4.23.2. ROOM 127 STILL
 HAS DOOR OPENING INTO CLEAR FLOOR SPACE.
 4) SHT A4 SHOWER STALLS SHALL COMPLY
 WITH 11-4.21.5 & 11-4.21.7. THESE DE-
 TAILS ARE NOT ON PLANS PER RESPONSE.
 5) SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, AND THE FBC-2001
 FUEL GAS CODE SECTION 402.2.
 NO RESPONSE.
 6) SHTS A2 & A4 ROOM #127 ROOM SIZE
 SHALL BE MINIMUM OF 5'3" INSIDE FINISHED
 PLEASE SHOW DIMENSION.
 7) SHT A4 DETAILS #3 & #7 GRAB BARS CAN-
 NOT EXTEND OVER LAV. SEE FIG. 29.
 RESPONSE SAYS REVISED BUT NO REVISION
 SHOWN.
 8) SHT A4 ROOM 129 DOOR TO OUTSIDE. RE-
 SPONSE SAYS THAT PLAN WAS REVISED, BUT
 NO REVISION SHOWN
 9) SHT A2 FUEL-FIRED WATER HEATERS SHALL
 NOT BE INSTALLED IN A BATHROOM OR A
 CLOSET ACCESSED THROUGH A BATHROOM.
 10) THIS IS THE THIRD SUBMITTAL - A FEE
 IS DUE FOR RESUBMITTAL. $194.25
 11) THIS IS THE THIRD REVIEW. PLEASE BE
 AWARE OF FS 553.80(2)(B). SEE ATTACHED
 COPY.
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-04-04 Cont ID  
Sent By kstevens Date 2003-04-04 Time 15:36 Rev Time 2.33
Received By kstevens Date 2003-04-04 Time 15:36 Sent To  
Notes
2003-04-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW.
 SHT A2 PLEASE CLAIRFY PREP AREAS. IF
 SERVING FOOD, PLEASE NOT THAT PLANS MAY
 HAVE TO BE ROUTED TO THE HEALTH DEPT. IF
 THESE ARE BREAK ROOMS, SINKS SHALL COM-
 PLY WITH SECTION 11-4.24 AND ALL SUB-
 SECTIONS AND A DETAIL WILL BE REQUIRED.
 2) FROM PREVIOUS REVIEW.
 SHT A3 PLEASE SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 1/2 AREA FOR ALL VERTICAL WALLS INCLUD-
 ING PARAPET WALLS IN CALCULATIONS. INDI-
 CATE LOCATION, NUMBER, & SIZE OF ALL
 DOWNSPOUTS. THERE ARE NEW GUTTERS AND
 DOWNSPOUTS INDICATED AND INFORMATION IS
 REQUIRED TO SEE IF THESE ARE SIZED PROP-
 ERLY.
 3) FROM PREVIOUS REVIEW.
 SECTION 11-4.1.2(6) IF TOILET FACILITIES
 ARE PROVIDED ON A SITE THEN EACH SUCH
 PUBLIC OR COMMON USE TOILET FACILITY
 SHALL COMPLY WITH 11-4.22.
 4) FROM PREVIOUS REVIEW.
 SHT A4 TOILET ROOMS SHALL COMPLY WITH
 SECTION 11-4.22 & ALL SUBSECTIONS.
 DOORS STILL OPEN INTO CLEAR FLOOR SPACE
 AND TURNING CIRCLES.
 5) FROM PREVIOUS REVIEW.
 SHT A4 SHOWER STALLS SHALL COMPLY WITH
 11-4.21.5 CONTROLS, & 11-4.21.7 CURBS.
 PLEASE SHOW ON DETAILS.
 6) FROM PREVIOUS REVIEW.
 SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 7) SHTS A2 & A4, ROOM #127, ROOM SIZE
 SHALL BE MINIMUM OF 5'3" INSIDE FINISHED
 PLEASE SHOW DIMENSION.
 8) SHT A4 DETAILS #3 & #7 GRAB BAR CAN-
 NOT EXTEND OVER LAV. (SEE FIG 29).
 9) SHT A4 ROOM 129 PLEASE INDICATE WHICH
 WAY THE DOOR TO THE OUTSIDE OPENS. IT
 CAN NOT OPEN INTO CLEAR FLOOR SPACE.
 10) SHTS A2 & A4, FUEL-FIRED WATER HEAT-
 ERS SHALL NOT BE INSTALLED IN A BATHROOM
 OR A CLOSET ACCESSED THROUGH A BATHROOM.
 >>>>>>> WHEN RESUBMITTING PLANS <<<<<<<<
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-01-25 Cont ID  
Sent By kstevens Date 2003-01-25 Time 05:35 Rev Time 1.50
Received By kstevens Date 2003-01-24 Time 17:51 Sent To  
Notes
2003-01-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 1) SHT A2 DEMO NOTES #'S 4,5,& 9, ALL
 PIPES CAPPED OFF IN FLOOR OR WALLS SHALL
 BE INSPECTED PRIOR TO COVERING.
 2) SHT A2 PLEASE CLAIRFY PREP AREAS. IF
 SERVING FOOD, PLEASE NOTE THAT PLANS MAY
 HAVE TO BE ROUTED TO THE HEALTH DEPT. IF
 THESE ARE BREAK ROOMS, SINKS SHALL COM-
 PLY WITH SECTION 11-4.24 AND ALL SUB-
 SECTIONS AND A DETAIL WILL BE REQUIRED.
 3) SHT A3 PLEASE SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 1/2 AREA FOR ALL VERTICAL WALLS INCLUD-
 ING PARAPET WALLS IN CALCULATIONS. INDI-
 CATE LOCATION, NUMBER, & SIZE OF ALL
 DOWNSPOUTS AND IF ROOF IS FLAT OR PITCH-
 ED.
 4) SECTION 11-4.1.2(6) IF TOILET FACIL-
 ITIES ARE PROVIDED ON A SITE THEN EACH
 SUCH PUBLIC OR COMMON USE TOILET FACIL-
 ITY SHALL COMPLY WITH 11-4.22. IF BATH-
 ING FACILITIES ARE PROVIDED ON A SITE,
 THEN EACH SUCH PUBLIC OR COMMON USE
 BATHING FACILITY SHALL COMPLY WITH
 11-4.23
 5) SHT A4 TOILET ROOMS SHALL COMPLY WITH
 SECTION 11-4.22 & ALL SUBSECTIONS.
 PLEASE SHOW ON DETAILS. (SEE SECTIONS
 11-4.16, 11-4.18, SHOW 5'TURNING RADIUS
 IN EACH TOILET ROOM, SEE FIG.28, DOORS
 SHALL NOT OPEN INTO ANY CLEAR FLOOR
 SPACE OR TURNING RADIUS ECT,)
 6) SHT A4 SHOWER STALLS SHALL COMPLY
 WITH 11-4.21 AND ALL SUBSECTIONS. PLEASE
 SHOW ON DETAILS.
 7) SHT P-2 SANITARY RISER DIAGRAM,
 DRINKING FOUNTAIN IS NOT SHOWN.
 8) SHT P-2 WATER RISER DIAGRAM, DRINKING
 FOUNTAIN IS NOT SHOWN. WATER HAMMER ARR-
 ESTORS ARE REQUIRED AT WASH MACHINE, ICE
 MAKER AND DISHWASHER IF PROVIDED. SECT.
 604.9
 9) SHT P-3 WATER HEATER DETAIL, THERMAL
 EXPANSION CONTROL REQUIRED. SEC 607.3.2
 PLEASE SHOW EXPANSION TANK.
 10) SHT P-3 GENERAL NOTES #16, AIR
 CHAMBERS ARE NOT APPROVED. PLEASE DELETE
 REFERENCE.
 11) SHT P-1 SEPARATE GAS PERMIT REQUIRED
 SEE FOLLOWING LIST OF GAS APPLICATION
 REQUIREMENTS.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377