Plan Review Details - Permit 03011199
Plan Review Stops For Permit 03011199
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-02-20 Cont ID  
Sent By hpiskura Date 2003-02-20 Time 14:04 Rev Time 0.00
Received By pkrauss Date 2003-02-19 Time 16:08 Sent To  
Notes
2003-02-20 00:00:00THE HC RAMP AND LANDING ON SHOWN ON THE
 SOUTH SIDE, SHEET A1 AND THE FLAT AREA
 ON THE NORTH SIDE DO NOT COMPLY WITH
 FBC 11-4.8.4 AND 11-4.13.6.PLEASE
 REVISE AS NECESSARY.
  
 SHOW THE FINISH FLOOR ELEVATION
 REALTIVE TO THE SURROUNDING TOPOGRAPHY.
 FBC 104.2
  
 SHEET A2.THE DOORS SHOWN SWINGING INTO
 THE CORRIDOR FROM THE TOILET ROOMS DO
 NOT COMPLY WITH FBC 1012.1.4.
  
 SHEET A2 THE AREA SHOWN AS CLUBHOUSE IS
 AN ASSEMBLY OCCUPANCY USE.THE DOORS
 MUST SWING IN THE DIRECTION OF TRAVEL,
 BE SIDE SWINGING AND PROVIDE 32" CLEAR
 WIDTH. SEE FBC 1012.1.2
  
 PLEASE PROVIDE THE ROOF COVERING
 INFORMATION IN ACCORDANCE WITH FBC
 104.2.1.1.
  
 SHEET A4 THE STAIR SECTION MAKES DESIGN
 REFERENCES AS "PER CODE" WHICH IS NOT
 ANACCEPTABEL SUBSTITUTE FOR SPECIFIC
 DESIGN INFORMATION.SEE FBC 1007.5 AND
 1015.
  
 THE STAIRS DO NOT COMPLY WITH THE RISER
 AND TREAD REQUIREMENTS OF FBC 1007.3.1.
  
 THE "STAIRWAYS" DO NOT MEET THE 1/2
 DIAGONAL DISTANCE REQUIREMENT OF FBC
 1006.2.2.
  
 SHEET A7.SHOW A CONNECTION DETAIL FOR
 THE 3-2X12 BEAM TO THE MASONRY COLUMNS
 SHOWN ON THE NORTH MOST SIDE.
  
 SHOW A FRAMING AND FASTENING DETAIL FOR
 THE SUSPENDED GYP BOARD CEILING SHOWN ON
 SHEET A8. FBC 104.2.
  
 SHOW THE DESIGN LOADS FOR THE BALCONIES
 AND THE STAIRS, AND THE COMPONENT AND
 CLADDING PRESSURES FOR THE ROOF.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO THE
 COUNTY THE PERMIT PLANS STAMPED BY THAT
 OFFICE AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 CALL 561-233-5025 FOR MORE INFORMATION.
  
 THE $237,600.00 DECLARED PERMIT
 VALUATION IS TOO LOW FOR THIS SCOPE OF
 WORK.THE CITY VALUATION IS
 $410792.00, PLEASE PAY AN ADDITIONAL
 $961.22 PERMIT FEES TO THE CITY.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-02-13 Cont ID  
Sent By dpalmer Date 2003-02-13 Time 11:30 Rev Time 1.00
Received By dpalmer Date 2003-02-13 Time 11:29 Sent To  
Notes
2003-02-13 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE PROVIDE CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULES
 PLEASE SUBMIT PANEL SCHEDULES.
 INFORMATION ON PANELS ETC
 2)NOTE: PLEASE SIZE SEC`S PER 310-15/
 310-16, 240-3.
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EEQUIPMENT.
  
 PLEASE COMPLETE PLANS FOR REVIEW,PLEASE
 NOTE THERE MAY BE ADDTIONAL COMMENTS DUE
 TO CIRCUITING,PANELS,LOADS ETC
  
 4)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 PER NEC 220, MIXED USE, 220-3,220-10,
 220-11,220-13,215-3,23-42 ETC.
  
 5)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 THAT MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2003-02-07 Cont ID  
Sent By mamini Date 2003-02-07 Time 09:26 Rev Time 1.00
Received By mamini Date 2003-02-07 Time 09:25 Sent To  
Notes
2003-02-07 00:00:00FAILED :
 1. PLEASE PROVIDE CIVIL ENGINEERING SITE
 PLANS FOR OUR REVIEW AND APPROVAL;
 CIVIL PALNS SHOULD INCLUDE STORM WATER
 CALCULATION, WATER QUALITY PROPOSALS,
 PERVIOUS AND IMPERVIOUS CALC. FOR THE
 SITE,CONNECTION TO CITY SERVICES AND
 LOCATIONS FOR BACKFLOW PREVENTERS
 ( DOMSTIC & IRRIGATIONS) AND POLLUTION
 PREVENTION PLANS.
 2. ALL PARKING STALLS MUST BE PAINTED
 WITH DOUBLE 4" WHITE.
 3. THE PROPOSED TURN-OUT MUST BE
 CONSTRUCTED PER CITY OF WPB STANDARD AND
 REQUIREMENTS.
 4. PLEASE SUBMIT 2 SETS OF PLANS TO
 PUBLIC UTILITIES ENGINEERING SERVICES
 FOR THE CONNECTIONS TO CITY SERVICES,
 ATT. MR. MANNY GONZALEZ 659-8040.
 5. PLEASE NOTE THAT A SEPARATE PERMIT
 APPLICATIONS AND FEES FOR CIVIL SITE
 WORKS WILL BE REQUIRED.
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-02-07 Cont ID  
Sent By mcarsill Date 2003-02-07 Time 12:53 Rev Time 0.00
Received By mcarsill Date 2003-02-07 Time 12:53 Sent To  
Notes
2003-02-07 00:00:001) SITE PLAN SHALL SHOW ALL FIRE
 HYDRANTS LOCATED IN THE IMMEDIATE
 VICINTY OF THE BUILDING.
  
 2) PLEASE CLEARLY ILLUSTRATE TENANT
 SEPARTION WALLS ON FLOOR PLANS.
  
 3) PLEASE INDICATE FIRE EXTINGUISHER
 LOCATIONS.
  
 4) BUILDING ADDRESS REQUIRED.
  
 5) APARTMENT DOORS SHALL BE AT LEAST
 20 MINUTE FIRE RATED.
  
 6) IT WAS NOTED THAT A STOVE IS PRESENT
 IN THE CLUBHOUSE. IF NO HOOD,DUCT,OR
 FIRE SUPPRESSION SYSTEM IS PLANNED,
 ONLY BOILING OF WATER WILL BE ALLOWED.
 NO COOKING THAT PRODUCES SMOKE OR
 GREASE LADEN VAPORS WILL BE ALLOWED
 WITHOUT THE PROPER FIRE SAFETY
 EQUIPMENT.
  
 7) IF NO FIRE SPRINKLERS ARE PLANNED,
 THEN ALL STORAGE ROOMS MUST BE AT
 LEAST ONE HOUR FIRE SEPARATED WITH
 45 MINUTE OPENING PROTECTIVES.
  
 8) ANOTHER EXIT SIGN IS REQUIRED NEAR
 FIRST FLOOR STORAGE NEAR THE GAME ROOM
 TO DIRECT PERSONS.
  
 9) STAIR TREADS AND RISERS ARE NOT
 PROPER.
  
 10) BATHROOM DOORS WHEN OPENED INTERFERE
 WITH THE PROPER WIDTH OF THE CORRIDOR.
  
 11) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-02-06 Cont ID  
Sent By dpalmer Date 2003-02-06 Time 10:01 Rev Time 0.00
Received By dpalmer Date 2003-02-06 Time 10:01 Sent To  
Notes
2003-02-06 00:00:00TO COMM BOARD #8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-17 Cont ID  
Sent By btrobaug Date 2003-01-17 Time 18:03 Rev Time 0.00
Received By btrobaug Date 2003-01-16 Time 18:05 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-02-13 Cont ID  
Sent By pkrauss Date 2003-02-13 Time 10:16 Rev Time 0.45
Received By pkrauss Date 2003-02-13 Time 10:02 Sent To  
Notes
2003-02-13 00:00:00DENIED:MECHANICAL PERMIT 03011207
  
 SEE REVIEW COMMENTS BY ASST. FIRE
 MARSHALL MIKE CARSILLO ITEMS #6 & 7,
 SHOULD STORAGE ROOMS HAVE A ONE HOUR
 FIRE SEPARATION FIRE DAMPERS WILL BE
 REQUIRED.PROVIDE MANUFACTURER SUBMITAL
 DATA FOR THE FIRE DAMPERS AS PER 2001
 FBC(M) 607.6
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-02-08 Cont ID  
Sent By sgraham Date 2003-02-05 Time 11:18 Rev Time 0.75
Received By kstevens Date 2003-02-08 Time 05:29 Sent To  
Notes
2003-02-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-2 KITCHEN SINK SHALL COMPLY
 WITH SECTION 4.24 AND ALL SUBSECTIONS.
 PLEASE PROVIDE DETAIL.
 2) SHT A-2 DRINKING FOUNTAIN SHALL COM-
 PLY WITH SECTION 4.15 AND ALL SUBSECT-
 IONS AND 11-4-1-3(10)(A) PROVISIONS FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING. PLEASE PROVIDE DETAIL.
 3) WATER RISER DIAGRAM REQUIRED. PLEASE
 SHOW ALL PIPE SIZING AND LOCATION OF ALL
 WATER HAMMER ARRESTORS REQUIRE BY SECT.
 604.9 (WASH MACHINE, ICE MAKER, DISH-
 WASHER IF PROVIDED).
 4) RPZ BACKFLOW REQUIRED.
 5) THERMAL EXPANSION CONTROL REQUIRED
 AT ALL WATER HEATERS PER SECTION 607.3.2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2003-02-05 Cont ID  
Sent By btrobaug Date 2003-01-17 Time 18:07 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***