Plan Review Details - Permit 03011187
Plan Review Stops For Permit 03011187
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-06-30 Cont ID  
Sent By hpiskura Date 2003-06-30 Time 12:17 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-06-30 00:00:00REVIEWED AGAIN 6/27/03

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-03-14 Cont ID  
Sent By hpiskura Date 2003-03-14 Time 13:39 Rev Time 0.00
Received By hpiskura Date 2003-03-14 Time 12:01 Sent To  
Notes
2003-03-14 00:00:00PLANS DATED 2/26/03

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-03-14 Cont ID  
Sent By jwitmer Date 2003-01-28 Time 13:28 Rev Time 1.25
Received By hpiskura Date 2003-01-28 Time 13:28 Sent To  
Notes
2003-01-28 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 03011187
 ADD: 700 S ROSEMARY # 113
 ARCH: HVC ARCHITECTS ( MICHAEL)
 TEL: (305)567-0602
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) 11-4.23.3 CLEAR FLOOR SPACE. A UNOBST
 RUCTEDTURNING SPACE COMPLYING WITH
 11-4.2.3 SHALL PROVIDED WITHIN AN ACCESS
 IBLE BATHROOM.
  
 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-06-16 Cont ID  
Sent By dpalmer Date 2003-06-16 Time 16:46 Rev Time 0.50
Received By dpalmer Date 2003-06-16 Time 16:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-03-18 Cont ID  
Sent By dpalmer Date 2003-03-18 Time 17:40 Rev Time 0.25
Received By dpalmer Date 2003-03-18 Time 17:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-01-27 Cont ID  
Sent By dpalmer Date 2003-01-27 Time 16:38 Rev Time 0.33
Received By dpalmer Date 2003-01-27 Time 16:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-06-30 Cont ID  
Sent By nmccray Date 2003-06-30 Time 10:45 Rev Time 0.00
Received By nmccray Date 2003-06-30 Time 10:45 Sent To  
Notes
2003-06-30 00:00:00**************PROVISO****************
 SEPARATE PLANS AND PERMITS REQUIRED FOR
 FIRE ALARM AND FIRE SPRINKLER SYSTEMS
 REVISION.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-04-02 Cont ID  
Sent By mcarsill Date 2003-04-02 Time 09:15 Rev Time 0.00
Received By mcarsill Date 2003-04-02 Time 09:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-01-23 Cont ID  
Sent By mcarsill Date 2003-01-23 Time 15:34 Rev Time 0.00
Received By mcarsill Date 2003-01-23 Time 15:34 Sent To  
Notes
2003-01-23 00:00:001) PLEASE PROVIDE A STROBE IN THE
 PRIVATE BATHROOM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-08-26 Cont ID  
Sent By csiegber Date 2003-08-26 Time 08:22 Rev Time 0.00
Received By csiegber Date 2003-08-26 Time 08:22 Sent To M
Notes
2003-08-26 00:00:00TO PK DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-06-30 Cont ID  
Sent By sthyng Date 2003-06-30 Time 09:39 Rev Time 0.00
Received By sthyng Date 2003-06-30 Time 09:39 Sent To  
Notes
2003-06-30 00:00:00TAKEN OFF OF BOARD, SENT TO FIRE (NM
 DESK)

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-06 Cont ID  
Sent By shernand Date 2003-06-06 Time 11:32 Rev Time 0.00
Received By shernand Date 2003-06-06 Time 11:32 Sent To  
Notes
2003-06-06 00:00:00COMM BOARD #42

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-13 Cont ID  
Sent By sthyng Date 2003-03-13 Time 13:31 Rev Time 0.00
Received By sthyng Date 2003-03-13 Time 13:31 Sent To  
Notes
2003-03-13 00:00:00COMM BOARD #30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-17 Cont ID  
Sent By btrobaug Date 2003-01-17 Time 18:35 Rev Time 0.00
Received By btrobaug Date 2003-01-16 Time 18:35 Sent To  
Notes
2003-01-17 00:00:00COM BOARD#28./WRT

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-06-27 Cont ID  
Sent By csiegber Date 2003-08-26 Time 08:22 Rev Time 0.50
Received By hmoser Date 2003-06-27 Time 16:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-03-18 Cont ID  
Sent By pkrauss Date 2003-03-18 Time 16:24 Rev Time 0.30
Received By pkrauss Date 2003-03-18 Time 16:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-02-03 Cont ID  
Sent By pkrauss Date 2003-02-03 Time 15:54 Rev Time 0.30
Received By pkrauss Date 2003-02-03 Time 15:47 Sent To  
Notes
2003-02-03 00:00:00DENIED:
  
 CLARIFY MAKE-UP AIR TO NEW BATHROOM.
 THE AMOUNT OF SUPPLY AIR SHALL BE
 APPROXIMATELY EQUAL TO THE AMOUNT OF
 AIR EXHAUSTED.2001 FBC(M) 403.1
  
 PLAN SHEET A.1 WALL LEGEND "EXISTING 1
 HR" RATED CONSTRUCTION.FIRE DAMPERS
 ARE REQUIRED ON DUCTS PENETRATING WALLS
 HAVING A FIRE RESISTANCE RATING OF 1 HR
 OR MORE.2001 FBC(M) 607.1.2 #1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-06-27 Cont ID  
Sent By kstevens Date 2003-06-27 Time 14:44 Rev Time 0.50
Received By kstevens Date 2003-06-27 Time 14:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-03-26 Cont ID  
Sent By kstevens Date 2003-03-26 Time 11:04 Rev Time 0.25
Received By kstevens Date 2003-03-26 Time 11:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-01-25 Cont ID  
Sent By kstevens Date 2003-01-25 Time 06:27 Rev Time 0.33
Received By kstevens Date 2003-01-25 Time 06:27 Sent To  
Notes
2003-01-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-1 TOILET ROOM, AN UNOBSTRUCTED
 TURNING SPACE SHALL BE PROVIDED WITHIN
 AN ACCESSIBLE TOILET ROOM COMPLYING WITH
 11-4.3.2.
 2) SHT M.E.P. PLEASE PROVIDE A SANITARY
 RISER DIAGRAM AND A WATER RISER DIAGRAM.
 SHOW ALL PIPE SIZES, AND VENT TERMINAT-
 ION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377