Plan Review Details - Permit 03011180
| Plan Review Stops For Permit 03011180 |
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2003-02-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-02-07 |
Time |
10:54 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2003-02-07 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2003-02-07 00:00:00 | REVISION - CHANGE TO 2 LB SYSTEM - ADD | | | REGULATORS - DELETE ONE GAS APPLIANCE |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2003-02-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-02-03 |
Time |
14:17 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2003-02-03 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2003-02-03 00:00:00 | REVISION OK - PIPE SIZES CHANGED TO | | | COMPLY WITH FUEL GAS CODE - PERMIT WAS | | | ISSUED IN ERROR, (TURN AROUND), NO PLAN | | | REVIEW PRIOR TO THIS DATE. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2003-01-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-01-29 |
Time |
08:52 |
Rev Time |
2.25 |
| Received By |
kstevens |
Date |
2003-01-28 |
Time |
17:50 |
Sent To |
|
|
| Notes |
| 2003-01-29 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 1) PERMIT ISSUED IN ERROR - NO PLAN RE- | | | VIEW FOR GAS PRIOR TO ISSUANCE. | | | 2) FOLLOWING INFORMATION REQUIRED FOR | | | REVISION. | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. | | | B. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2001 FUEL | | | GAS CODE SECTION 304. WATER HEATER NOT | | | SHOWN ON PLAN. | | | C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2 | | | D. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2003-01-16 |
|
|
Cont ID |
|
| Sent By |
kmcvey |
Date |
2003-01-16 |
Time |
12:17 |
Rev Time |
0.10 |
| Received By |
kmcvey |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2003-01-16 00:00:00 | APPROVED PERKEN STEVENS 1-16-03 KAM |
|
|
|