Plan Review Details - Permit 03011168
Plan Review Stops For Permit 03011168
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-01-31 Cont ID  
Sent By shernand Date 2003-06-23 Time 11:08 Rev Time 2.00
Received By jgomez Date 2003-01-31 Time 12:16 Sent To  
Notes
2003-01-31 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-REVISE ROOF SHEATHING FASTENER SPACING
 FOR ZONE 3 AREAS. SEE TABLE 2306.1 OF
 CITY AMENDMENTS TO FBC 2001.
 2-BEFORE INSTALLATION PROVIDE PRODUCT
 APPROVAL FOR:
 A)FRENCH DOORS WITH LEGIBLE DRAWINGS.
 B)CASEMENT WINDOWS WITH LEGIBLE DRAWINGS
 AND/OR SINGLE HUNG WINDOWS AS SHOWN ON
 EXTERIOR ELEVATIONS.
 C)ROOF SHINGLES.
 **NOTE:
 PLEASE GET APPROVAL FROM HISTORICAL
 DISTRICT PRIOR TO SUBMITTAL TO THIS
 OFFICE.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-01-31 Cont ID  
Sent By pkrauss Date 2003-01-24 Time 10:09 Rev Time 0.50
Received By btrobaug Date 2003-01-30 Time 08:42 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-06-23 Cont ID  
Sent By shernand Date 2003-06-23 Time 11:08 Rev Time 0.00
Received By shernand Date 2003-06-23 Time 11:08 Sent To B
Notes
2003-06-23 00:00:00JGOMEZ DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-06-12 Cont ID  
Sent By shernand Date 2003-06-12 Time 14:39 Rev Time 0.00
Received By shernand Date 2003-06-12 Time 14:39 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date 2003-02-24 Cont ID  
Sent By lmartine Date 2003-02-24 Time 16:55 Rev Time 0.00
Received By lmartine Date   Time   Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-23 Cont ID  
Sent By dpalmer Date 2003-01-23 Time 09:37 Rev Time 0.00
Received By dpalmer Date 2003-01-23 Time 09:37 Sent To P
Notes
2003-01-23 00:00:00TO PLUMB INBOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-16 Cont ID  
Sent By sgraham Date 2003-01-21 Time 16:04 Rev Time 0.00
Received By btrobaug Date 2003-01-16 Time 13:18 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-07-07 Cont ID  
Sent By pkrauss Date 2003-07-07 Time 12:19 Rev Time 0.25
Received By pkrauss Date 2003-07-07 Time 09:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-06-17 Cont ID  
Sent By pkrauss Date 2003-06-17 Time 12:56 Rev Time 0.35
Received By pkrauss Date 2003-06-17 Time 12:23 Sent To  
Notes
2003-06-17 00:00:00DENIED:
  
 1. ORIGINAL PLANS SUBMITTED AND APPROVED
 ARE SIGNED & SEALED BY ARCHITECT.ANY
 CHANGES TO THESE PLANS MUST BE DONE BY
 THE ARCHITECT AND BE SIGNED AND SEALED.
  
 2. PLEASE NOTE THE SUPPLY DUCT TO THE
 DISTRIBUTION BOX IS NOT SIZED.
  
 3. THE EQUIPMENT SUBMITTED & APPROVED
 IS GOODMAN, NO MANUFACTURER IS SHOWN
 ON THE PLANS SUBMITTED.
  
 4. THE APPROVED ENERGY & MANUAL J CALCS
 DO NOT MATCH THE REVISED EQUIPMENT
 SUBMITTED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-01-24 Cont ID  
Sent By shernand Date 2003-06-12 Time 14:39 Rev Time 0.30
Received By pkrauss Date 2003-01-24 Time 09:37 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-03-14 Cont ID  
Sent By lmartine Date 2003-02-24 Time 16:55 Rev Time 1.00
Received By kstevens Date 2003-03-01 Time 14:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-01-23 Cont ID  
Sent By dpalmer Date 2003-01-23 Time 09:37 Rev Time 0.25
Received By kstevens Date 2003-01-23 Time 15:21 Sent To M
Notes
2003-01-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT 5 SANITARY RISER DIAGRAM, ONLY
 THE FIXTURES WITHIN THE BATHROOM GROUP
 SHALL CONNECT TO THE WET-VENTED HORIZON-
 TAL BRANCH DRAIN. THE WASH MACHINE AND
 KITCHEN SINK SHALL TIE IN DOWNSTREAM OF
 THE BATHROOM GROUP. SECTION 909.1
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2003-01-21 Cont ID  
Sent By btrobaug Date 2003-01-16 Time 13:18 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***