| 2003-02-05 00:00:00 | BUILDING DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) PLEASE REVISE NOTE #11 UNDER PLAN |
| | NOTES ON C1 TO INDICATE THAT HURRICANE |
| | PANELS ARE REQUIRED IN WIND BOURNE |
| | DEBRIS REGIONS. |
| | |
| | 4) PLEASE INDICATE ON C1 NOTE #15 UNDER |
| | FRAMING NOTES THAT HIGH RIB METAL LATH |
| | IS REQUIRED TO BE FASTENED AT EACH RIB |
| | (4"OC) PER ASTM C 1063 AND FBC 2504.2.2 |
| | |
| | 5) SPECIFY ON THE PLANS THAT THE WWM IN |
| | THE SLAB IS REQUIRED TO BE SUPPORTED ON |
| | APPROVED MATERIAL AT A MAXIMUM OF THREE |
| | FEET ON CENTER PER FBC 1909.3. |
| | |
| | 6) THE FOUNDATION FOR THE PRIVACY WALL |
| | ENCROACHS ON THE ADJACENT LOT AT THE |
| | ZERO LOT LINE. PLEASE CORRECT. |
| | |
| | 7)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | INDICATE THE INTERNAL PRESSURE |
| | INTERNAL PRESSURE COEFFICIENT ON THE |
| | PLANS. |
| | |
| | 8) DETAIL 10 ON A5 IS INDICATED AT THE |
| | WRONG TRUSS ON THE FRAMING PLAN. |
| | |
| | 9) THE CONDITIONED FLOOR AREA GIVEN ON |
| | THE ENERGY CALCULATIONS IS 2464 SQFT AND |
| | THE PLANS LIST 2526 SQFT. PLEASE CORRECT |
| | |
| | 10) THE ENERGY CALCULATIONS INDICATE |
| | THAT THE CREDIT FOR CEILING FANS IS |
| | BEING TAKEN. PLEASE INDICATE ON THE |
| | PLANS THE LOCATION AND SIZE OF THE FANS |
| | BASED ON THE ROOM SIZE PER FBC CHAPTER |
| | 13 TABLE 6-6. |
| | |
| | 11) THE WALL SECTION ON A4 SPECIFIES |
| | INSULATION WITH A MINIMUM OF R 3.5 AND |
| | THE ENERGY CALCS. LIST R 4.2. PLEASE |
| | CORRECT. |
| | |
| | 12) PROVIDE THE UL LISTING INFORMATION |
| | AND MANUFACTURER'S SPECIFICATIONS FOR |
| | THE ONE HOUR FIRE RATED GLASS BLOCKS. |
| | |
| | 13) THE KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR THE STORM PANELS DO NOT |
| | MATCH THE ARCHITECTURAL DRAWINGS. PLEASE |
| | REVISE. |
| | |
| | 14) THE PRODUCT APPROVAL FOR THE DOUBLE |
| | OUTSWING FRONT DOORS IS A PRELIMINARY |
| | NOA. THE DRAWINGS DO NOT HAVE THE |
| | RENEWAL STAMP WITH THE NEW NUMBER. |
| | PLEASE SUBMIT THE FINAL NOA. |
| | |
| | 15) THE PRODUCT APPROVALS SUBMITTED FOR |
| | THE STRUCTURAL MULLIONS DO NOT HAVE |
| | ADEQUATE DESIGN PRESSURES LISTED FOR THE |
| | MULLION BETWEEN THE 12'X8' SLIDING GLASS |
| | DOOR AND THE FIXED GLASS WINDOWS. PLEASE |
| | SUBMIT APPROPRIATE PRODUCT APPROVAL OR |
| | ENGINEERED ASSEMBLY. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |