| 2003-02-04 00:00:00 | BUILDING DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) PLEASE REVISE NOTE 11 ON C1 UNDER |
| | PLAN NOTES TO " IN WIND BOURNE DEBRIS |
| | REGIONS PROVIDE HURRICANE SHUTTERS ..." |
| | |
| | 4) THREE EIGHTS INCH (HI-RIB) METAL LATH |
| | IS REQUIRED TO BE FASTENED AT EACH RIB |
| | (4" O.C.) PER FBC 2405.2.2 & ASTM C 1063 |
| | PLEASE REVISE NOTE 15 ON C1 UNDER |
| | FRAMING NOTES. |
| | |
| | 5) THE PRIVACY WALL FOOTING ENCROACHES |
| | ONTO THE ADJOINING LOT AT THE ZERO LOT |
| | LINE. PLEASE CORRECT. |
| | |
| | 6) ONE HOUR FIRE RATED GLASS BLOCK IS |
| | REQUIRED AT THE ZERO LOT LINE. PLEASE |
| | SPECIFY THIS ON THE PLANS AND SUBMIT THE |
| | UL LISTING AND MANUFACTURER'S |
| | INFORMATION FOR FIRE RATING. |
| | |
| | 7) SPECIFY ON THE PLAN THAT THE BONUS |
| | ROOM, WHICH DOES NOT HAVE AN EGRESS |
| | WINDOW IS NOT TO BE USED AS A SLEEPING |
| | ROOM. |
| | |
| | 8) THE WALL SECTION ON A4 SPECIFIES A |
| | MINIMUM R3.5 INSULATION AND THE ENERGY |
| | CALCULATIONS LIST THE WALL INSULATION AS |
| | R4.2. PLEASE CORRECT. |
| | |
| | 9) THE DETAIL FOR THE GIRDER AT THE REAR |
| | COVERED PORCH IS LISTED AS DET. 15/A5 ON |
| | SHEET A6 AND IT APPEARS THAT IT SHOULD |
| | BE 12/A5. PLEASE CLARIFY. |
| | |
| | 10) THE DISTANCES TO THE PROPERTY LINES |
| | FROM THE STRUCTURE IS NOT INDICATED ON |
| | THE SITE PLAN. |
| | |
| | 11) THE PRODUCT APPROVALS THAT WERE |
| | SUBMITTED FOR THE FRONT DOORS IS A |
| | PRELIMINARY NOA THE DRAWINGS DO NOT HAVE |
| | THE RENEWAL STAMP WITH THE NEW NOA #. |
| | PLEASE SUBMIT FINAL NOA. |
| | |
| | 12) THE KEY PLAN AND INSTALLATION |
| | SCHEDULE SUBMITTED DOES NOT CORRESPOND |
| | WITH THE ARCHITECTURAL PLANS. SUBMIT THE |
| | CORRECT INFORMATION. |
| | |
| | 13) THE PRODUCT APPROVALS SUBMITTED FOR |
| | THE STRUCTURAL MULLIONS WILL NOT WORK |
| | BETWEEN THE TWELEVE FOOT SLIDING GLASS |
| | DOOR AND THE FIXED WINDOW ABOVE. THE |
| | CHARTS DO NOT LIST DESIGN PRESSURES FOR |
| | A 144" MULLION LENGTH AND A 120" OPENING |
| | WIDTH. ANOTHER PRODUCT APPROVAL OR AN |
| | ENGINEERED SYSTEM WILL BE REQUIRED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |