Plan Review Details - Permit 03011058
Plan Review Stops For Permit 03011058
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-02-25 Cont ID  
Sent By shernand Date 2003-06-03 Time 09:46 Rev Time 4.00
Received By rmcdouga Date 2003-02-25 Time 14:27 Sent To M
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-02-04 Cont ID  
Sent By btrobaug Date 2003-02-03 Time 09:17 Rev Time 5.00
Received By rmcdouga Date 2003-02-04 Time 10:36 Sent To  
Notes
2003-02-04 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PLEASE REVISE NOTE 11 ON C1 UNDER
 PLAN NOTES TO " IN WIND BOURNE DEBRIS
 REGIONS PROVIDE HURRICANE SHUTTERS ..."
  
 4) THREE EIGHTS INCH (HI-RIB) METAL LATH
 IS REQUIRED TO BE FASTENED AT EACH RIB
 (4" O.C.) PER FBC 2405.2.2 & ASTM C 1063
 PLEASE REVISE NOTE 15 ON C1 UNDER
 FRAMING NOTES.
  
 5) THE PRIVACY WALL FOOTING ENCROACHES
 ONTO THE ADJOINING LOT AT THE ZERO LOT
 LINE. PLEASE CORRECT.
  
 6) ONE HOUR FIRE RATED GLASS BLOCK IS
 REQUIRED AT THE ZERO LOT LINE. PLEASE
 SPECIFY THIS ON THE PLANS AND SUBMIT THE
 UL LISTING AND MANUFACTURER'S
 INFORMATION FOR FIRE RATING.
  
 7) SPECIFY ON THE PLAN THAT THE BONUS
 ROOM, WHICH DOES NOT HAVE AN EGRESS
 WINDOW IS NOT TO BE USED AS A SLEEPING
 ROOM.
  
 8) THE WALL SECTION ON A4 SPECIFIES A
 MINIMUM R3.5 INSULATION AND THE ENERGY
 CALCULATIONS LIST THE WALL INSULATION AS
 R4.2. PLEASE CORRECT.
  
 9) THE DETAIL FOR THE GIRDER AT THE REAR
 COVERED PORCH IS LISTED AS DET. 15/A5 ON
 SHEET A6 AND IT APPEARS THAT IT SHOULD
 BE 12/A5. PLEASE CLARIFY.
  
 10) THE DISTANCES TO THE PROPERTY LINES
 FROM THE STRUCTURE IS NOT INDICATED ON
 THE SITE PLAN.
  
 11) THE PRODUCT APPROVALS THAT WERE
 SUBMITTED FOR THE FRONT DOORS IS A
 PRELIMINARY NOA THE DRAWINGS DO NOT HAVE
 THE RENEWAL STAMP WITH THE NEW NOA #.
 PLEASE SUBMIT FINAL NOA.
  
 12) THE KEY PLAN AND INSTALLATION
 SCHEDULE SUBMITTED DOES NOT CORRESPOND
 WITH THE ARCHITECTURAL PLANS. SUBMIT THE
 CORRECT INFORMATION.
  
 13) THE PRODUCT APPROVALS SUBMITTED FOR
 THE STRUCTURAL MULLIONS WILL NOT WORK
 BETWEEN THE TWELEVE FOOT SLIDING GLASS
 DOOR AND THE FIXED WINDOW ABOVE. THE
 CHARTS DO NOT LIST DESIGN PRESSURES FOR
 A 144" MULLION LENGTH AND A 120" OPENING
 WIDTH. ANOTHER PRODUCT APPROVAL OR AN
 ENGINEERED SYSTEM WILL BE REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-05-17 Cont ID  
Sent By dpalmer Date 2003-05-17 Time 07:38 Rev Time 0.25
Received By dpalmer Date 2003-05-17 Time 07:38 Sent To B
Notes
2003-05-17 00:00:00*********** NOTES /REDLINED ************
  
  
 1)MISSING SD OUTSIDE BEDROOM #3
 2)MISSING EQUIPMENT GROUNDING FROM MAIN
 TO PANEL.250-110/250-122
 3)RECEPT TO BE W/IN 3' OF SINK MASTER-
 BATH.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-02-03 Cont ID  
Sent By shernand Date 2003-05-16 Time 15:30 Rev Time 0.75
Received By btrobaug Date 2003-02-03 Time 09:17 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-06-03 Cont ID  
Sent By shernand Date 2003-06-03 Time 09:45 Rev Time 0.00
Received By shernand Date 2003-06-03 Time 09:45 Sent To B
Notes
2003-06-03 00:00:00RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-05-16 Cont ID  
Sent By shernand Date 2003-05-16 Time 15:30 Rev Time 0.00
Received By shernand Date 2003-05-16 Time 15:30 Sent To E
Notes
2003-05-16 00:00:00DP DESK, BT ON VACATION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-03-06 Cont ID  
Sent By dpalmer Date 2003-03-06 Time 10:41 Rev Time 0.00
Received By dpalmer Date 2003-03-06 Time 10:41 Sent To M
Notes
2003-03-06 00:00:00TO PK'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-17 Cont ID  
Sent By btrobaug Date 2003-01-17 Time 16:01 Rev Time 0.00
Received By btrobaug Date 2003-01-17 Time 16:01 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-16 Cont ID  
Sent By btrobaug Date 2003-01-16 Time 17:10 Rev Time 0.00
Received By btrobaug Date 2003-01-15 Time 17:09 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-03-06 Cont ID  
Sent By kstevens Date 2003-05-24 Time 10:53 Rev Time 0.40
Received By pkrauss Date 2003-03-06 Time 13:56 Sent To  
Notes
2003-03-06 00:00:00PROVISO:MECHANICAL PERMIT 03011068
 1. O.A. CALCS REQUIRED AT ROUGH
 2. FAN SHUTDOWN REQUIRED AT FINAL
 3. SHOULD GAS DRYER BE INSTALLED,
 PROVIDE CALCS FOR THE LAUNDRY ROOM -
 CONFINED OR UNCONFINED SPACE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-02-25 Cont ID  
Sent By dpalmer Date 2003-03-06 Time 10:41 Rev Time 0.30
Received By pkrauss Date 2003-02-25 Time 14:36 Sent To  
Notes
2003-02-25 00:00:00DENIED:MECHANICAL PERMIT 03011068
  
 2ND REQUEST - PROVIDE GRILLE SIZES & CFM
 DISTRIBUTION.
  
 FRESH AIR CALCS REQUIRED AT ROUGH
 INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-01-25 Cont ID  
Sent By rmcdouga Date 2003-02-25 Time 14:28 Rev Time 0.50
Received By hmoser Date 2003-01-25 Time 13:04 Sent To E
Notes
2003-01-25 00:00:00PLAN DENIED
 1) NO CAN SIZE OR CFM.ON A/C DROPS
 2) NEED FRESH AIR CALCULATIONS FOR ROUGH
 INSPECTION
 3) NEED RETURN AIR IN MASTER SUITE
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-05-24 Cont ID  
Sent By kstevens Date 2003-05-24 Time 10:53 Rev Time 0.50
Received By kstevens Date 2003-05-24 Time 10:53 Sent To M
Notes
2003-05-24 00:00:00REVISION OK - REVERSE SANT. RISER DIAG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-01-25 Cont ID  
Sent By rmcdouga Date 2003-05-19 Time 15:09 Rev Time 0.25
Received By jleech Date 2003-01-25 Time 06:53 Sent To M
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2003-06-04 Cont ID  
Sent By rmcdouga Date 2003-06-04 Time 15:31 Rev Time 2.00
Received By rmcdouga Date 2003-06-04 Time 15:31 Sent To  
Notes
2003-06-04 00:00:00REVISION DATED 5-6-03 IS OK

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2003-05-19 Cont ID  
Sent By rmcdouga Date 2003-05-19 Time 14:49 Rev Time 1.00
Received By rmcdouga Date 2003-05-19 Time 14:49 Sent To P
Notes
2003-05-19 00:00:00REVISION DENIED BY BUILDING
  
 THE FOOTING FOR THE PRIVACY WALL AT THE
 ZERO LOT LINE,AS INDICATED ON THE DETAIL
 ON A1,ENCROACHES ON THE ADJACENT LOT.

Review Stop Z ZONING
Rev No 1 Status P Date 2003-01-17 Cont ID  
Sent By btrobaug Date 2003-01-16 Time 17:10 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***