| 2003-02-10 00:00:00 | BUILDING DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) PLEASE CLARIFY NOTE #9 UNDER GENERAL |
| | NOTES ON SHEET 1 TO INCLUDE WINDOWS THAT |
| | ARE WITHIN THREE FEET HORIZONTALLY OF |
| | THE TUB OR SHOWER. SEE FBC 2405.2.1. |
| | |
| | 3) SPECIFY ON THE PLANS THAT THE WIRE |
| | MESH IN THE SLAB IS REQUIRED TO BE |
| | SUPPORTED AT A MAXIMUM OF THREE FEET ON |
| | CENTER PER FBC 1909.3. |
| | |
| | 4) SPECIFY THE SIZES OF THE FIXED GLASS |
| | TRANSOM AND THE AND THE SIDELITE AT THE |
| | FRONT DOOR ON THE PLANS. |
| | |
| | 5) THE ROOF FRAMING PLAN ON 3A, 3B AND |
| | 3C SPECIFY AN A-5 TRUSS CONNECTOR FOR |
| | THE HIP GIRDER AT THE GARAGE. HOWEVER, |
| | THERE IS NO A-5 CONNECTOR LISTED IN THE |
| | ANCHOR SCHEDULE ON SHEET 2. PLEASE |
| | CLARIFY. |
| | |
| | 6) DETAIL 3 ON 4 DOES NOT SPECIFY THE |
| | LENGTH OR EMBEDMENT DEPTH OF THE 5/8" |
| | EXPANSION BOLTS FOR THE OVERHEAD GARAGE |
| | DOOR. PLEASE SPECIFY. |
| | |
| | 7) THE HVAC CREDIT IS BEING TAKEN FOR |
| | CEILING FANS ON THE ENERGY CALCULATIONS. |
| | PLEASE INDICATE THE REQUIRED MINIMUM FAN |
| | SIZE FOR EACH ROOM ON THE PLANS. SEE FBC |
| | CHAPTER 13-607.1.A.1 AND TABLE 6-6. |
| | |
| | 8) PROVIDE THE MANUFACTURER'S SPECS. AND |
| | UL LISTING INFORMATION FOR THE ONE HOUR |
| | FIRE RATED GLASS BLOCK ASSEMBLY. |
| | |
| | 9) THE JOB LOCATION IS REQUIRED TO BE ON |
| | THE SITE SPECIFIC PRODUCT APPROVALS FROM |
| | NORANDEX. |
| | |
| | 10) THERE IS NO PRODUCT INFORMATION IN |
| | THE NORANDEX SITE SPECIFIC APPROVALS FOR |
| | THE 96"X 60" GLIDER WINDOW WITH AN XOX |
| | CONFIGURATION. PLEASE SUBMIT ONE. |
| | |
| | 11) THE SURVEY HAS THE INCORRECT LOMR |
| | CASE # AND DATE FOR THE FLOOD ZONE. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |