| 2003-02-06 00:00:00 | BUILDING DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) SPECIFY ON THE PLANS THAT THE WIRE |
| | MESH IN THE SLAB WILL BE SUPPORTED AS |
| | REQUIRED BY FBC 1909.3. |
| | |
| | 3) THE WINDOW IN BATH #2 WHICH IS WITHIN |
| | THREE FT. HORIZONTALLY OF THE TUB/SHOWER |
| | IS REQUIRED TO HAVE SAFETY GLASS. THIS |
| | IS NOT CLEARLY INDICATED BY GENERAL NOTE |
| | #9 ON SHEET 1. PLEASE CLARIFY. SEE |
| | FBC 2405.2.1. |
| | |
| | 4) SPECIFY THE SIZE OF THE ATTIC ACCESS |
| | ON THE PLANS. THE MINIMUM SIZE IS 20" X |
| | 36" PER FBC 2309.6. |
| | |
| | 5) SPECIFY THE LENGTH/EMBED DEPTH OF THE |
| | 5/8" EXPANSION BOLTS FOR THE OVERHEAD |
| | GARAGE DOOR BUCKS. |
| | |
| | 6)THE GABLE END AT THE REAR AND ADJACENT |
| | TO THE VAULTED CEILING IS REQUIRED TO BE |
| | CONTINOUS FROM THE FLOOR TO THE CEILING |
| | DIAPHRAM PER FBC 1918.3.2. PLEASE |
| | PROVIDE A DETAIL OF THE RAKE BEAM AT |
| | THIS LOCATION. |
| | |
| | 7) THE SITE SPECIFIC PRODUCT APPROVALS |
| | FOR THE NORANDEX PRODUCTS IS REQUIRED TO |
| | HAVE THE JOB SITE LOCATION ON THE FORM. |
| | |
| | 8) THE SITE SPECIFIC PROD. APPROVALS FOR |
| | THE NORANDEX PRODUCTS DOES NOT INCLUDE |
| | A HORIZONTAL GLIDER WINDOW WITH A XOX |
| | CONFIGURATION AS IS SHOWN ON THE PLANS. |
| | PLEASE SUBMIT ONE FOR THIS WINDOW. |
| | |
| | 9) THE R VALUES GIVEN FOR THE INSULATION |
| | AT THE EXTERIOR CONC. WALLS AND THE WOOD |
| | FRAME ADJACENT WALLS ON THE ENERGY |
| | CALCULATIONS ARE REVERSED. PLEASE |
| | CORRECT. |
| | |
| | 10) PROVIDE THE MANUFACTURER'S |
| | SPECIFICATIONS AND UL LISTING |
| | INFORMATION FOR THE ONE HOUR FIRE RATED |
| | GLASS BLOCK ASSEMBLY. |
| | |
| | 11) INDICATE ON THE PLANS THE SIZE OF |
| | THE FIXED GLASS TRANSOM ABOVE THE FRONT |
| | DOOR. |
| | |
| | 12) THE INSTALLATION SCHEDULE FOR THE |
| | STORM PANELS HAS THE WRONG SIZES FOR THE |
| | TRANSOM ABOVE THE FRONT DOOR, SIDELITE |
| | AT FRONT DOOR, THE BATHROOM AND MASTER |
| | BED ROOM WINDOWS. PLEASE CHECK THE PLANS |
| | AND REVISE. |
| | |
| | 13) THE SURVEY HAS THE WRONG CASE # AND |
| | DATE FOR THE LOMR WITH THE FLOOD ZONE |
| | INFORMATION. PLEASE CORRECT. |
| | |
| | 14) PLEASE INDICATE ON THE PLANS WHICH |
| | OPTIONS ARE BEING USED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |