| 2003-02-06 00:00:00 | BUILDING DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) SPECIFY ON PLANS THAT WIRE MESH IN |
| | SLAB IS TO BE SUPPORTED AS REQUIRED BY |
| | FBC 1909.3. |
| | |
| | 3) THE WINDOW IN BATH #2 WHICH IS WITHIN |
| | THREE FEET HORIZONTALLY OF THE TUB/ |
| | SHOWER IS REQUIRED TO HAVE SAFETY GLASS. |
| | THIS IS NOT CLEARLY INDICATED BY GENERAL |
| | NOTE #9 ON SHEET 1. PLEASE REVISE. SEE |
| | FBC 2405.2.1. |
| | |
| | 4) SPECIFY THE SIZE OF THE ATTIC ACCESS |
| | ON THE PLANS. THE MINIMUM SIZE IS 20" X |
| | 36" PER FBC 2309.6. |
| | |
| | 5) SPECIFY THE LENGTH/EMBED DEPTH OF THE |
| | 5/8" EXPANSION BOLTS FOR THE GARAGE DOOR |
| | BUCKS ON SHEET 4. |
| | |
| | 6) THE GABLE END AT THE REAR AND |
| | ADJACENT TO THE VAULTED CEILING IS |
| | REQUIRED TO BE CONTINOUS FROM THE FLOOR |
| | TO CEILING DIAPHRAGM PER FBC 1918.3.2. |
| | PLEASE PROVIDE A DETAIL OF THE RAKE |
| | BEAM IN THIS AREA. |
| | |
| | 7) THE SITE SPECIFIC ENGINEERING FOR THE |
| | NORANDEX WINDOWS, DOORS AND MULLIONS ARE |
| | REQUIRED TO HAVE THE EMBOSSED SEAL OF |
| | THE ENGINEER/ARCHITECT FOR THE STRUCTURE |
| | AND THE LOCATION OF THE JOB ON THE FORM. |
| | THIS A REQUIREMENT OF THE BUILDING |
| | OFFICIAL PER CITY AMENDMENTS TO THE FBC |
| | 103.7. |
| | |
| | 8) THE R VALUES GIVEN FOR THE INSULATION |
| | AT THE CONCRETE EXTERIOR WALLS AND THE |
| | WOOD FRAME ADJACENT WALLS ON THE ENERGY |
| | CALCS. ARE REVERSED. PLEASE CORRECT. |
| | |
| | 9) PROVIDE THE MANUFACTURER'S |
| | SPECIFICATIONS AND UL LISTING |
| | INFORMATION FOR THE ONE HOUR FIRE RATED |
| | GLASS BLOCK ASSEMBLY. |
| | |
| | 10) PROVIDE A KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR THE STORM PANELS. |
| | |
| | 11) PROVIDE PRODUCT APPROVALS FOR THE |
| | HORIZONTAL GLIDER WINDOW WITH THE XOX |
| | CONFIGURATION AS SHOWN ON THE PLANS. THE |
| | NORANDEX SUBMITTAL ONLY COVERS WINDOWS |
| | WITH AN XO CONFIGURATION. |
| | |
| | 12) THE SURVEY HAS THE WRONG CASE # AND |
| | DATE FOR THE LOMR WITH THE FLOOD ZONE |
| | INFORMATION. PLEASE CORRECT. |
| | |
| | 13) PLEASE CLARIFY ON PLANS IF OPTIONAL |
| | REAR PORCH IS BEING BUILT. CROSS OFF |
| | OPTIONS IF THEY ARE NOT TO BE USED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |