Plan Review Details - Permit 03010851
Plan Review Stops For Permit 03010851
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-03-31 Cont ID  
Sent By jwitmer Date 2003-03-31 Time 10:40 Rev Time 0.75
Received By jwitmer Date 2003-03-31 Time 10:40 Sent To  
Notes
2003-03-31 00:00:00PROVISO: THAT THAT VERTICAL ACCESSIBIL-
 ITY SHALL BE MET WITH PORTABLE VERTICAL
 LIFT TO BE PRESENT ON SITE AT ALL TIMES.
 JIM WITMER
 BUILDING PLAN REVIEW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-03-15 Cont ID  
Sent By jwitmer Date 2003-03-15 Time 08:29 Rev Time 1.25
Received By jwitmer Date 2003-03-15 Time 08:29 Sent To  
Notes
2003-03-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03010851
 ADD: 4500 S DIXIE HWY
 CONT: TUSCANI
 TEL: (561)586-3808
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) 11-4.1.2 VERTICAL ACCESSIBILITY,
 NOTHING IN THIS CODE SHALL BE CONSTRUED
 TO RELIEVE THE OWNER OF ANY BUILDING,
 SSTRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE OR BELOW THE OCCUPIAABLE
 GRADE LEVEL.
 11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENTRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY.
 11-4.1.6 ACCESSIBLE BUILDINGS:
 ALTERATIONS 1(B) IF EXISTING ELEMENTS,
 SPACES OR COMMON AREAS ARE ALTERED, THEN
 SUCH ALTERED ELEMENTS, SPACES, FEATURES,
 OR AREA SHALL COMPLY WITH THE APPLICABLE
 PROVISIONS OF 11-4.1.1 TO 11-4.1.3
 MINIMUM REQUIREMENTS FOR NEW CONSTRUC-
 TION.
  
 ADDITIONAL INFORMATION SHALL BE RE-
 QUIRED FOR THE USE OF THE VERTICAL
 PLATFORM LIFT.THE FOLLOWING WILL BE
 REQUIRED:
 (A) A NOTIRIZED LETTER FROM THE SCHOOL
 ADMINISTRATOR ATESTING THAT THE VER-
 TICAL LIFT WILL BE AVAILABLE FOR ANY
 ONE THAT MAY REQUIRE ASSISTANCE ONTO
 THE STAGE. THAT IT WILL BE READILLY
 AVAILABLE ON REQUEST.
 (B) LOCATE ON THE ARCHITECTS FLOOR PLAN
 THE LOCATION WHERE THE LIFT WILL BE
 USED AND INDICATE THE AREA IT WILL
 BE STORED AT WHEN NOT IN USE.
 (C) PROVIDE ADDITIONAL INFORMATION
 THE MANUFACTURES SPECIFICATIONS,
 WHAT TYPE OF DESIGN:ENTER/ EXIT OF
 LIFT, SYSTEMS DESCRIPTION OF PLAT-
 FORM, GUARDRAILS OR PANELS, DOORS
 OR GATES, DRIVE UNIT, CONTROLS,
 SIGNALS OR LIMIT SWITCHES, POWER
 REQUIRED, INDICATE ON THE FLOOR PLAN
 THE POWER SOURCE.
 (D) PROVIDE SHOP DRAWINGS OF THE SYSTEM
 WITH THE LOAD LIMITATIONS. IS THE
 SAFE LOAD NOT TO EXCEED INDICATED
 ON THE UNIT.
 (E) ASSUMING THIS IS A PORTABLE UNIT HOW
 IS THE TRANSITION FROM FINISH FLOOR
 TO THE VERTICAL LIFT MADE, WHAT IS
 THE SLOPE AND THE LENGTH OF THE RE-
 REQUIRED RAMP? HOW IS A SAFE TRANSI-
 TION MADE FROM THE VERTICAL LIFT
 WHILE IN USE TO THE STAGE?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-03-06 Cont ID  
Sent By jwitmer Date 2003-03-06 Time 16:01 Rev Time 0.55
Received By jwitmer Date 2003-03-06 Time 16:01 Sent To  
Notes
2003-03-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03010851
 ADD: 4500 S DIXIE HWY
 CONT: TUSCANI
 TEL: (561) 586-3808
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)11-4.1.6 ACCESSIBLE BUILDINGS:
 ALTERATIONS,
 1(B) IF EXISTING ELEMENTS, OR COMMON
 AREAS ARE ALTERED, THEN EACH SUCH ALTER-
 ED ELEMENT,SPACE, FEATURE, OR AREA
 SHALL COMPLY WITH THE APPLICABLE
 PROVISIONS OF 11-4.1.1 TO 11-4.1.3.
 MINIMUM REQUIREMENTS FOR NEW CONSTRUC-
 TION, INDICATE HOW VERTICAL ACCESSIBIL-
 ITY IS BEING MET FROM THE BAND ROOM TO
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026
 HE

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-01-24 Cont ID  
Sent By jwitmer Date 2003-01-24 Time 14:43 Rev Time 1.26
Received By jwitmer Date 2003-01-24 Time 14:43 Sent To  
Notes
2003-01-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03010851
 ADD: 4500 S DIXIE
 CONT: TUSCANI GENERAL CONTRACTORS
 TEL: (561)586-3808
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) 11-4.1.6:ACCESSIBLE BUILDINGS:
 ALTERATIONS,
 1 (B) IF EXISTING ELEMENTS, OR COMMON
 AREAS ARE ALTERED, THEN EACH SUCH ALTER-
 ED ELEMENT, SPACE, FEATURE, OR AREA
 SHALL COMPLY WITH THE APPLICABLE PROVIS-
 IONS OF 11-4.1.1 TO 11-4.1.3. MINIMUM
 REQUIREMENTS FOR NEW CONSTRUCTION.
 INDICATE HOW VERTICAL ACCESSILITY IS
 BEING MET FROM THE BAND ROOM TO THE
 STAGE?
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 (8412)

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-07-29 Cont ID  
Sent By dpalmer Date 2003-07-29 Time 14:02 Rev Time 0.25
Received By dpalmer Date 2003-07-29 Time 14:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-03-28 Cont ID  
Sent By alange Date 2003-07-25 Time 10:36 Rev Time 0.50
Received By dpalmer Date 2003-03-28 Time 16:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-01-27 Cont ID  
Sent By dpalmer Date 2003-01-27 Time 06:40 Rev Time 0.25
Received By dpalmer Date 2003-01-27 Time 06:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-03-31 Cont ID  
Sent By nmccray Date 2003-03-31 Time 11:40 Rev Time 0.00
Received By nmccray Date 2003-03-31 Time 11:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2003-03-06 Cont ID  
Sent By mcarsill Date 2003-03-06 Time 09:43 Rev Time 0.00
Received By mcarsill Date 2003-03-06 Time 09:43 Sent To  
Notes
2003-03-06 00:00:00PREVIOUS PLAN REVIEW COMMENTS NOT
 CORRECTED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-01-30 Cont ID  
Sent By mcarsill Date 2003-01-30 Time 10:58 Rev Time 0.00
Received By mcarsill Date 2003-01-30 Time 10:58 Sent To  
Notes
2003-01-30 00:00:001) PLEASE EXPLAIN HOW ACCESSIBILITY IS
 ACHEIVED FOR THE STAGE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-25 Cont ID  
Sent By alange Date 2003-07-25 Time 10:36 Rev Time 0.00
Received By alange Date 2003-07-25 Time 10:36 Sent To E
Notes
2003-07-25 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-14 Cont ID  
Sent By btrobaug Date 2003-01-14 Time 17:18 Rev Time 0.00
Received By btrobaug Date 2003-01-14 Time 17:18 Sent To  
Notes
2003-01-14 00:00:00COM BOARD #2./WRT