| 2003-01-15 00:00:00 | PLEASE PROVIDE THE FOLLOWING INFORMATION |
| | FOR REVIEW. |
| | |
| | 1.SUBMITTAL/INSTALLATION INSTRUCTIONS |
| | FOR THE FIRE WRAP. (FIRE WRAP ABOVE |
| | HOOD CEILING RATED CHASE TO BEGIN AT |
| | THE MEZZANINE LEVEL). |
| | |
| | 2.PLAN SHEET M-2.04, PLAN INDICATES |
| | THE GREASE DUCT & SUPPLY DUCT ARE IN |
| | THE SAME SHAFT.AS PER NFPA 96 4-7.6, |
| | MULTIPLE DUCTS SHALL NOT BE PERMITTED IN |
| | A SINGLE ENCLOSURE. 2001 FBC(M) 506.3.12 |
| | GREASE DUCT ENCLOSURE SHALL BE SEPARATED |
| | FROM THE DUCT A MINIMUM OF 6" AND A |
| | MAXIMUM OF 12" & SHALL SERVE A SINGLE |
| | GREASE EXHAUST DUCT SYSTEM. |
| | |
| | 3.PLEASE NOTE AIR VELOCITY SHALL BE |
| | A MINIMUM OF 1,500 FPM & NOT GREATER |
| | THAN 2,500 FPM.2001 FBC(M) 506.3.6. |
| | |
| | 4.PLANS SUBMITTED WITH BUILDING PERMIT |
| | INDICATE A HOOD FOR THE DISHWASHER. |
| | PLEASE PROVIDE SUBMITTAL FOR HOOD. |
| | |
| | PROVISO:WELDS TO BE INSPECTED PRIOR TO |
| | COVERING WITH WRAP OR INSTALLED IN SHAFT |
| | |
| | ADDITIONAL PERMIT REQUIRED FOR FIRE |
| | SUPRESSION.PROVIDE PLANS WITH PERMIT |
| | APPLICATION. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT 659-8096 |