| Plan Review Stops For Permit 03010697 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2003-02-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-02-07 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-02-07 |
Time |
10:07 |
Sent To |
|
|
| Notes |
| 2003-02-07 00:00:00 | 1) PLEASE SUBMIT PRODUCT APPROVALS FOR | | | DUCT WRAP. | | | | | | 2) IF STEAM KETTLE IS TO BE USED FOR | | | ANY COOKING THAT PRODUCES SMOKE OR | | | GREASE LADEN VAPORS, THEN AN | | | EXTINGUISHING NOZZLE WILL BE REQUIRED. | | | | | | 3) PLEASE SEE MECHANICAL REVIEWER NOTES | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2003-02-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-02-07 |
Time |
09:20 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2003-02-07 |
Time |
09:20 |
Sent To |
FIRE |
|
| Notes |
| 2003-02-07 00:00:00 | PROVISO: | | | | | | AIR VELOCITY WITHIN THE DUCT SYSTEM | | | SHALL BE A MINIMUM OF 1,500 FPM & NOT | | | GREATER THAN 2,500 FPM. | | | | | | PROVIDE MANUFACTURERS INSTALLATION | | | INSTRUCTIONS FOR THE 3M FIREWRAP ON THE | | | JOBSITE AT TIME OF INSPECTION. | | | | | | WELDS ON DUCT SHALL BE INSPECTED PRIOR | | | TO COVERING. | | | | | | TEST & BALANCE REQUIRED FOR FINAL. | | | | | | ADDITIONAL PLANS & PERMIT REQUIRED FOR | | | FIRE SUPRESSION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
|