Plan Review Details - Permit 03010697
Plan Review Stops For Permit 03010697
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-02-07 Cont ID  
Sent By pkrauss Date 2003-02-07 Time 09:33 Rev Time 0.00
Received By mcarsill Date 2003-02-07 Time 10:07 Sent To  
Notes
2003-02-07 00:00:001) PLEASE SUBMIT PRODUCT APPROVALS FOR
 DUCT WRAP.
  
 2) IF STEAM KETTLE IS TO BE USED FOR
 ANY COOKING THAT PRODUCES SMOKE OR
 GREASE LADEN VAPORS, THEN AN
 EXTINGUISHING NOZZLE WILL BE REQUIRED.
  
 3) PLEASE SEE MECHANICAL REVIEWER NOTES
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-02-07 Cont ID  
Sent By pkrauss Date 2003-02-07 Time 09:20 Rev Time 0.30
Received By pkrauss Date 2003-02-07 Time 09:20 Sent To FIRE
Notes
2003-02-07 00:00:00PROVISO:
  
 AIR VELOCITY WITHIN THE DUCT SYSTEM
 SHALL BE A MINIMUM OF 1,500 FPM & NOT
 GREATER THAN 2,500 FPM.
  
 PROVIDE MANUFACTURERS INSTALLATION
 INSTRUCTIONS FOR THE 3M FIREWRAP ON THE
 JOBSITE AT TIME OF INSPECTION.
  
 WELDS ON DUCT SHALL BE INSPECTED PRIOR
 TO COVERING.
  
 TEST & BALANCE REQUIRED FOR FINAL.
  
 ADDITIONAL PLANS & PERMIT REQUIRED FOR
 FIRE SUPRESSION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.