Plan Review Details - Permit 03010450
Plan Review Stops For Permit 03010450
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-01-28 Cont ID  
Sent By btrobaug Date 2003-01-24 Time 13:34 Rev Time 2.50
Received By lhatten Date 2003-01-24 Time 17:57 Sent To  
Notes
2003-01-28 00:00:00REVIEW & STAMPED PLANS 01/24/2003
 PRINT CARD01/28/2003

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-10-09 Cont ID  
Sent By btrobaug Date 2003-10-09 Time 17:51 Rev Time 0.50
Received By btrobaug Date 2003-10-09 Time 17:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-03-10 Cont ID  
Sent By csiegber Date 2003-10-06 Time 14:30 Rev Time 0.00
Received By btrobaug Date 2003-03-10 Time 11:30 Sent To P
Notes
2003-03-10 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING CHANGES TO
 PLANS PRIOR TO ROUGH
 INSPECTION,RESUBMIT FOR REVIEW.
  
 1} THE LAUNDRY CIRCUIT ON THE PANEL
 SCHEDULE SHOULD BE CALCULATED @ 1500
 VA.PER210-16(B).
  
 2} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.ON PANEL
 SCHEDULE.
  
 3} THE GROUNDED ELECTRODE CONDUCTOR IS
 TOO SMALL FOR 400 AMP SERVICE,SEE
 250-66.SHOULD BE 1/0.
  
 4} THE FEEDER TO TO PANEL "B" SHOULD
 CONTAIN AN EQUIPMENT GROUND PER 250-122.
  
 5} THE SMOKE DETECTOR IN THE KITCHEN
 DOES NOT COMPLY WITH 8-1.4.2
 NFPA-72,SHOULD BE CHANGED TO A HEAT
 DETECTOR OR BE REMOVED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT 8392

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-01-24 Cont ID  
Sent By dpalmer Date 2003-03-10 Time 08:25 Rev Time 0.50
Received By btrobaug Date 2003-01-24 Time 13:30 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-10-06 Cont ID  
Sent By csiegber Date 2003-10-06 Time 14:30 Rev Time 0.00
Received By csiegber Date 2003-10-06 Time 14:30 Sent To E
Notes
2003-10-06 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-03-13 Cont ID  
Sent By sthyng Date 2003-03-13 Time 14:18 Rev Time 0.00
Received By sthyng Date 2003-03-13 Time 14:18 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-03-10 Cont ID  
Sent By dpalmer Date 2003-03-10 Time 08:25 Rev Time 0.00
Received By dpalmer Date 2003-03-10 Time 08:25 Sent To E
Notes
2003-03-10 00:00:00TO BT`S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-02-20 Cont ID  
Sent By dpalmer Date 2003-02-20 Time 15:41 Rev Time 0.00
Received By dpalmer Date 2003-02-20 Time 15:41 Sent To P
Notes
2003-02-20 00:00:00TO PLUMB INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-13 Cont ID  
Sent By dpalmer Date 2003-01-13 Time 08:18 Rev Time 0.00
Received By dpalmer Date 2003-01-13 Time 08:18 Sent To P
Notes
2003-01-13 00:00:00RES RACK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-09 Cont ID  
Sent By sgraham Date 2003-01-10 Time 15:25 Rev Time 0.00
Received By dpalmer Date 2003-01-09 Time 18:53 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-03-03 Cont ID  
Sent By pkrauss Date 2003-03-03 Time 13:34 Rev Time 0.35
Received By pkrauss Date 2003-03-03 Time 13:30 Sent To  
Notes
2003-03-03 00:00:00MECHANICAL PERMIT 03010477

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-01-18 Cont ID  
Sent By kstevens Date 2003-03-01 Time 11:38 Rev Time 1.00
Received By hmoser Date 2003-01-18 Time 09:37 Sent To E
Notes
2003-01-18 00:00:00PLAN DENIED
 CFM.ON PLAN DO NOT MATCH CFM.ON
 EQUIPMENT,OR MANUAL (J)
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-03-14 Cont ID  
Sent By kstevens Date 2003-03-14 Time 17:05 Rev Time 0.50
Received By kstevens Date 2003-03-14 Time 17:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2003-03-12 Cont ID  
Sent By sthyng Date 2003-03-13 Time 14:18 Rev Time 0.33
Received By kstevens Date 2003-03-12 Time 14:12 Sent To  
Notes
2003-03-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) WASH MACHINE AND LAUNDRY SINK ARE
 STILL DRAINING INTO THE WET VENT FOR THE
 MASTER BATHROOM. SEPARATE THE LAUNDRY
 ROOM PLUMBING FROM THE BATHROOM PLUMBING
 AND GROUP ALL THE FIXTURES FOR THE
 BATHROOM GROUP TOGETHER ON SANITARY
 RISER DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-03-01 Cont ID  
Sent By btrobaug Date 2003-03-10 Time 11:30 Rev Time 0.75
Received By kstevens Date 2003-03-01 Time 11:33 Sent To M
Notes
2003-03-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) COMMENTS FROM PREVIOUS REVIEW WERE
 NOT ADDRESSED.
 A) ONLY FIXTURES IN THE BATHROOM GROUP
 SHALL CONNECT TO THE WET VENTED HORI-
 ZONTAL BRANCH DRAIN. SEC 909.1. 2ND
 FLOOR LAUNDRY SHALL DRAIN DOWNSTREAM OF
 THE W/C AND SHOWER.
 B) MASTER BATH FLOOR PLAN SHOWS 2 LAVS,
 BUT RISER SHOWS 3? PLEASE CLAIRFY
 C) RISER DIAGRAM SHOWS SINK ON 2ND
 FLOOR, BUT NOT SHOWN ON FLOOR PLAN.
 PLEASE CLAIRFY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-01-18 Cont ID  
Sent By dpalmer Date 2003-02-20 Time 15:41 Rev Time 1.00
Received By jleech Date 2003-01-18 Time 08:32 Sent To M
Notes
2003-01-18 00:00:00DENIED;
 PAGE A-1 PLUMBING RISER;
 1.ONLY FIXTURES IN THE BATHROOM GROUP
 SHALL CONNECT TO THE WET VENTED
 HORIZONTAL BRANCH DRAIN. SEC.909.1.
 2ND FL. LAUNDRY AND MASTER BATH.
 2.TABLE 909.3
 ONLY 4 FU'S ON 2" WET VENT.
 3.MASTER BATH FLOOR PLAN SHOWS 2 LAVS.
 RISER DIAGRAM SHOWS 3.
 4.RISER DIAGRAM SHOWS SINK ON 2ND FLOOR
 NOT SHOWN ON FLOOR PLAN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop Z ZONING
Rev No 1 Status P Date 2003-01-10 Cont ID  
Sent By dpalmer Date 2003-01-09 Time 18:53 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***