Plan Review Details - Permit 03010432
Plan Review Stops For Permit 03010432
Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status P Date 2003-11-05 Cont ID  
Sent By rbrown Date 2003-11-05 Time 17:58 Rev Time 0.00
Received By rbrown Date 2003-11-05 Time 17:58 Sent To  
Notes
2003-11-05 00:00:00REVISION 10/23/03 FOR LOADING RAMP
 DETAIL SHEET A-16

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2003-11-05 Cont ID  
Sent By rbrown Date 2003-11-05 Time 17:27 Rev Time 0.00
Received By rbrown Date 2003-11-05 Time 17:27 Sent To  
Notes
2003-11-05 00:00:00REVISION 10/23/03 FOR 40' LONG RETAINING
 WALL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2003-08-25 Cont ID  
Sent By csiegber Date 2003-10-24 Time 10:36 Rev Time 0.00
Received By rbrown Date 2003-08-25 Time 11:08 Sent To  
Notes
2003-08-25 00:00:00REVISION SUBMITTED 8/18/03 FOR TRUCK
 RAMPS AND OVERHEAD DOORS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status F Date 2003-08-06 Cont ID  
Sent By alange Date 2003-08-18 Time 14:49 Rev Time 0.00
Received By rbrown Date 2003-08-06 Time 14:04 Sent To  
Notes
2003-08-06 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 REVISION SUBMITTED ON 7/31/03 FOR TRUCK
 RAMPS AND OVERHEAD DOORS:
  
 1) FBC 1707.4OVERHEAD DOORS ON NORTH
 AND WEST ELEVATIONS.THE PROPOSED
 REVISIONS WOULD INCREASE THE OPENING
 WIDTH TO 12'.THAT SIZE IS OUTSIDE THE
 SCOPE OF THE SUBMITTED J.B. GARAGE DOOR,
 INC. STEEL OVERHEAD GARAGE DOOR PRODUCT
 APPROVAL NOA# 01-0129.16.SUBMIT THREE
 COPIES OF ALTERNATIVE PRODUCT APPROVAL
 OR AMEND THE OPENING SIZE ON THE PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status F Date 2003-08-06 Cont ID  
Sent By rbrown Date 2003-08-06 Time 11:26 Rev Time 0.00
Received By rbrown Date 2003-08-06 Time 11:26 Sent To  
Notes
2003-08-06 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 SUBMITTAL ON 7/31/03 FOR ADDITIONAL
 STEEL SHOP DRAWINGS:
  
 1) STRUCTURAL SHOP DRAWINGS SHALL BE
 REVIEWED AND STAMPED BY THE ENGINEER OF
 RECORD BEFORE SUBMITTAL.ALTERNATIVELY,
 A SIGNED AND SEALED LETTER FROM THE
 ENGINEER OF RECORD CAN BE SUBMITTED WITH
 THE DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2003-08-06 Cont ID  
Sent By rbrown Date 2003-08-06 Time 11:25 Rev Time 0.00
Received By rbrown Date 2003-08-06 Time 11:25 Sent To  
Notes
2003-08-06 00:00:00REVISION SUBMITTED 7/23/03 FOR COLUMN
 FIRE PROTECTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2003-08-06 Cont ID  
Sent By rbrown Date 2003-08-06 Time 11:24 Rev Time 0.00
Received By rbrown Date 2003-08-06 Time 11:24 Sent To  
Notes
2003-08-06 00:00:00REVISION SUBMITTED 7/23/03 FOR FLASHING
 DETAIL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2003-08-06 Cont ID  
Sent By rbrown Date 2003-08-06 Time 11:22 Rev Time 0.00
Received By rbrown Date 2003-08-06 Time 11:22 Sent To  
Notes
2003-08-06 00:00:00REVISION SUBMITTED 7/23/03 FOR JOIST AND
 GIRDER DETAILS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2003-05-19 Cont ID  
Sent By alange Date 2003-07-31 Time 14:20 Rev Time 0.00
Received By rbrown Date 2003-05-19 Time 16:17 Sent To  
Notes
2003-05-19 00:00:005-12-03 SUBMITTAL FOR WALL LIFT
 ENGINEERING

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2003-05-19 Cont ID  
Sent By rbrown Date 2003-05-19 Time 16:16 Rev Time 0.00
Received By rbrown Date 2003-05-19 Time 16:16 Sent To  
Notes
2003-05-19 00:00:005-12-03 SUBMITTAL FOR ROOFING PRODUCT
 APPROVAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2003-04-23 Cont ID  
Sent By shernand Date 2003-05-12 Time 13:18 Rev Time 0.00
Received By rbrown Date 2003-04-23 Time 10:42 Sent To  
Notes
2003-04-23 00:00:004-18-03 SUBMITTAL FOR STOREFRONT FRAMING
 SYSTEM AND ANCHORAGE

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2003-04-22 Cont ID  
Sent By rbrown Date 2003-04-22 Time 19:20 Rev Time 0.00
Received By rbrown Date 2003-04-22 Time 19:20 Sent To  
Notes
2003-04-22 00:00:004-18-03 SUBMITTAL FOR WALL PANEL REINF.
 SHOP DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2003-04-22 Cont ID  
Sent By rbrown Date 2003-04-22 Time 19:13 Rev Time 0.00
Received By rbrown Date 2003-04-22 Time 19:13 Sent To  
Notes
2003-04-22 00:00:004-18-03 SUBMITTAL FOR WALL PANEL SHOP
 DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-04-22 Cont ID  
Sent By rbrown Date 2003-04-22 Time 18:43 Rev Time 0.00
Received By rbrown Date 2003-04-22 Time 18:42 Sent To  
Notes
2003-04-22 00:00:00STRUCTURAL STEEL SHOP DRAWING SUBMITTAL
 ON 4-18-03

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-04-11 Cont ID  
Sent By shernand Date 2003-04-18 Time 15:58 Rev Time 0.00
Received By rbrown Date 2003-04-10 Time 15:22 Sent To  
Notes
2003-04-10 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 --PROVISO--
 THE SUBMITTED RATIONAL ANALYSIS FOR THE
 STOREFRONT DOORS REFERS TO MIAMI-DADE
 PRODUCT APPROVAL NOA# 01-0226.05.THAT
 PRODUCT APPROVAL (NOT SUBMITTED WITH THE
 APPLICATION) HAS BEEN DOWNLOADED FROM
 THE MIAMI-DADE WEBSITE AND ATTACHED TO
 THE RATIONAL ANALYSIS SHEETS.ANY
 DEVIATION FROM THE PRODUCT APPROVAL AND
 RATIONAL ANALYSIS WILL REQUIRE A
 SEPARATE PERMIT APPLICATION AND FEES.
 NOTE:UNLIKE THE ONE PREVIOUSLY
 SUBMITTED, DOOR PRODUCT APPROVAL
 NOA# 01-0226.05 AND ASSOCIATED RATIONAL
 ANALYSIS WILL REQUIRE HURRICANE SHUTTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-03-24 Cont ID  
Sent By shernand Date 2003-04-04 Time 14:59 Rev Time 0.00
Received By rbrown Date 2003-03-24 Time 15:15 Sent To  
Notes
2003-03-24 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 2/11/03:
  
 2) SUBMITTAL OF THE RECEIPT FOR IMPACT
 FEES IS NOTED BUT THE SUBMITTED PLANS
 ARE NOT STAMPED BY PAIM BEACH COUNTY
 BUILDING DEPT TO VERIFY THAT THEY ARE
 THE PLANS ASSESSED FOR IMPACT.INSERT
 ONE STAMPED PLAN SHEET INTO EACH SET.
  
 7) FBC* 104.2.1CANTILEVERED CONCRETE
 EYEBROW DETAIL 5/S4.4.THE SUBMITTED
 HAND-DRAWN SKETCH DOES NOT SHOW THE
 DOWEL BAR BEING USED IN ACCORDANCE WITH
 THE MANUFACTURER'S RECOMMENDATIONS.
 REVIEW AND AMEND THE DETAIL AS NECESSARY
 THE DETAILS SHALL BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 SPECIFYING THE DOWEL CONNECTORS.THE
 DETAILS SHALL THEN BE SIGNED AND DATED
 BY THE ENGINEER OF RECORD TO CONFIRM
 THAT THEY HAVE BEEN REVIEWED AND
 ACCEPTED.
  
 13)FBC 13-101.1.6SHELL BUILDINGS.
 THE PROJECT INFORMATION HAS NOT BEEN
 ENTERED ON PAGE 1 OF THE SUBMITTED CODE
 COMPLIANCE FORM 400B.ALSO, FOR SHELL
 BUILDINGS, ALL ASSUMPTIONS MADE ABOUT
 FEATURES NOT INSTALLED UNTIL LATER, AND
 ARE NOT ON THE BUILDING PLANS, SHALL BE
 LISTED AND APPENDED TO FORM 400B.THIS
 WILL BE COMPARED TO THOSE FEATURES
 PROPOSED FOR INSTALLATION AT A LATER
 DATE WHEN COMPLETION OF THE BUILDING IS
 PERMITTED.
  
 15) DOOR AND WINDOW SCHEDULES, SHEETS
 A-5 AND A-7 SHOW A 9'-0" HIGH STOREFRONT
 DOOR WHICH EXCEEDS THE MAXIMUM HEIGHT
 COVERED BY SUBMITTED PRODUCT APPROVAL
 NOA# 01-0919.02
  
 16) FBC* 105.3RESIDENT INSPECTOR
 PROGRAM.SUBMIT A THIRD SET OF THE
 PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-02-11 Cont ID  
Sent By rbrown Date 2003-02-11 Time 13:21 Rev Time 0.00
Received By rbrown Date 2003-02-11 Time 13:21 Sent To  
Notes
2003-02-11 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT SHALL BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 A COPY OF THE RECEIPT SUBMITTED, TO CITY
 OF WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) FBC 705.1.1.2NORTH END OF THE WEST
 ELEVATION.THAT SECTION OF THE WALL
 WHICH IS WITHIN 15 FEET OF THE PROPERTY
 LINE SHALL HAVE ALL OPENINGS EQUIPPED
 WITH APPROVED OPENING PROTECTIVES (SEE
 FBC 705.1.3) WITH A RATING OF NOT LESS
 THAN 3/4 HOUR.
  
 4) FBC* 1804.2.2SUBMIT A GEOTECHNICAL
 REPORT (REF: DRAWING SHEET S5.2,
 SITE WORK NOTE #2).
  
 5) FBC* 104.2.1.2FOUNDATION SECTION
 7/S4.1 (TYP).NO ANCHORAGE
 REINFORCEMENT IS SHOWN BETWEEN THE TILT-
 UP WALL PANELS AND THE FOUNDATIONS.
 SUBMIT AN ENGINEER'S SIGNED AND SEALED
 LETTER, CONFIRMING THAT NO ANCHORAGE TO
 THE FOUNDATION IS REQUIRED FOR UPLIFT OR
 FOR LATERAL LOAD DUE TO THE RETAINED
 FILL AND THE WAREHOUSE FLOOR SURCHARGE
 LOADS.
  
 6) NOTE:DETAIL 8/S4.1 HAS BEEN RED-
 LINED TO REFERENCE 9/S4.1 WHICH DOES NOT
 APPEAR TO BE CALLED UP ANYWHERE ON THE
 PLANS.
  
 7) PROVISO: FBC* 104.2.1.2 DETAIL 5/S4.4
 INCIDENTAL/MAINTENANCE LOADING ON THE
 CANTILEVER CONCRETE 'EYEBROW'.SUBMIT
 SHOP DRAWINGS OF THE MEANS OF ATTACHING
 THE 'EYEBROW' TO THE TILT-UP WALL PANEL.
  
 8) FBC* F102.2.4FIRE DISTRICT.AMEND
 THE PLANS TO INCLUDE THE REQUIREMENT FOR
 THE ROOF COVERING TO BE CLASS A OR B, AS
 THE BUILDING IS WITHIN THE FIRE DISTRICT
  
 9) SUBMIT A PRODUCT APPROVAL FOR THE
 PROPOSED ROOFING SYSTEM.
  
 10) SUBMIT A PRODUCT APPROVAL FOR THE
 PROPOSED HURRICANE MISSILE IMPACT
 PROTECTION SHUTTERS.
  
 11) METAL AWNINGS.SUBMIT DETAILS, OR
 A SEPARATE AWNING PERMIT APPLICATION
 WILL BE REQUIRED.
  
 12) A SEPARATE PERMIT APPLICATION WILL
 BE REQUIRED FOR THE DUMPSTER ENCLOSURE.
  
 13) NOTE:FBC 13-101.1.6ENERGY CODE
 COMPLIANCE SHALL BE DEMONSTRATED BY
 SUBMITTAL OF CODE COMPLIANCE FORM 400B
 WITH A LIST APPENDED TO DESCRIBE THE
 ASSUMPTIONS MADE ABOUT BUILDING FEATURES
 NOT INSTALLED DURING THIS PHASE OF THE
 PROJECT.
  
 14) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-12-18 Cont ID  
Sent By btrobaug Date 2003-12-18 Time 15:22 Rev Time 0.50
Received By btrobaug Date 2003-12-18 Time 15:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-03-17 Cont ID  
Sent By dpalmer Date 2003-03-17 Time 06:47 Rev Time 0.50
Received By dpalmer Date 2003-03-17 Time 06:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-02-07 Cont ID  
Sent By dpalmer Date 2003-02-07 Time 11:31 Rev Time 0.50
Received By dpalmer Date 2003-02-07 Time 11:30 Sent To  
Notes
2003-02-07 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SEE RISER DIAGRAM,
 PLEASE SHOW SIZE OF METER AND MAIL DISC
 FEEDING NEW PANEL 1HP. PLEASE ALSO
 SEE LOAD SHOWN AT 147A'S WITH #3'S
 FEEDING A 225A PANEL? PLEASE SIZE
 CONDUCTORS ACCORDING TO 310-16 AND OCP
 PER 240.
  
 2)NOTE: PLEASE SHOW AIC RATING OF THAT
 SAME NEW (HOUSE) DISCONNECT.
 IF DIFFERENT FROM TYPICALS??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2003-02-10 Cont ID  
Sent By mamini Date 2003-02-10 Time 09:54 Rev Time 0.50
Received By mamini Date 2003-02-10 Time 09:54 Sent To  
Notes
2003-02-10 00:00:00PASSED:
 1. SEE PERMIT # 03012266 FOR UNDERGROUND
 UTILITIES AND SITE WORKS.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-03-19 Cont ID  
Sent By mcarsill Date 2003-03-19 Time 12:18 Rev Time 0.00
Received By mcarsill Date 2003-03-19 Time 12:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-02-07 Cont ID  
Sent By mcarsill Date 2003-02-07 Time 13:12 Rev Time 0.00
Received By mcarsill Date 2003-02-07 Time 13:12 Sent To  
Notes
2003-02-07 00:00:001) SITE PLAN SHALL SHOW ALL FIRE
 HYDRANTS LOCATED IN THE VICINTY OF THE
 BUILDING.
  
 2) NO FIRE SPRINKLER PLANS OR HYDRAULIC
 CALCULATIONS PROVIDED WITH DRAWINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2003-10-24 Cont ID  
Sent By csiegber Date 2003-10-24 Time 10:36 Rev Time 0.00
Received By csiegber Date 2003-10-24 Time 10:36 Sent To B
Notes
2003-10-24 00:00:00TO RB DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2003-10-24 Cont ID  
Sent By csiegber Date 2003-10-24 Time 10:32 Rev Time 0.00
Received By csiegber Date 2003-10-24 Time 10:32 Sent To B
Notes
2003-10-24 00:00:00TO RB DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2003-08-18 Cont ID  
Sent By alange Date 2003-08-18 Time 14:49 Rev Time 0.00
Received By alange Date 2003-08-18 Time 14:49 Sent To B
Notes
2003-08-18 00:00:00TO RB DESK

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2003-07-31 Cont ID  
Sent By alange Date 2003-07-31 Time 14:20 Rev Time 0.00
Received By alange Date 2003-07-31 Time 14:20 Sent To B
Notes
2003-07-31 00:00:00TO RB DESK

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-07-31 Cont ID  
Sent By alange Date 2003-07-31 Time 08:52 Rev Time 0.00
Received By alange Date 2003-07-31 Time 08:52 Sent To B
Notes
2003-07-31 00:00:00TO RB DESK

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-07-23 Cont ID  
Sent By alange Date 2003-07-23 Time 11:11 Rev Time 0.00
Received By alange Date 2003-07-23 Time 11:11 Sent To B
Notes
2003-07-23 00:00:00TO RB DESK,3 REVISIONS

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-05-12 Cont ID  
Sent By shernand Date 2003-05-12 Time 13:18 Rev Time 0.00
Received By shernand Date 2003-05-12 Time 13:18 Sent To B
Notes
2003-05-12 00:00:00RBROWN DESK\\

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-04-18 Cont ID  
Sent By shernand Date 2003-04-18 Time 15:56 Rev Time 0.00
Received By shernand Date 2003-04-18 Time 15:56 Sent To B
Notes
2003-04-18 00:00:00RBROWN DESK.4 RESUBS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-04-04 Cont ID  
Sent By shernand Date 2003-04-04 Time 14:59 Rev Time 0.00
Received By shernand Date 2003-04-04 Time 14:59 Sent To B
Notes
2003-04-04 00:00:00RBROWN DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-02-27 Cont ID  
Sent By sgraham Date 2003-01-31 Time 08:25 Rev Time 0.00
Received By dpalmer Date 2003-02-27 Time 16:08 Sent To  
Notes
2003-02-27 00:00:00TO COMM BOARD #62

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-09 Cont ID  
Sent By dpalmer Date 2003-01-09 Time 18:56 Rev Time 0.00
Received By dpalmer Date 2003-01-09 Time 18:56 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-03-10 Cont ID  
Sent By pkrauss Date 2003-03-10 Time 09:20 Rev Time 0.35
Received By pkrauss Date 2003-03-10 Time 09:17 Sent To  
Notes
2003-03-10 00:00:00MECHANICAL PERMIT 03022068
 SCOPE OF THIS PERMIT IS ELECTRICAL ROOM
 EXHAUST ONLY.TENANT BUILDOUT WILL
 BE UNDER SEPARATE PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-02-10 Cont ID  
Sent By pkrauss Date 2003-02-10 Time 09:58 Rev Time 0.30
Received By pkrauss Date 2003-02-10 Time 09:58 Sent To  
Notes
2003-02-10 00:00:00DENIED:
 REFERENCE PLAN SHEET A-9 & 10 NOTES:
 PLEASE CLARIFY HOW THE VENTILATION
 REQUIREMENTS ARE TO BE MET (.05 CFM PER
 SQ FT) WITHOUT INSTALLING THE CURBS &
 EXHAUST FANS.
  
 PROVISO:
 EXHAUST FANS FOR THE ELEC/PUMP ROOMS -
 EXHAUST SHALL NOT BE DIRECTED ONTO
 WALKWAYS AS PER 2001 FBC(M) 401.5.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-03-26 Cont ID  
Sent By kstevens Date 2003-03-26 Time 07:45 Rev Time 1.00
Received By kstevens Date 2003-03-26 Time 07:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-01-30 Cont ID  
Sent By kstevens Date 2003-01-30 Time 17:11 Rev Time 1.33
Received By kstevens Date 2003-01-30 Time 17:10 Sent To  
Notes
2003-01-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHTS A-6, A-9, & A-15 DETAIL #3.
 A-6 SHOWS SCUPPER SIZE TO BE 12"X20",
 A-9 SHOWS SCUPPER SIZE TO BE 10"X23",
 A-15 SHOWS SCUPPER SIZE TO BE 12"X20",
 PLEASE CLAIRFY.
 2) PLEASE PROVIDE CALCULATIONS FOR ROOF
 DRAINS, PRIMARY AND SECONDARY PER SEC
 1106, AND 1107. SHOW TOTAL SQ FT INCLUD-
 ING 1/2 AREA OF ALL VERTICAL WALLS &
 PARAPET WALLS.
 3) SHT PO.1 WATER RISER, AIR CHAMBERS
 ARE NOT APPROVED AND WATER HAMMER ARRES-
 TORS REQUIRED BY 604.9 SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT ABOVE THE CEILING AT THE TOP OF THE
 DROPS.
 4) SHT PO-1 PLUMBING NOTES #13 AIR CHAM-
 BERS ARE NOT APPROVED. PLEASE DELETE
 FROM REFERENCE.
 5) SHT P2.1 FLOOR DRAIN FROM PUMP ROOM
 SHALL DRAIN TO SANITARY NOT STORM.
 6) SEPARATE IRRIGATION PLANS AND PERMIT
 REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2003-01-31 Cont ID  
Sent By dpalmer Date 2003-01-09 Time 18:56 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***