Plan Review Details - Permit 03010378
Plan Review Stops For Permit 03010378
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-03-18 Cont ID  
Sent By jwitmer Date 2003-03-18 Time 10:44 Rev Time 1.00
Received By jwitmer Date 2003-03-18 Time 10:44 Sent To  
Notes
2003-03-18 00:00:00 
  
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 03020378
 ADDRESS: 1801 PALM BCH LAKES BLVD
 "SEARS"
 CONT: TO BE DETERMINED
 TELL # (561)------
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.104.2.1.2 ADMINISTRATIVE CODE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-01-27 Cont ID  
Sent By jwitmer Date 2003-01-27 Time 10:43 Rev Time 1.55
Received By jwitmer Date 2003-01-27 Time 10:43 Sent To  
Notes
2003-01-27 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03010378
 ADD: 1801 PALM BEACH LAKESBLVD
 CONT: PLAN REVIEW
 SIMON PROPERTIES/
 MARCY ESPOSITO
 TEL: (954)931-0442
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) A206 DETAIL# 4 INDICATES STUD BRACING
 TO THE STRUCTURE ABOVE, NO INFORMATION
 AS TO WHAT TYPE OF FASTENER TO THE STRUC
 TURE ABOVE?
  
 2) A206 DETAIL # 10 GLASS GUARDRAIL
 SYSTEM: PLEASE PROVIDE MANUFACTURES SPEC
 ON THE GLASS PANEL SYSTEM AND FASTENING
 TO THE STRUCTURE TO MEET THE REQUIREMENT
 OF 1608.2.2GUAEDRAIL SYSTEM DESIGN AND
 CONSRUCTION,
 2405.5 GLASS BALISTER PANELS/ RAILING
  
 3) A302 DETAIL# 3, CEILING SOFFIT DETAIL
 THIS SEEMS TO BE THE ONLY DETAIL TO BE
 USED FOR ALL SOFFITS, PLEASE PROVIDE
 THE STUD SPACING C/C, MISSING INFO FOR
 THE ATTACHMENT TO THE STRUCTURE ABOVE?
  
 4) A 201/ A 202 IN THE HANDICAPPED FIT-
 TING ROOMS ARE THESE BENCHES SELF SUP-
 PORTING? OR ARE BACKING REQUIREMENTS
 NEEDED?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 8412

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-08-04 Cont ID  
Sent By dpalmer Date 2003-08-04 Time 14:56 Rev Time 0.33
Received By dpalmer Date 2003-08-04 Time 14:56 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-07-23 Cont ID  
Sent By alange Date 2003-08-01 Time 11:46 Rev Time 0.33
Received By dpalmer Date 2003-07-23 Time 15:07 Sent To  
Notes
2003-07-23 00:00:00*********** UNSAT **************
  
 1)NOTE: PLEASE SEE ATTACHED COPY OF FAC
 61G15-23.002
 PLEASE SEE MISSING INFORMATION ON TITLE
 BLOCK. AUTH #, ENG'S #`S ETC.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE NAY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-03-05 Cont ID  
Sent By shernand Date 2003-07-17 Time 15:41 Rev Time 0.75
Received By dpalmer Date 2003-03-05 Time 06:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-01-24 Cont ID  
Sent By dpalmer Date 2003-01-24 Time 14:17 Rev Time 0.50
Received By dpalmer Date 2003-01-24 Time 14:05 Sent To  
Notes
2003-01-24 00:00:00************ UNSAT **************
  
 1)NOTE: PLANS ARE SHOWING ALL WORK TO BE
 UNDER 2000 NEC. PLEASE NOTE, WE ARE
 UNDER THE 99NEC.FYI, THE NEXT NEC AFTER
 THAT WOULD BE 2002.
  
  
 2)NOTE: PLEASE CLARIFY LOADS BEING BEING
 ADDED AND EXISTING LOADS. PLEASE NOTE
 A LOAD CALCULATION IS REQ`D FOR LOADS
 BEING ADDED DUE TO AGE OF PANELS AND/OR
 SERVICE IN EXISTING BLDG.215-5
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-08-06 Cont ID  
Sent By nmccray Date 2003-08-06 Time 15:36 Rev Time 0.00
Received By nmccray Date 2003-08-06 Time 15:36 Sent To  
Notes
2003-08-06 00:00:00REVISION DATED 8-01-03 OK

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-02-28 Cont ID  
Sent By dpalmer Date 2003-08-04 Time 14:56 Rev Time 0.00
Received By mcarsill Date 2003-02-28 Time 09:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-01-16 Cont ID  
Sent By mcarsill Date 2003-01-16 Time 17:10 Rev Time 0.00
Received By mcarsill Date 2003-01-16 Time 17:10 Sent To  
Notes
2003-01-16 00:00:001) THE INSTALLATION OF ANY NEW FLOORING
 SHALL NOT INTERFERE WITH ANY EXIT ACCESS
 OR EXIT DISCHARGE FROM THE INTERIOR OF
 THE STORE.
  
 2) NEW DROPPED SOFFITS SHALL NOT
 INTERFERE WITH THE OPERATION OF ANY
 EXISTING FIRE SPRINKLER HEADS.
  
 3) PLEASE INDICATE STRENGTH REQUIREMENTS
 OF GUARDRAIL ASSEMBLY SHOWN ON A206.
  
 4) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR NEW CEILING PANELS
 AND OR GRID.
  
 5) ALL EXISTING ILLUMINATED EXIT SIGNS
 OR EMERGENCY LIGHTING EQUIPMENT ARE TO
 REMAIN OPERATIONAL DURING RENOVATION
 ACTIVITIES.
  
 6) PROVIDE SEPARATE PLANS AND PERMIT
 FOR FIRE SPRINKLER REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-08-01 Cont ID  
Sent By alange Date 2003-08-01 Time 11:46 Rev Time 0.00
Received By alange Date 2003-08-01 Time 11:46 Sent To E
Notes
2003-08-01 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-17 Cont ID  
Sent By shernand Date 2003-07-17 Time 15:41 Rev Time 0.00
Received By shernand Date 2003-07-17 Time 15:41 Sent To E
Notes
2003-07-17 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-20 Cont ID  
Sent By dpalmer Date 2003-02-20 Time 06:32 Rev Time 0.00
Received By dpalmer Date 2003-02-20 Time 06:32 Sent To  
Notes
2003-03-05 00:00:00TO COMM BOARD #45

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-03-17 Cont ID  
Sent By pkrauss Date 2003-03-17 Time 14:44 Rev Time 0.25
Received By pkrauss Date 2003-03-17 Time 14:40 Sent To  
Notes
2003-03-17 00:00:00PLANS APPROVED 1-17-03,PLANS RESUBMITTED
 WITH ORIGINAL PLANS STAMPED - NO
 REPLACEMENT SHEETS SUBMITTED FOR MECH.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-01-17 Cont ID  
Sent By pkrauss Date 2003-01-17 Time 16:13 Rev Time 1.10
Received By pkrauss Date 2003-01-17 Time 16:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-03-06 Cont ID  
Sent By kstevens Date 2003-03-06 Time 13:20 Rev Time 0.50
Received By kstevens Date 2003-03-06 Time 13:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-01-21 Cont ID  
Sent By kstevens Date 2003-01-21 Time 09:15 Rev Time 0.80
Received By kstevens Date 2003-01-21 Time 09:15 Sent To  
Notes
2003-01-21 00:00:00 
 DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) PLEASE PROVIDE A SANITARY RISER DIA-
 GRAM AND A WATER RISER DIAGRAM. SECTION
 104.2 AND SECTION 104.3.1.1
 2) SHT P-1 WATER HEATER DETAIL AND NOTE
 BY W/HEATER ON FLOOR PLAN, FLOOR DRAINS
 ARE NOT AN APPROVED INDIRECT WASTE REC-
 EPTOR. PLEASE PROVIDE A FLOOR SINK FOR
 RELIEF VALVE OR DRAIN INTO MOP SINK WITH
 AN AIR GAP.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377