| Plan Review Stops For Permit 03010378 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2003-03-18 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2003-03-18 |
Time |
10:44 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2003-03-18 |
Time |
10:44 |
Sent To |
|
|
| Notes |
| 2003-03-18 00:00:00 | | | | | | | *** ISSUED PERMIT*** | | | -PLAN REVIEW HISTORY- | | | | | | PERMIT# 03020378 | | | ADDRESS: 1801 PALM BCH LAKES BLVD | | | "SEARS" | | | CONT: TO BE DETERMINED | | | TELL # (561)------ | | | | | | THE ATTACHED COMMENTS ARE PART OF THE | | | PERMIT AND PLAN REVIEW PACKAGE AND ARE | | | NOT TO BE REMOVED FROM THE ISSUED SET OF | | | PLANS.104.2.1.2 ADMINISTRATIVE CODE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-01-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2003-01-27 |
Time |
10:43 |
Rev Time |
1.55 |
| Received By |
jwitmer |
Date |
2003-01-27 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2003-01-27 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 03010378 | | | ADD: 1801 PALM BEACH LAKESBLVD | | | CONT: PLAN REVIEW | | | SIMON PROPERTIES/ | | | MARCY ESPOSITO | | | TEL: (954)931-0442 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1) A206 DETAIL# 4 INDICATES STUD BRACING | | | TO THE STRUCTURE ABOVE, NO INFORMATION | | | AS TO WHAT TYPE OF FASTENER TO THE STRUC | | | TURE ABOVE? | | | | | | 2) A206 DETAIL # 10 GLASS GUARDRAIL | | | SYSTEM: PLEASE PROVIDE MANUFACTURES SPEC | | | ON THE GLASS PANEL SYSTEM AND FASTENING | | | TO THE STRUCTURE TO MEET THE REQUIREMENT | | | OF 1608.2.2GUAEDRAIL SYSTEM DESIGN AND | | | CONSRUCTION, | | | 2405.5 GLASS BALISTER PANELS/ RAILING | | | | | | 3) A302 DETAIL# 3, CEILING SOFFIT DETAIL | | | THIS SEEMS TO BE THE ONLY DETAIL TO BE | | | USED FOR ALL SOFFITS, PLEASE PROVIDE | | | THE STUD SPACING C/C, MISSING INFO FOR | | | THE ATTACHMENT TO THE STRUCTURE ABOVE? | | | | | | 4) A 201/ A 202 IN THE HANDICAPPED FIT- | | | TING ROOMS ARE THESE BENCHES SELF SUP- | | | PORTING? OR ARE BACKING REQUIREMENTS | | | NEEDED? | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2003-08-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-08-04 |
Time |
14:56 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-08-04 |
Time |
14:56 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2003-07-23 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2003-08-01 |
Time |
11:46 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-07-23 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2003-07-23 00:00:00 | *********** UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE ATTACHED COPY OF FAC | | | 61G15-23.002 | | | PLEASE SEE MISSING INFORMATION ON TITLE | | | BLOCK. AUTH #, ENG'S #`S ETC. | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. | | | IF THERE ARE NAY QUESTIONS, PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2003-03-05 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-17 |
Time |
15:41 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2003-03-05 |
Time |
06:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-01-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-01-24 |
Time |
14:17 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-01-24 |
Time |
14:05 |
Sent To |
|
|
| Notes |
| 2003-01-24 00:00:00 | ************ UNSAT ************** | | | | | | 1)NOTE: PLANS ARE SHOWING ALL WORK TO BE | | | UNDER 2000 NEC. PLEASE NOTE, WE ARE | | | UNDER THE 99NEC.FYI, THE NEXT NEC AFTER | | | THAT WOULD BE 2002. | | | | | | | | | 2)NOTE: PLEASE CLARIFY LOADS BEING BEING | | | ADDED AND EXISTING LOADS. PLEASE NOTE | | | A LOAD CALCULATION IS REQ`D FOR LOADS | | | BEING ADDED DUE TO AGE OF PANELS AND/OR | | | SERVICE IN EXISTING BLDG.215-5 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2003-08-06 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-08-06 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-08-06 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2003-08-06 00:00:00 | REVISION DATED 8-01-03 OK |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2003-02-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-08-04 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-02-28 |
Time |
09:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2003-01-16 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-01-16 |
Time |
17:10 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-01-16 |
Time |
17:10 |
Sent To |
|
|
| Notes |
| 2003-01-16 00:00:00 | 1) THE INSTALLATION OF ANY NEW FLOORING | | | SHALL NOT INTERFERE WITH ANY EXIT ACCESS | | | OR EXIT DISCHARGE FROM THE INTERIOR OF | | | THE STORE. | | | | | | 2) NEW DROPPED SOFFITS SHALL NOT | | | INTERFERE WITH THE OPERATION OF ANY | | | EXISTING FIRE SPRINKLER HEADS. | | | | | | 3) PLEASE INDICATE STRENGTH REQUIREMENTS | | | OF GUARDRAIL ASSEMBLY SHOWN ON A206. | | | | | | 4) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR NEW CEILING PANELS | | | AND OR GRID. | | | | | | 5) ALL EXISTING ILLUMINATED EXIT SIGNS | | | OR EMERGENCY LIGHTING EQUIPMENT ARE TO | | | REMAIN OPERATIONAL DURING RENOVATION | | | ACTIVITIES. | | | | | | 6) PROVIDE SEPARATE PLANS AND PERMIT | | | FOR FIRE SPRINKLER REMODEL. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-08-01 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2003-08-01 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2003-08-01 |
Time |
11:46 |
Sent To |
E |
|
| Notes |
| 2003-08-01 00:00:00 | TO DP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-07-17 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-17 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-07-17 |
Time |
15:41 |
Sent To |
E |
|
| Notes |
| 2003-07-17 00:00:00 | DP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-02-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-20 |
Time |
06:32 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2003-02-20 |
Time |
06:32 |
Sent To |
|
|
| Notes |
| 2003-03-05 00:00:00 | TO COMM BOARD #45 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2003-03-17 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-03-17 |
Time |
14:44 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2003-03-17 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2003-03-17 00:00:00 | PLANS APPROVED 1-17-03,PLANS RESUBMITTED | | | WITH ORIGINAL PLANS STAMPED - NO | | | REPLACEMENT SHEETS SUBMITTED FOR MECH. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2003-01-17 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-01-17 |
Time |
16:13 |
Rev Time |
1.10 |
| Received By |
pkrauss |
Date |
2003-01-17 |
Time |
16:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2003-03-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-03-06 |
Time |
13:20 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-03-06 |
Time |
13:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-01-21 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-01-21 |
Time |
09:15 |
Rev Time |
0.80 |
| Received By |
kstevens |
Date |
2003-01-21 |
Time |
09:15 |
Sent To |
|
|
| Notes |
| 2003-01-21 00:00:00 | | | | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) PLEASE PROVIDE A SANITARY RISER DIA- | | | GRAM AND A WATER RISER DIAGRAM. SECTION | | | 104.2 AND SECTION 104.3.1.1 | | | 2) SHT P-1 WATER HEATER DETAIL AND NOTE | | | BY W/HEATER ON FLOOR PLAN, FLOOR DRAINS | | | ARE NOT AN APPROVED INDIRECT WASTE REC- | | | EPTOR. PLEASE PROVIDE A FLOOR SINK FOR | | | RELIEF VALVE OR DRAIN INTO MOP SINK WITH | | | AN AIR GAP. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|