Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-08-04 Cont ID  
Sent By jgomez Date 2003-08-04 Time 10:43 Rev Time 0.25
Received By jgomez Date 2003-08-04 Time 10:43 Sent To PC
Notes
2003-08-04 00:00:00ENERGY CALCULATIONS SIGNED BY OWNER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-07-23 Cont ID  
Sent By jgomez Date 2003-07-23 Time 16:23 Rev Time 3.00
Received By jgomez Date 2003-07-23 Time 16:22 Sent To PC
Notes
2003-07-23 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-RESUBMIT PRODUCT APPROVAL FOR SINGLE
 HUNG IMPACT RESISTANT WINDOWS. NEED
 DRAWINGS TO BE LEGIBLE.
 2-PROVIDE COMPLETE SHOP DRAWINGS FOR
 ALL GUARDRAIL AND HANDRAIL WORK
 SHOWING COMPLIANCE WITH SECTIONS
 1015.3, 1608.2, 1007.5 FBC 2001.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-06-03 Cont ID  
Sent By kstevens Date 2003-07-18 Time 11:19 Rev Time 3.50
Received By jgomez Date 2003-06-03 Time 17:09 Sent To  
Notes
2003-06-03 00:00:00BUILDING REVIEW CHECKLIST:
 1-SOME DRAWINGS ARE MISSING EMBOSSED
 ARCHITECT'S SEAL AS REQ'D BY CHAPTER
 481 FLORIDA STATUTES WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
 2-ENERGY CALCULATIONS ARE NOT INCLUDED
 IN THE PACKAGE. RESUBMIT.
 3-PROVIDE SOIL TEST REPORT W/ ENGINEER'S
 ORIGINAL, SEAL SIGNATURE AND DATE AS
 REQ'DBY CHAPTER 471 WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
 4-ALUMIMUM GUARDRAIL SYSTEM PACKAGE:
 A)IT DOESN'T SHOW COMPLIANCE WITH FBC
 2001 SECTIONS 1015.3 AND 1608.2. (SEE
 OPENINGS REQUIREMENTS, INCLUDING AT
 BOTTOM RAIL AND LOAD DESIGN)
 B)ARCHITECT/ENGINEER OF RECORD TO REVIEW
 AND APPROVE (USE REVIEW STAMP) ALL
 SHOP DRAWINGS PRIOR TO SUBMITTAL TO
 THIS OFFICE.
 C)SAME APPLIES TO INTERIOR STAIRS.
 5-PROVIDE 2 COPIES OF PRODUCT APPROVALS
 FOR DOORS AND WINDOWS ASSEMBLIES WITH
 TRANSOM OR SIDELITES AS SHOWN ON PLANS
 **NOTE: MISSILE IMPACT ASSEMBLIES AS
 SPECIFIED ON PLANS.
 6-PROVIDE 2 COPIES OF PRODUCT APPROVALS
 FOR STRUCTURAL MULLIONS (IMPACT).
 7-PROVIDE 2 COPIES OF PRODUCT APPROVALS
 FOR ROOF TILE.
 **NOTE: OWNER HAS THE OPTION TO PROVIDE
 PRODUCT APPROVAL INFO. AT A LATER TIME
 BUT UNDER SEPARATE PERMIT AND FEES AND
 PRIOR TO INSTALLATION.
 8-UPDATE TRUSS ANCHOR SCHEDULE & DETAILS
 THAT ARE AFFECTED BY SEC. 1609.4.3
 FBC 2001 WHERE THE 33% ALLOWABLE
 STRESS INCREASE IS NOT PERMITTED. SEE
 REVISED CONNECTOR'S CATALOGUE AND
 REVISE AS REQUIRED.
 9-OWES $385.55 FOR UPDATED VALUATION AND
 RADON FEES. PLEASE PAY ATTACHED
 RECEIPT #225825.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-03-27 Cont ID  
Sent By kstevens Date 2003-05-31 Time 08:15 Rev Time 3.50
Received By jgomez Date 2003-03-27 Time 10:45 Sent To  
Notes
2003-03-27 00:00:00BUILDING REVIEW CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY
 BRING BACK STAMPED DRAWINGS AND PAID
 RECEIPT.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-PROVIDE SOIL TEST REPORT.
 4-PROVIDE ALL INFORMATION (5 ITEMS ) AS
 REQUESTED ON SEC. 1606.1.7 FBC 2001.
 INCLUDING INTERNAL DESIGN PRESSURES
 AND COMPONENTS AND CLADDING.
 5-ALL DRAWINGS THAT ARE REPLACED NEED TO
 BE RE-STAMPED BY HISTORICAL PRIOR TO
 SUBMITTAL TO THIS OFFICE.
 NOTE: ONLY TWO SETS OF DRAWINGS ARE
 REQUIRED, NOT THREE.
 6-PROVIDE COMPLETE GUARDRAIL & HANDRAILS
 DETAILS. SEE SEC. 1608.2 FOR DESIGN
 CRITERIA. ALSO, SEE SEC. 1007.5 AND
 SEC. 1015 FBC 2001.
 7-CLARIFY AREA TABULATION ON SHEET A-4:
 CLEARLY IDENTIFY GARAGE AREA AND
 VESTIBULE GROUND FLOOR AREA. CLARIFY
 WHAT'S VESTIBULE GROUND FLOOR AREA?
 INCLUDE THIS AREA ON ENTRY HALL AND
 CLOSET AREA.
 8-PROVIDE COMPLETE DETAIL FOR 2X BUCK
 DETAIL. SEE SEC. 1707.4.4.2 FBC 2001
 FOR APPROPRIATE INSTALLATION OF 2X
 STRUCTURAL BUCK TO SUBSTRATE.
 9-PROVIDE 2 COPIES OF PRODUCT APPROVALS
 FOR DOORS AND WINDOWS ASSEMBLIES WITH
 TRANSOM ABOVE OR SIDELITES AS SINGLE
 ASSEMBLIES AS SHOWN ON PLANS.
 10-PROVIDE 2 COPIES OF PRODUCT APPROVALS
 FOR STRUCTURAL DOOR & WINDOW MULLIONS
 11-PROVIDE 2 COPIES OF PRODUCT APPROVAL
 FOR ROOF TILE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-07-16 Cont ID  
Sent By btrobaug Date 2003-07-16 Time 14:52 Rev Time 0.50
Received By btrobaug Date 2003-07-16 Time 14:11 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-05-29 Cont ID  
Sent By shernand Date 2003-07-14 Time 09:55 Rev Time 0.75
Received By btrobaug Date 2003-05-28 Time 17:39 Sent To P
Notes
2003-05-29 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE NECESSARY CHANGES FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATED AND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
  
 2} PLEASE SEE ARTICLE 230-70 WEST PALM
 BEACH AMMENDMENTS,TO DETERMINE IF A
 DISCONNECT IS REQUIRED AT THE METER.
  
 3} THE GROUNDING ELECTRODE CONDUCTOR
 FROM PANEL "B" TO GROUND PARALLELS THE
 GROUNDED NEUTRAL AND MAY NOT BE
 INSTALLED.
  
 4} THE FEED FROM PANEL "C" TO "B" IS
 SHOWN AS #3/0 ON THE RISER & #1/0 ON
 THE PANEL SCHEDULE. PLEASE CLARIFY.
  
 5} PLEASE NOTE THAT CKT. BREAKERS #41 &
 42 APPEAR TO HAVE THE GRONDING CONDUCTOR
 ATTACHED TO THEM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-03-19 Cont ID  
Sent By shernand Date 2003-05-23 Time 16:50 Rev Time 0.75
Received By dpalmer Date 2003-03-19 Time 06:04 Sent To P
Notes
2003-03-19 00:00:00************ UNSAT ******************
  
 PLANS NEED TO PLACED INTO TWO SETS FOR
 REVIEW AND STAMPING.
  
 1)NOTE: PLEASE SHOW GARAGE RECEPTS AS
 GFI. 210-8
  
 2)NOTE: PLEASE SHOW MAIN GROUNDING
 ELECTRODE CONDUCTOR TO FOOTER STEEL AS
 1/0. PLEASE NOTE, SHOWN TO SUPPLEMENTAL
 AND THEN A #6 TO FOOTER STEEL. PLEASE
 CHANGE.
 250-50
  
 3)NOTE: PLEASE CLARIFY TWO SD`S SHOWN
 IN GARAGE W/IN ABOUT 4' OF EACH OTHER??
  
 4)NOTE: PLEASE SEE MISSING SD INSIDE
 BEDROOM. PER NFPA-72 8-1.4.2
  
 5)NOTE: PLEASE SEE MISSING CONTROL OF
 EGRESS LIGHTING LEAVING FIRST FLOOR
 ENTRY TO REAR STOOP, AND ALSO 2ND FLR
 LEAVING TO BRIDGE AREA. 210-70
  
 6)NOTE: PLEASE SUBMIT A PANEL SCHEDULE
 FOR ALL NEW CIRCUITING. PLEASE SUBMIT
 LOAD CALCULATIONS W/ NEW AND EXISTING
 LOADS. PLEASE SHOW OCP AND WIRE SIZES IN
 PANEL.
  
 7)NOTE: PLEASE LIST THE REQ`D DEDICATED
 BATH CIRCUIT(S) AS #12/20 210-52D/210-11
 -C-3.
  
 8)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 CIRCUITS PER 210-12
  
 9)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN PANEL
 AND SUB-PANEL. SIZE PER 250-122
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-07-14 Cont ID  
Sent By shernand Date 2003-07-14 Time 09:55 Rev Time 0.00
Received By shernand Date 2003-07-14 Time 09:55 Sent To E
Notes
2003-07-14 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-05-23 Cont ID  
Sent By shernand Date 2003-05-23 Time 16:50 Rev Time 0.00
Received By shernand Date 2003-05-23 Time 16:50 Sent To E
Notes
2003-05-23 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-03-13 Cont ID  
Sent By sthyng Date 2003-03-13 Time 08:41 Rev Time 0.00
Received By sthyng Date 2003-03-13 Time 08:41 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-02-26 Cont ID  
Sent By dpalmer Date 2003-02-26 Time 10:07 Rev Time 0.00
Received By dpalmer Date 2003-02-26 Time 10:07 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-27 Cont ID  
Sent By dpalmer Date 2003-01-27 Time 11:22 Rev Time 0.00
Received By dpalmer Date 2003-01-27 Time 11:22 Sent To Z
Notes
2003-01-27 00:00:00SUBMITTAL OF SURVEY.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-09 Cont ID  
Sent By dpalmer Date 2003-01-09 Time 11:55 Rev Time 0.00
Received By dpalmer Date 2003-01-09 Time 11:55 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-03-26 Cont ID  
Sent By kstevens Date 2003-03-24 Time 05:43 Rev Time 0.35
Received By pkrauss Date 2003-03-26 Time 11:36 Sent To B
Notes
2003-03-26 00:00:00PROVISO:
  
 AHU #1 & 2, SHALL COMPLY WITH 2001 FBC,
 (MECH) 306.3, THE CLEAR ACCESS OPENING
 DIMENSIONS SHALL BE A MINIMUM OF 20" X
 30".
  
 AHU #1 & 2 SHALL ALSO COMPLY WITH 2001
 FBC CHAPTER 13 SECTION 610.1.ABC.3.5.2.
  
 PROVIDE FLOAT SWITCH OR SECONDARY DRAIN
 LINE TERMINATING AT A CONSPICUOUS POINT
 REQUIRED ON THE AUXILIARY DRAIN PANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-07-18 Cont ID  
Sent By kstevens Date 2003-07-18 Time 11:18 Rev Time 0.50
Received By kstevens Date 2003-07-18 Time 11:18 Sent To B
Notes
2003-07-18 00:00:00NO RISER DIAGRAM SUBMITTED - PLAN VEIW
 ONLY

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-05-31 Cont ID  
Sent By btrobaug Date 2003-07-16 Time 14:52 Rev Time 0.25
Received By kstevens Date 2003-05-31 Time 08:14 Sent To B
Notes
2003-05-31 00:00:00DENIED
 REFERENCE: FLORIDA STATUTES
  
 1) THE PERSONAL SEAL, SIGNATURE, (NOT A
 COPY), AND DATE OF THE ARCHTIECT OR IN-
 TERIOR DESIGNER SHALL APPEAR ON ALL
 ARCHITECTURAL OR INTERIOR DESIGN DOCU-
 MENTS TO BE FILED FOR PUBLIC RECORD.
 61G1-16.003
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-03-24 Cont ID  
Sent By btrobaug Date 2003-05-29 Time 07:06 Rev Time 0.75
Received By kstevens Date 2003-03-22 Time 17:04 Sent To M
Notes
2003-03-24 00:00:00DENIED
  
 PLUMBING OK - PLEASE SUBMIT A MINIMUM OF
 2 COMPLETE SETS OF PLANS FOR REVIEW AND
 STAMPING
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 3 Status P Date 2003-03-04 Cont ID  
Sent By sgraham Date 2003-03-04 Time 14:08 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2003-01-30 Cont ID  
Sent By dpalmer Date 2003-02-26 Time 10:07 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-01-30 00:00:00DENIED BY ZONING 2ND CHECKLIST
 1. DOORS #2 & #4 MUST BE REMOVED

Review Stop Z ZONING
Rev No 1 Status F Date 2003-01-16 Cont ID  
Sent By dpalmer Date 2003-01-27 Time 11:22 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-01-16 00:00:00DENIED BY ZONING,DOOR #2 & #4 MUST BE
 REMOVED