| Plan Review Stops For Permit 03010347 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2003-08-04 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2003-08-04 |
Time |
10:43 |
Rev Time |
0.25 |
| Received By |
jgomez |
Date |
2003-08-04 |
Time |
10:43 |
Sent To |
PC |
|
| Notes |
| 2003-08-04 00:00:00 | ENERGY CALCULATIONS SIGNED BY OWNER. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2003-07-23 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2003-07-23 |
Time |
16:23 |
Rev Time |
3.00 |
| Received By |
jgomez |
Date |
2003-07-23 |
Time |
16:22 |
Sent To |
PC |
|
| Notes |
| 2003-07-23 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-RESUBMIT PRODUCT APPROVAL FOR SINGLE | | | HUNG IMPACT RESISTANT WINDOWS. NEED | | | DRAWINGS TO BE LEGIBLE. | | | 2-PROVIDE COMPLETE SHOP DRAWINGS FOR | | | ALL GUARDRAIL AND HANDRAIL WORK | | | SHOWING COMPLIANCE WITH SECTIONS | | | 1015.3, 1608.2, 1007.5 FBC 2001. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2003-06-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-07-18 |
Time |
11:19 |
Rev Time |
3.50 |
| Received By |
jgomez |
Date |
2003-06-03 |
Time |
17:09 |
Sent To |
|
|
| Notes |
| 2003-06-03 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1-SOME DRAWINGS ARE MISSING EMBOSSED | | | ARCHITECT'S SEAL AS REQ'D BY CHAPTER | | | 481 FLORIDA STATUTES WHEN SUBMITTING | | | DOCUMENTS FOR PUBLIC RECORDS. | | | 2-ENERGY CALCULATIONS ARE NOT INCLUDED | | | IN THE PACKAGE. RESUBMIT. | | | 3-PROVIDE SOIL TEST REPORT W/ ENGINEER'S | | | ORIGINAL, SEAL SIGNATURE AND DATE AS | | | REQ'DBY CHAPTER 471 WHEN SUBMITTING | | | DOCUMENTS FOR PUBLIC RECORDS. | | | 4-ALUMIMUM GUARDRAIL SYSTEM PACKAGE: | | | A)IT DOESN'T SHOW COMPLIANCE WITH FBC | | | 2001 SECTIONS 1015.3 AND 1608.2. (SEE | | | OPENINGS REQUIREMENTS, INCLUDING AT | | | BOTTOM RAIL AND LOAD DESIGN) | | | B)ARCHITECT/ENGINEER OF RECORD TO REVIEW | | | AND APPROVE (USE REVIEW STAMP) ALL | | | SHOP DRAWINGS PRIOR TO SUBMITTAL TO | | | THIS OFFICE. | | | C)SAME APPLIES TO INTERIOR STAIRS. | | | 5-PROVIDE 2 COPIES OF PRODUCT APPROVALS | | | FOR DOORS AND WINDOWS ASSEMBLIES WITH | | | TRANSOM OR SIDELITES AS SHOWN ON PLANS | | | **NOTE: MISSILE IMPACT ASSEMBLIES AS | | | SPECIFIED ON PLANS. | | | 6-PROVIDE 2 COPIES OF PRODUCT APPROVALS | | | FOR STRUCTURAL MULLIONS (IMPACT). | | | 7-PROVIDE 2 COPIES OF PRODUCT APPROVALS | | | FOR ROOF TILE. | | | **NOTE: OWNER HAS THE OPTION TO PROVIDE | | | PRODUCT APPROVAL INFO. AT A LATER TIME | | | BUT UNDER SEPARATE PERMIT AND FEES AND | | | PRIOR TO INSTALLATION. | | | 8-UPDATE TRUSS ANCHOR SCHEDULE & DETAILS | | | THAT ARE AFFECTED BY SEC. 1609.4.3 | | | FBC 2001 WHERE THE 33% ALLOWABLE | | | STRESS INCREASE IS NOT PERMITTED. SEE | | | REVISED CONNECTOR'S CATALOGUE AND | | | REVISE AS REQUIRED. | | | 9-OWES $385.55 FOR UPDATED VALUATION AND | | | RADON FEES. PLEASE PAY ATTACHED | | | RECEIPT #225825. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-03-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-05-31 |
Time |
08:15 |
Rev Time |
3.50 |
| Received By |
jgomez |
Date |
2003-03-27 |
Time |
10:45 |
Sent To |
|
|
| Notes |
| 2003-03-27 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1-PAY IMPACT FEES TO PALM BEACH COUNTY | | | BRING BACK STAMPED DRAWINGS AND PAID | | | RECEIPT. | | | 2-NEED RECORDED NOTICE OF COMMENCEMENT. | | | 3-PROVIDE SOIL TEST REPORT. | | | 4-PROVIDE ALL INFORMATION (5 ITEMS ) AS | | | REQUESTED ON SEC. 1606.1.7 FBC 2001. | | | INCLUDING INTERNAL DESIGN PRESSURES | | | AND COMPONENTS AND CLADDING. | | | 5-ALL DRAWINGS THAT ARE REPLACED NEED TO | | | BE RE-STAMPED BY HISTORICAL PRIOR TO | | | SUBMITTAL TO THIS OFFICE. | | | NOTE: ONLY TWO SETS OF DRAWINGS ARE | | | REQUIRED, NOT THREE. | | | 6-PROVIDE COMPLETE GUARDRAIL & HANDRAILS | | | DETAILS. SEE SEC. 1608.2 FOR DESIGN | | | CRITERIA. ALSO, SEE SEC. 1007.5 AND | | | SEC. 1015 FBC 2001. | | | 7-CLARIFY AREA TABULATION ON SHEET A-4: | | | CLEARLY IDENTIFY GARAGE AREA AND | | | VESTIBULE GROUND FLOOR AREA. CLARIFY | | | WHAT'S VESTIBULE GROUND FLOOR AREA? | | | INCLUDE THIS AREA ON ENTRY HALL AND | | | CLOSET AREA. | | | 8-PROVIDE COMPLETE DETAIL FOR 2X BUCK | | | DETAIL. SEE SEC. 1707.4.4.2 FBC 2001 | | | FOR APPROPRIATE INSTALLATION OF 2X | | | STRUCTURAL BUCK TO SUBSTRATE. | | | 9-PROVIDE 2 COPIES OF PRODUCT APPROVALS | | | FOR DOORS AND WINDOWS ASSEMBLIES WITH | | | TRANSOM ABOVE OR SIDELITES AS SINGLE | | | ASSEMBLIES AS SHOWN ON PLANS. | | | 10-PROVIDE 2 COPIES OF PRODUCT APPROVALS | | | FOR STRUCTURAL DOOR & WINDOW MULLIONS | | | 11-PROVIDE 2 COPIES OF PRODUCT APPROVAL | | | FOR ROOF TILE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2003-07-16 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-07-16 |
Time |
14:52 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2003-07-16 |
Time |
14:11 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2003-05-29 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-14 |
Time |
09:55 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2003-05-28 |
Time |
17:39 |
Sent To |
P |
|
| Notes |
| 2003-05-29 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE NECESSARY CHANGES FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE NOTE THAT ALL PLANS | | | DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- | | | ING A TITLE BLOCK, MUST BE SIGNED, | | | DATED AND SEALED BY THE ARCH/ENGINEER OF | | | RECORD. PER FS/FAC 481.221 & 471.025 | | | | | | 2} PLEASE SEE ARTICLE 230-70 WEST PALM | | | BEACH AMMENDMENTS,TO DETERMINE IF A | | | DISCONNECT IS REQUIRED AT THE METER. | | | | | | 3} THE GROUNDING ELECTRODE CONDUCTOR | | | FROM PANEL "B" TO GROUND PARALLELS THE | | | GROUNDED NEUTRAL AND MAY NOT BE | | | INSTALLED. | | | | | | 4} THE FEED FROM PANEL "C" TO "B" IS | | | SHOWN AS #3/0 ON THE RISER & #1/0 ON | | | THE PANEL SCHEDULE. PLEASE CLARIFY. | | | | | | 5} PLEASE NOTE THAT CKT. BREAKERS #41 & | | | 42 APPEAR TO HAVE THE GRONDING CONDUCTOR | | | ATTACHED TO THEM. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-03-19 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-23 |
Time |
16:50 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2003-03-19 |
Time |
06:04 |
Sent To |
P |
|
| Notes |
| 2003-03-19 00:00:00 | ************ UNSAT ****************** | | | | | | PLANS NEED TO PLACED INTO TWO SETS FOR | | | REVIEW AND STAMPING. | | | | | | 1)NOTE: PLEASE SHOW GARAGE RECEPTS AS | | | GFI. 210-8 | | | | | | 2)NOTE: PLEASE SHOW MAIN GROUNDING | | | ELECTRODE CONDUCTOR TO FOOTER STEEL AS | | | 1/0. PLEASE NOTE, SHOWN TO SUPPLEMENTAL | | | AND THEN A #6 TO FOOTER STEEL. PLEASE | | | CHANGE. | | | 250-50 | | | | | | 3)NOTE: PLEASE CLARIFY TWO SD`S SHOWN | | | IN GARAGE W/IN ABOUT 4' OF EACH OTHER?? | | | | | | 4)NOTE: PLEASE SEE MISSING SD INSIDE | | | BEDROOM. PER NFPA-72 8-1.4.2 | | | | | | 5)NOTE: PLEASE SEE MISSING CONTROL OF | | | EGRESS LIGHTING LEAVING FIRST FLOOR | | | ENTRY TO REAR STOOP, AND ALSO 2ND FLR | | | LEAVING TO BRIDGE AREA. 210-70 | | | | | | 6)NOTE: PLEASE SUBMIT A PANEL SCHEDULE | | | FOR ALL NEW CIRCUITING. PLEASE SUBMIT | | | LOAD CALCULATIONS W/ NEW AND EXISTING | | | LOADS. PLEASE SHOW OCP AND WIRE SIZES IN | | | PANEL. | | | | | | 7)NOTE: PLEASE LIST THE REQ`D DEDICATED | | | BATH CIRCUIT(S) AS #12/20 210-52D/210-11 | | | -C-3. | | | | | | 8)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | CIRCUITS PER 210-12 | | | | | | 9)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR BETWEEN MAIN PANEL | | | AND SUB-PANEL. SIZE PER 250-122 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2003-07-14 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-14 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-07-14 |
Time |
09:55 |
Sent To |
E |
|
| Notes |
| 2003-07-14 00:00:00 | BT DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2003-05-23 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-23 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-05-23 |
Time |
16:50 |
Sent To |
E |
|
| Notes |
| 2003-05-23 00:00:00 | BT DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2003-03-13 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-13 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-13 |
Time |
08:41 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-02-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-26 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2003-02-26 |
Time |
10:07 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-01-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-01-27 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2003-01-27 |
Time |
11:22 |
Sent To |
Z |
|
| Notes |
| 2003-01-27 00:00:00 | SUBMITTAL OF SURVEY. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-01-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-01-09 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2003-01-09 |
Time |
11:55 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2003-03-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-03-24 |
Time |
05:43 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2003-03-26 |
Time |
11:36 |
Sent To |
B |
|
| Notes |
| 2003-03-26 00:00:00 | PROVISO: | | | | | | AHU #1 & 2, SHALL COMPLY WITH 2001 FBC, | | | (MECH) 306.3, THE CLEAR ACCESS OPENING | | | DIMENSIONS SHALL BE A MINIMUM OF 20" X | | | 30". | | | | | | AHU #1 & 2 SHALL ALSO COMPLY WITH 2001 | | | FBC CHAPTER 13 SECTION 610.1.ABC.3.5.2. | | | | | | PROVIDE FLOAT SWITCH OR SECONDARY DRAIN | | | LINE TERMINATING AT A CONSPICUOUS POINT | | | REQUIRED ON THE AUXILIARY DRAIN PANS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2003-07-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-07-18 |
Time |
11:18 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-07-18 |
Time |
11:18 |
Sent To |
B |
|
| Notes |
| 2003-07-18 00:00:00 | NO RISER DIAGRAM SUBMITTED - PLAN VEIW | | | ONLY |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2003-05-31 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-07-16 |
Time |
14:52 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2003-05-31 |
Time |
08:14 |
Sent To |
B |
|
| Notes |
| 2003-05-31 00:00:00 | DENIED | | | REFERENCE: FLORIDA STATUTES | | | | | | 1) THE PERSONAL SEAL, SIGNATURE, (NOT A | | | COPY), AND DATE OF THE ARCHTIECT OR IN- | | | TERIOR DESIGNER SHALL APPEAR ON ALL | | | ARCHITECTURAL OR INTERIOR DESIGN DOCU- | | | MENTS TO BE FILED FOR PUBLIC RECORD. | | | 61G1-16.003 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-03-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-05-29 |
Time |
07:06 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2003-03-22 |
Time |
17:04 |
Sent To |
M |
|
| Notes |
| 2003-03-24 00:00:00 | DENIED | | | | | | PLUMBING OK - PLEASE SUBMIT A MINIMUM OF | | | 2 COMPLETE SETS OF PLANS FOR REVIEW AND | | | STAMPING | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2003-03-04 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2003-03-04 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2003-01-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-26 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2003-01-30 00:00:00 | DENIED BY ZONING 2ND CHECKLIST | | | 1. DOORS #2 & #4 MUST BE REMOVED |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2003-01-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-01-27 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2003-01-16 00:00:00 | DENIED BY ZONING,DOOR #2 & #4 MUST BE | | | REMOVED |
|
|