| Plan Review Stops For Permit 03010215 |
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2003-10-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-10-18 |
Time |
12:09 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-10-18 |
Time |
12:09 |
Sent To |
|
|
| Notes |
| 2003-10-18 00:00:00 | REVISION OK - BBQ, FIREPLACE, & EMERG. | | | GENERATOR TO BE VALVED & CAPPED FOR | | | FURTURE USE. | | | | | | | | | | | | | | | | | | PER N. MELICK MANUFACTURE INFO | | | NOT REQUIRED FOR 1 & 2 FAMILY HOMES. | | | JULY 17, 2002 OFFICAL INTERPRETATION. | | | THE FIELD INSPECTOR SHALL VERIFY THE | | | INSTALLED EQUIPMENT INPUT DOES NOT EX- | | | CEED THE PIPE SIZING. | | | | | | IF DRYER ROOM IS A CONFINED SPACE, | | | OPENINGS REQUIRED PER SECTION 304.3.1 0R | | | SECTION 304.3.2 SHALL BE INSTALLED. | | | MINIMUM 1,100 CUBIC FEET REQUIRED. | | | | | | | | | | | | Z |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2003-01-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-01-17 |
Time |
08:18 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2003-01-17 |
Time |
08:17 |
Sent To |
|
|
| Notes |
| 2003-01-17 00:00:00 | PASSED/PROVISO | | | | | | MANUFACTURE INSTALLATION INSTRUCTION ARE | | | REQUIRED AT FINAL FOR GENERATOR. |
|
|
|