| 2003-01-29 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-AREA CALCULATIONS ARE WRONG. REVISE AS |
| | REQUIRED CALCULATIONS ON SHEET A-4. |
| | 2-REVISE DESIGN PARAMETERS CRITERIA ON |
| | SHEET A1.1. MEAN ROOF HEIGHT IS 22'-0" |
| | +/- NOT 18"-6". SEE BUILDING HEIGHT ON |
| | CHAPTER 2 DEFINITIONS OF FBC 2001. |
| | 3-DESIGN PARAMETERS CRITERIA ON SHEET |
| | A1.1 IS MISSING THE +/- INTERNAL |
| | PRESSURES AS REQUIRED BY SECTION |
| | 1606.1.7 FBC 2001. |
| | 4-REVISE SPECIFICATIONS FOR CEILING |
| | INSTALLATION AT FRONT & REAR PORCHES. |
| | SEE ASTM C-926 AND ASTM C-1063 FOR |
| | PROPER FASTENING TYPE, SIZE & SPACING. |
| | (SEC. 2504.2 FBC 2001). |
| | 5-SPECIFY SPACING FOR WWM SUPPORTS IN |
| | CONCRETE SLAB AS REQUIRED BY SECTION |
| | 1909.3 FBC 2001. |
| | 6-LIBRARY ROOM. PROVIDE EGRESS WINDOWS |
| | THAT COMPLY WITH SEC. 1005.4.4 FBC/01 |
| | OR CLEARLY SPECIFY UNDER ROOM NAME |
| | THAT SUCH ROOM IS NOT TO BE USED FOR |
| | SLEEPING PURPOSES (AS PER BUILDING |
| | OFFICIAL INTERPRETATION). |
| | 7-GLASS BLOCK IN MASTER BATHROOM TO BE |
| | SAFETY GLASS IF FACE THICKNESS IS LESS |
| | THAN 0.25". SEC. 2405.2.2 FBC 2001. |
| | 8-COMPLETE STRUCTURAL BUCK DETAIL FOR |
| | GARAGE DOOR. SPECIFY SIZE OF WASHER. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 9-REVISE 2X STRUCTURAL BUCK DETAIL FOR |
| | DOOR TO COMPLY WITH SEC. 1707.4.4.2 |
| | FBC 2001. |
| | 10-STORM SHUTTERS: A)SEE LIMITATIONS ON |
| | PAGE 8 OF 8 OF PRODUCT APPROVAL REPORT |
| | TO VERIFY IF STRUCTURE PROVIDES REQ'D |
| | STRENGTH. |
| | B)PROVIDE COMPLETE INSTALLATION SCHED. |
| | USING CITY SAMPLE ATTACHED. |
| | C)CLEARLY MARK ON DRAWINGS SPECIFIC |
| | MOUNTING CONDITIONS AND ANCHOR TYPE & |
| | SPACING TO BE USED ACCORDING TO THE |
| | MEAN ROOF HEIGHT, DESIGN PRESSURES, |
| | EDGE DISTANCE, PANEL SPAN, CONNECTION |
| | TYPE AND STRUCTURE TO BE ATTACHED TO. |
| | |
| | 11-PROVIDE PRODUCT APPROVAL FOR: |
| | A)GLASS BLOCK WITH CLEAR DRAWINGS. |
| | B)WINDOW MULLIONS. |
| | C)FIXED WINDOW SIZE AS CALLED FOR LIVING |
| | D)GARAGE DOORS: CLEARLY MARK ON DRAWINGS |
| | MODEL TO BE USED AND CHECK THE DESIGN |
| | PRESSURES CALCULATED BY THE ARCHITECT. |
| | |
| | 12-TYPICAL WALL SECTION ON SHEET AS1: |
| | REVISE ATTIC INSULATION VALUE. SEE THE |
| | ENERGY CALCULATIONS. |