Plan Review Details - Permit 02121457
Plan Review Stops For Permit 02121457
Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-10-16 Cont ID  
Sent By btrobaug Date 2003-10-16 Time 13:41 Rev Time 0.75
Received By btrobaug Date 2003-10-16 Time 13:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-09-11 Cont ID  
Sent By dpalmer Date 2003-09-11 Time 10:41 Rev Time 1.00
Received By dpalmer Date 2003-09-11 Time 10:41 Sent To  
Notes
2003-09-11 00:00:00********** NOTE ****************
  
 PLEASE SEE THE FOLLOWING IS A GIVEN
 EXPLANATION FOR SYSTEM REQUESTED TO BE
 INSTALLED AT "ESPLANADE GRANDE"
  
 1)NOTE: PLEASE SEE THAT THE PROPOSED
 LIGHTNING PROTECTION SYSTEM HAS BEEN
 RESERCHED. WE HAVE NOT BEEN ABLE TO FIND
 SUFFICIENT INFORMATION FOR THE SYSTEM TO
 BE PERMITTED TO BE INSTALLED.
 THE SYSTEM IS NOT RECOGNIZED BY NFPA 780
  
 2)NOTE: PLEASE NOTE, SYSTEM SEEMS TO
 CONTAIN ALL LISTED PRODUCTS BUT SYSTEM
 IS NOT A LISTED ASSEMBLY PER NFPA 70
  
 PLEASE NOTE, AN OPTION THAT MAY BE TAKEN
 AND WILL BE ACCEPTABLE BY THIS OFFICE,
 IS TO HAVE A UL FIELD REPRESENTIVE DO AN
 INSPECTION ON SYSTEM AND CERTIFY WITH
 FIELD STICKERS AND A FOLLOW UP LETTER
 TO KEEP AS RECORD.
  
 PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-01-07 Cont ID  
Sent By dpalmer Date 2002-12-31 Time 10:24 Rev Time 1.50
Received By btrobaug Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-31 Cont ID  
Sent By dpalmer Date 2002-12-31 Time 10:24 Rev Time 0.00
Received By dpalmer Date 2002-12-31 Time 10:24 Sent To E
Notes
2002-12-31 00:00:00ELEC INBOX