Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-04-03 Cont ID  
Sent By shernand Date 2003-04-18 Time 14:05 Rev Time 0.50
Received By jwitmer Date 2003-04-03 Time 09:39 Sent To  
Notes
2003-04-03 00:00:00REVISION DATE ON PLAN SEAL 3-18-03
 FOR NEW COVERING FOR SHELL WALLS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-03-27 Cont ID  
Sent By shernand Date 2003-04-02 Time 16:41 Rev Time 1.25
Received By jwitmer Date 2003-03-27 Time 09:31 Sent To  
Notes
2003-03-27 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02121450
 ADD: 5820 N JOG RD
 CONT: ADVANCED ROOFING
 TEL: (954)868-0063
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 REVISION: UNKNOWN
 ACTION: DENIED
  
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 REVISIONS ARE TO BE DESIGNATED WITH
 CLOUDS, DELTAS ETC...
  
 2) SHEET S-14 DESIGN CRITERIA,
 AS PER MEETING WITH THE ENGINEERS BEFORE
 THE ISSUANCE OF PLANS, PLANS WERE RED
 LINED TO RELFECT THE BUILDING DESIGN WAS
 DESIGNED TO THE 1997 SBC/ @ 110 MPH.
 TO USE THE 2001 FLORIDA BLDG CODE @ 140
 MPH THE ORIGINAL STEEL STRUCTURE WOULD
 REQUIRE CERTIFYING IT AT 140MPH, W/ AND
 IMPORTANCE FACTOR OF 1. THE ENGINEERS
 STATED THIS BUILDING WOULD NOT MAKE THE
 MORE STRIGENT WINDLOADING OF THE NEW
 CODE. THE COMPOST BUILDING CAN ASSUME AN
 IMPORTANCE FACTOR OF .77 (TABLE 1606,
 FOOTNOTE-A). 140X.77=107.8 WHICH IS
 BELOW THE 110 MPH WITHOUT CONVERTING
 FROM FASTEST 3 SECOND GUST TO FASTEST
 MILE (TABLE 1606.1.6.1), 107.8 /3 SEC
 GUST CONVERTS TO 87 MPH FASTEST MILE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-01-13 Cont ID  
Sent By sthyng Date 2003-03-19 Time 16:00 Rev Time 0.75
Received By jwitmer Date 2003-01-13 Time 13:44 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-01-06 Cont ID  
Sent By jwitmer Date 2003-01-06 Time 12:34 Rev Time 1.75
Received By jwitmer Date   Time   Sent To  
Notes
2003-01-06 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02121450
 ADD: 5820 N JOG RD
 CONT: DKG & ASSOCIATES
 TEL: (954)433-0815
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 2)FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) ROOFING ASSEMBLIES
 B) GLAZED OPENINGS (TRANSLUCENT PANELS)
 IS THIS BLDG DESIGNED AS A OPEN,
 PARTIALLY OPEN OR ENCLOSED BLDG?
 C) SKYLIGHTS (ELEC PAGES) INDICATED
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-01-07 Cont ID  
Sent By dpalmer Date 2003-01-07 Time 14:52 Rev Time 1.00
Received By dpalmer Date 2003-01-07 Time 14:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-01-14 Cont ID  
Sent By jwitmer Date 2003-01-13 Time 13:44 Rev Time 0.00
Received By mcarsill Date 2003-01-14 Time 12:51 Sent To  
Notes
2003-01-14 00:00:001) SEE LETTER TO FIRE DEPT.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-04-18 Cont ID  
Sent By shernand Date 2003-04-18 Time 14:05 Rev Time 0.00
Received By shernand Date 2003-04-18 Time 14:04 Sent To B
Notes
2003-04-18 00:00:00JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-04-02 Cont ID  
Sent By shernand Date 2003-04-02 Time 16:41 Rev Time 0.00
Received By shernand Date 2003-04-02 Time 16:40 Sent To B
Notes
2003-04-02 00:00:00JWITMER DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-19 Cont ID  
Sent By sthyng Date 2003-03-19 Time 15:59 Rev Time 0.00
Received By sthyng Date 2003-03-19 Time 15:59 Sent To B
Notes
2003-03-19 00:00:00TO JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-31 Cont ID  
Sent By dpalmer Date 2002-12-31 Time 11:39 Rev Time 0.00
Received By dpalmer Date 2002-12-31 Time 11:39 Sent To  
Notes
2002-12-31 00:00:00TO COMM BOARD #13.\\BLDG REVIEW ONLY