Plan Review Details - Permit 02121272
Plan Review Stops For Permit 02121272
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-03-07 Cont ID  
Sent By hpiskura Date 2003-03-07 Time 15:09 Rev Time 0.00
Received By hpiskura Date 2003-03-07 Time 13:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-01-28 Cont ID  
Sent By hpiskura Date 2003-01-28 Time 09:46 Rev Time 0.00
Received By hpiskura Date 2003-01-23 Time 13:36 Sent To Z
Notes
2003-01-28 00:00:00PAID PLAN REVIEW, NOT A PERMIT
 APPLICATION.
  
 SHEET S.01 DOES NOT INDICATE THE LIVE
 LOADS FOR THEBALCONIES.SEE FBC 1604.
 1.
  
 NOTE #7 UNDER SITE WORK ON SHEET S.01
 CALLS OUT EARTH FORMS FOR THE
 FOUNDATIONS.THIS IS PROHIBITTED BY FBC
 1804.1.1 AS AMENDED BY THE CITY OF WEST
 PALM BEACH.
  
 SHEET S.02 UNDER TRUSS NOTES DOES NOT
 INDICATE THE MINIMUM 10 PSF FOR ATTIC
 LIVELOADS IN ACCORDANCE WITH FBC TABLE
 1604.1.
  
 A PORTION OF THE PROPERTY IS LOCATED IN
 A FLOOD HAZARD AREA A5 WITH A BFE OF
 7.0' NGVD.THE LOWEST FINISHED FLOOR
 MUST BE A MINIMUM OF 0.5' ABOVE THE BFE
 AS PROVIDED FOR IN CITY ORDINANCE
 1440-79.
  
 A RESIDENT INSPECTOR AS PROVIDED FOR IN
 FBC 105.3 AS AMENDED BY THE CITY.
 CONTACT DON NEELY AT 561-659-8096 X8333
 FOR MORE INFORMATION.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO THE
 COOUNTY, THE PERMIT PLANS STAMPED BY
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.
  
 EACH TOWNHOUSE WILL BE PERMITTED
 SEPARATELY, IE 42 INDIVIDUAL PERMIT
 APPLICATIONS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-03-19 Cont ID  
Sent By dpalmer Date 2003-03-19 Time 15:44 Rev Time 4.50
Received By dpalmer Date 2003-03-19 Time 15:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-01-22 Cont ID  
Sent By dpalmer Date 2003-01-22 Time 06:50 Rev Time 6.50
Received By dpalmer Date 2003-01-22 Time 06:50 Sent To  
Notes
2003-01-22 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SEE RISER HC & HB, PLEASE
 SEE 3-3/0` IN 1 1/4" CONDUIT. PLEASE SEE
 CONDUIT FILL IN NEC.
  
 2)NOTE: PLEASE SEE 210-52G FOR MISSING
 RECEPT IN GARAGE. PLEASE ALSO SEE 210-8
 FOR GFI PROTECTION. #`S1,4,3,8
 SOME UNITS SHOW REC, BUT NOT GFI.
 3)NOTE: PLEASE CLARIFY ELEVATOR SHOWN
 ON PANEL SCHEDULE AND CAN NOT FIND ON
 PLANS.??
  
 4)NOTE: PLEASE SEE SOME UNITS MISSING
 RECEPTS PER 210-52E SHOWS FRONT BUT NOT
 REAR?
  
 5)NOTE: ALL RECEOTS SERVING KITCHEN
 COUNTERSPACE ARE TO BE SHOWN AS GFI/GFI
 PROTECTED PER 210-8-A-6.
  
 6)NOTE; PLEASE SIZE GROUNDING ELECTRODE
 CONDUCTOR PER 250-66. (3/0`S). SEC.
  
 7)NOTE: PLEASE SEE 680-70 FOR REQ`D GFI
 PROTECTION OF SPA -TUB SHOWN. PLEASE
 INDICATE ON PLANS.
  
 8)NOTE: PLEASE CLARIFY ELEVATOR CAR LTS
 BEING SHOWNAS "GFI" ON PANEL SCHEDULE?
  
 9)NOTE: PLEASE CLARIFY SUB-PANEL BEING
 SHOWN AS 200A MCB ON PANEL AND 125 MLO
 ON RISER. (E-2.7)
  
 10)NOTE: PLEASE SEE OCP AND MIN SIZE
 AWG FOR 1OKW HEAT/AHU ON 2.21. PLEASE
 SEE 424-3B MIN 125%
  
 11)NOTE: PLEASE SEE AWG FOR AHU IN PANEL
 HA, #12 W/30A OCP?
  
 12)NOTE: PLEASE SHOW ALL CONTINUOUS LOAD
 -S ON HOUSE PANELS AT 125%. 215-3,230-42
 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2003-01-06 Cont ID  
Sent By mamini Date 2003-01-06 Time 15:36 Rev Time 0.00
Received By mamini Date 2003-01-06 Time 15:36 Sent To  
Notes
2003-01-06 00:00:00N/A :
 1. SEE PERMIT # 02121271 FOR CIVIL /SITE
 WORK.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-03-20 Cont ID  
Sent By shernand Date 2003-05-28 Time 09:11 Rev Time 0.00
Received By mcarsill Date 2003-03-20 Time 09:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-01-16 Cont ID  
Sent By mcarsill Date 2003-01-16 Time 10:46 Rev Time 0.00
Received By mcarsill Date 2003-01-16 Time 10:46 Sent To  
Notes
2003-01-16 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO,DURING,AND AFTER CONSTRUCTION.
  
 2) SUITABLE ROADS ARE TO BE PROVIDED FOR
 FIRE AND PARAMEDICAL EQUIPMENT DURING
 CONSTRUCTION.
  
 3) ENSURE ALL GARAGE DOORS INSTALLED IN
 RATED SEPARATION WALLS ARE LABELED AND
 RATED.
  
 4) PROVIDE PORTABLE FIRE EXTINGUISHERS.
  
 5) FIRE LINES ARE NOT ALLOWED TO BE RUN
 UNDERNEATH BUILDING FOUNDATIONS.
  
 6) PROVIDE SEPARATE PLANS AND PERMITS
 FOR FIRE SPRINKLER SYSTEM INSTALLATIONS.
  
 7) PROVIDE SEPARATE PLANS AND PERMITS
 FOR FIRE ALARM SYSTEM EQUIPMENT.
  
 8) PROVIDE SEPARATE PLANS AND PERMITS
 FOR SECURITY GATES.
  
 9) ALL SMOKE DETECTORS ARE TO BE
 INSTALLED A MINIMUM OF THREE FEET FROM
 AC DIFFUSERS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-28 Cont ID  
Sent By shernand Date 2003-05-28 Time 09:11 Rev Time 0.00
Received By shernand Date 2003-05-28 Time 09:11 Sent To FIRE
Notes
2003-05-28 00:00:00SUBMITTAL:NEW FLOW TEST CALCS PER FIRE
 REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-27 Cont ID  
Sent By dpalmer Date 2003-02-27 Time 16:28 Rev Time 0.00
Received By dpalmer Date 2003-02-27 Time 16:28 Sent To  
Notes
2003-03-05 00:00:00TO COMM BOARD #49, PLANS ON BOTTOM SHELF
 ON RACK BY CONF. ROOM.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-03-18 Cont ID  
Sent By pkrauss Date 2003-03-18 Time 14:20 Rev Time 0.00
Received By pkrauss Date 2003-03-18 Time 14:20 Sent To  
Notes
2003-03-18 00:00:00DENIED:
  
 COMMENT #2 FROM PREVIOUS REVIEW WAS NOT
 ADDRESSED:
 MASTER BATHROOMS TO ALL UNITS INDICATE
 AN EXHAUST FAN ONLY IN THE "TOILET" ROOM
 ONE WILL ALSO BE REQUIRED WHERE THE
 SHOWER, BATHTUB AND SINKS ARE LOCATED
 AS PER 2001 FBC(M) 402.3.1.
  
 DEVELOPED LENGTH FOR THE DRYER EXHAUST
 SHALL NOT EXCEED 25 FT AS PER 2001
 FBC(M) 504.6.THERE IS A 5 FT REDUCTION
 FOR EACH 90 DEGREE RAD & 2 1/2 FT
 REDUCTION FOR EACH 45 DEGREE RAD.
  
 PLEASE NOTE UNITS 20,11,12,14,15,17,18,
 21,23,24,26,27, & 28, 10" X 10" DROP
 DOWN FROM SECOND FLOOR INTO GARAGE AREA
 THEN BACK INTO THE FIRST FLOOR.THIS IS
 A RATED WALL & FLOOR ASSEMBLY.DUCT
 CANNOT EXCEED 100 SQ IN AND SHALL COMPLY
 WITH ALL OF 2001 FBC(M) 607.1.3 #3 ITEMS
 1 THRU 4.WHERE THE 8" DUCT PENETRATES
 FROM THE GARAGE INTO THE "FOYER" THIS
 DUCT SHALL ALSO COMPLY WITH THE AFORE-
 MENTIONED CODE.
  
 DRYER EXHAUST WAS NOT ADDRESSED.MAX
 DEVELOPED LENGTH OF 25 FT WITH A 5 FT
 REDUCTION FOR EACH 90 DEGREE RAD &
 2 1/2 FT REDUCTION FOR EACH 45 DEGREE
 RAD.
  
 PLEASE CLARIFY PLAN SHEET AC-2.28, POOL
 CABANA FLOOR PLAN - DETAIL INDICATES THE
 CONDENSING UNIT UPSTAIRS, THE ARCH PLAN
 SHEET A.45.01 INDICATES THIS TO BE THE
 AHU.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-01-14 Cont ID  
Sent By pkrauss Date 2003-01-13 Time 15:45 Rev Time 8.00
Received By pkrauss Date 2003-01-13 Time 15:45 Sent To  
Notes
2003-01-13 00:00:00DENIED:
  
 1.PROVIDE OUTSIDE AIR CALCULATION AS
 PER 2001 FBC(M) TABLE 403.3 OR 402.2 FOR
 NATURAL VENTILATION.INDICATE OUTSIDE
 AIR ON PLAN, INDICATE DUCT MATERIAL,
 SIZE, AND LAYOUT.
  
 2.ALL MASTER BATHROOMS INDICATE AN
 EXHAUST FAN IN THE TOILET ROOM ONLY.
 AS PER 2001 FBC(M) 402.3.1, ROOMS
 CONTAINING BATHTUBS SHOWERS OR SPAS
 SHALL BE MECHANICALLY VENTILATED.
  
 3.PLAN SHEET AC-2.4 & AC-2.5, DO NOT
 INDICATE AN EXHAUST FAN IN THE 2ND FLOOR
 PDR ROOM.
  
 4.EXHAUST FAN SCHEDULE NOR PLAN SHOW
 GRILLE SIZE FOR EHXAUST FANS 4 & 5.
  
 5.UNITS 9,20,11,12,14,15,21,23,24,26,
 27,28,29, & 30 DO NOT INDICATE MAKE-UP
 AIR FOR THE BATHROOMS (MASTER BATHROOMS
 DO INDICATE MAKE-UP AIR, OTHER BATHROOMS
 DO NOT). PLEASE INDICATE HOW REQUIREMENT
 FOR MAKEUP AIR WILL BE ACHIEVED. 2001
 FBC(M) 501.4.
  
 6.PLEASE NOTE, DRYERS EXHAUSTING MORE
 THAN 200 CFM SHALL HAVE MAKE-UP AIR AS
 PER 2001 FBC(M) 504.5.
  
 7.PLEASE NOTE, DEVELOPED LENGTH SHALL
 NOT EXCEED 25 FT WITH A 5 FT REDUCTION
 FOR EACH 90 DEGREE RAD. & A 2 1/2 FT
 REDUCTION FOR EACH 45 DEGREE RAD. 2001
 FBC(M) 504.6.
  
 8.PLANS DO NOT GIVE SPECIFIC DEMINSION
 FOR ACCESS & CLEARANCE FOR SERVICE FOR
 THE AHU'S LOCATED IN THE ATTIC.PLEASE
 SHOW COMPLIANCE WITH 2001 FBC(M) 306.3 &
 2001 FBC CHAPTER 13 610.1.ABC.3.5.2 FOR
 REQUIRED CLEARANCES & ACCESS.
  
 PLEASE NOTE, ALL AHU'S ARE REQUIRED TO
 HAVE AN AUXILLIARY DRAIN PAN WITH OVER
 FLOW PROTECTION.2001 FBC(M) 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-03-20 Cont ID  
Sent By kstevens Date 2003-03-20 Time 16:09 Rev Time 3.00
Received By kstevens Date 2003-03-20 Time 16:09 Sent To  
Notes
2003-03-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
  
 1) SHTS A.29, A.30, A.32, A.33, A.34,
 A.35, A.36, A.37, A.38, A.39, A.40, A.41
 A.42, A.43, A.44. & A.44A - PLEASE INDI-
 CATE SPECIFICATION "A" OR "B" PER RE-
 QUIREMENT 7B FHA-DESIGN MANUAL.
 2) SAME SHTS AS COMMENT #1, PLEASE IN-
 DICATE SIZE OF OPENING FOR W/C. MINIMUM
 OF 33" REQUIRED. (18 - 15).
 3) SHTS A.37 & A.38 IF THERE IS BOTH A
 BATHROOM AND A POWDER ROOM THEN THE
 BATHROOM WOULD BE REQURED TO BE USEABLE
 AND MEET REQUIREMENTS.
 4) SHT A.45 FACILITIES FOR POOL CABANA
 TO BE APPROVED AND STAMPED BY THE HEALTH
 DEPT. 901 EVERNIA ST. (FROM PREV. REVIEW
 5) SHT A.51 PROVIDE BACKING DETAIL THAT
 COMPLYS WITH FHA-DESIGN MANUAL REQUIRE-
 MENT 6.
 6) SHT P2.23 WATER HEATER DETAIL, PRESS-
 URE RELIEF VALVES SHALL NOT BE USED AS A
 MEANS FOR CONTROLLING THERMAL EXPANSION.
 SEE SECTION 504.5. AN EXPANSION TANK IS
 REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-01-15 Cont ID  
Sent By kstevens Date 2003-01-15 Time 07:17 Rev Time 5.50
Received By kstevens Date 2003-01-14 Time 18:41 Sent To  
Notes
2003-01-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) ALL FIRST FLOOR BATHROOM IN UNITS
 WITH ELEVATORS SHALL COMPLY WITH THE U S
 DEPT OF HOUSING AND URBAN DEVELOPMENT
 (HUD) FAIR HOUSING ACT REGULATIONS, 24
 CODE OF FEDERAL REGULATIONS (CFR)
 100.201 (C)(3)(IV). PLEASE SHOW CLEAR
 FLOOR SPACE FOR ALL BATHROOMS PER PAGE
 7.43 PARAGRAPH 1 OF THE FHA-AMEND 98
 DESIGN MANUAL.
 2) SHT A.45 FACILITIES FOR POOL CABANA
 TO BE APPROVED AND STAMPED BY THE HEALTH
 DEPT. 901 EVERNIA ST.
 3) SHT A.45 TYPICAL HDCP BATH ACCESSORY
 PLAN SHOW W/C AT 1'10" OFF WALL TO CENT-
 ER OF FIXTURE. 1'6" IS REQUIRED .
 4) SHT A.45 PLEASE SUBMIT DETAIL FOR
 URNAL SHOWING COMPLIANCE WITH SECTION
 11-4.18 AND ALL SUBSECTIONS.
 5) SEPARATE POOL PERMITS REQUIRED FOR
 EACH POOL.
 5) RPZ BACKFLOW REQUIRED FOR CABANA
 WATER SERVICE AND ANY WATER SERVICE FOR
 UNITS WITH POOLS.
 6) SHT A.48 ENTRY GATE TOILET ROOM SHALL
 BE ACCESSIBLE PER 11-4.22. PLEASE SUBMIT
 A DETAIL.
 7) SHT A.51 DRAWING SHALL BE DRAWN WITH
 SUFFICIENT CLARITY AND DETAIL TO INDIC-
 ATE THE NATURE AND CHARACTER OF WORK.
 SOME OF THE DETAILS ON THIS PAGE ARE
 VERY HARD TO READ. PLEASE SUBMIT CLEAR
 DETAILS.
 8) SHT P-2.3 UTILITY ROOM STACK, WASH
 MACHINE AND LAUNDRY SINK SHALL NOT BE
 ON A SANITARY CROSS. W/M TEE SHALL BE
 LOWER THAN LAUNDRY SAN. TEE. SECTION
 706.3
 9) SHTS P2.19 & P2.20 IS W/C FOR BATH
 FOR DEN/BEDROOM #3 BEING PICKED UP ON
 THE VERTICAL RISER OR ON THE HORIZONTAL
 PIPE? IT SHOWS BEING PIPED TO BOTH.
 10)SHT P-2.23 WATER HEATER DETAIL, THER-
 MAL EXPANSION CONTROL WILL BE REQUIRED
 FOR ANY UNIT THAT HAS AN RPZ BACKFLOW ON
 WATER SERVICE. SECTION 607.3.2 - T/P
 RELIEF LINE SHALL NOT HAVE ANY TRAPPED
 SECTIONS IN DISCHARGE LINE PER SECTION
 504.7.1
 11) SHT P-2.23 W/M DETAIL, C/O SHALL BE
 MIN. 4' AFF.
 12) PLEASE PROVIDE A DETAIL FOR FLOOR
 DRAINS. SHOW HOW THE DRAIN AND DRAIN
 AREA WILL BE WATER PROOFED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2003-01-29 Cont ID  
Sent By hpiskura Date 2003-01-28 Time 10:34 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***