Plan Review Details - Permit 02121233
Plan Review Stops For Permit 02121233
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-02-07 Cont ID  
Sent By pschmitz Date 2003-02-13 Time 07:39 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-01-17 Cont ID  
Sent By lsmith Date 2003-01-17 Time 13:52 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
2003-01-17 00:00:00************FAILED**************
  
 1. FIRE SPRINKLER PERMIT REQUIRED
 2. ALL SUBS MUST APPLY FOR SEPARATE
 PERMITS.
 3. NEED HEALTH DEPT. SIGN OFF
 4. BUILDING CLASSIFICATION IS "M" PER
 FBC 310.1. 34 SEATS RESTAURANT (UNDER
 50).
 5. GET HEALTH DEPARTMENT APPROVAL.
  
  
  
 AANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 659-8096 EXT. 8394

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2003-05-28 Cont ID  
Sent By btrobaug Date 2003-05-28 Time 10:25 Rev Time 1.00
Received By btrobaug Date 2003-05-28 Time 10:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2003-05-27 Cont ID  
Sent By btrobaug Date 2003-05-27 Time 12:51 Rev Time 1.00
Received By btrobaug Date 2003-05-27 Time 12:51 Sent To  
Notes
2003-05-27 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 THERE ARE 12 CIRCUITS IN PANEL "A" AND
 6 CIRCUITS IN PANEL"B"SCHEDULES THAT
 ARE EITHER DUPLICATED OR DO NOT
 CORRELATE WITH THE CIRCUITS NUMBERS ON
 THE DRAWING AT THE CIRCUIT LOCATION.
  
 PLEASE CORRELATE THE SCHEDULES WITH
 ACTUAL JOB CONDITIONS AND RESUBMIT FOR
 REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2003-05-05 Cont ID  
Sent By dpalmer Date 2003-05-05 Time 12:36 Rev Time 1.25
Received By dpalmer Date 2003-05-05 Time 12:36 Sent To  
Notes
2003-05-05 00:00:00************ UNSAT *****************
  
 1)NOTE: PLEASE CORRELATE LOADS/PANELS/
 AND DISC`S.
 PLEASE INCREASE SERVICE TO MEET LOAD
 SERVED.
 SHOWS 204A`S ON 150A FUSES AND 200A DISC
 .
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-02-13 Cont ID  
Sent By dpalmer Date 2003-02-13 Time 07:50 Rev Time 0.50
Received By dpalmer Date 2003-02-13 Time 07:50 Sent To  
Notes
2003-02-13 00:00:00**********PROVISO/NOTES ****************
  
 1)NOTE: PLEASE PROVIDE LOAD CALCULATIONS
 ON EXISTING 1000A MAIN.
 PLEASE SHOW EXSITING WITH NEW, PLEASE
 SUBMIT THE ABOVE INFORMATION FOR REVIEW
 BEFORE ANY ELECTRICAL INSPECTION IS
 CALLED IN.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-02-07 Cont ID  
Sent By dpalmer Date 2003-02-07 Time 13:18 Rev Time 0.50
Received By dpalmer Date 2003-02-07 Time 13:18 Sent To  
Notes
2003-02-07 00:00:00************* NOTES ***********
  
 PROVIDE LOAD CALCS ON MAIN DISC BEFORE
 ROUGH.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-01-06 Cont ID  
Sent By dpalmer Date 2003-01-06 Time 11:28 Rev Time 0.50
Received By dpalmer Date 2003-01-06 Time 11:16 Sent To  
Notes
2003-01-06 00:00:00*********** UNSAT **************
  
 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 FOR EM/EXT LTS. PLEASE ALSO SHOW PER
 700-12E FOR CIRCUITING.
  
 2)NOTE: PLEASE NOTE CIRCUIT FOR SIGN
 SHOWN AS STEAM TABLE ON PANEL "B".
  
 3)NOTE: PLEASE PROVIDE AIC RATING FOR
 NEW DISC`S SHOWN ON RISER DIAGRAM.
 110-9/215-5
  
 4)NOTE: PLEASE CLARIFY EQUIPMENT GROUND-
 ING METHOD BETWEEN MAIN DISC`S AND PANEL
 -S.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-02-07 Cont ID  
Sent By mcarsill Date 2003-02-07 Time 10:31 Rev Time 0.00
Received By mcarsill Date 2003-02-07 Time 10:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-01-02 Cont ID  
Sent By mcarsill Date 2003-01-02 Time 19:32 Rev Time 0.00
Received By mcarsill Date 2003-01-02 Time 19:32 Sent To  
Notes
2003-01-02 00:00:001) PLEASE INDICATE HOW MANY EMPLOYEES
 ARE EXPECTED TO BE PRESENT DURING
 NORMAL BUSINESS HOURS.
  
 2) COULD NOT LOCATE ANY FIRE ALARM
 EQUIPMENT CONTAINED WITHIN TENANT
 SPACE.
  
 3) DOOR SCHEDULE MAKES REFERENCE TO
 DEADBOLT LOCKS. PLEASE ADVISE IF THESE
 ARE SINGLE CYLINDER OR DOUBLE CYLINDER
 LOCKS. LOCKING DEVICES ON EXIT DOORS
 THAT REQUIRE THE USE OF A KEY ARE
 PROHIBITED.
  
 4) COULD NOT LOCATE ANY FIRE ALARM
 EQUIPMENT WITHIN TENANT SPACE.
  
 5) PLEASE INDICATE LOCATIONS OF
 PORTABLE FIRE EXTINGUISHERS.
  
 6) IT APPEARS THAT ONLY ONE EMERGENCY
 LIGHT FIXTURE IS PRESENT WITHIN THE
 SPACE. THIS DOES NOT APPEAR TO BE
 ACCEPTABLE.
  
 7) COMPLETE PLANS AND PERMIT FOR HOOD,
 DUCT, AND EXTINGUISHING SYSTEM PLANNED
 FOR USE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2003-02-13 Cont ID  
Sent By pschmitz Date 2003-02-13 Time 07:39 Rev Time 1.00
Received By pschmitz Date   Time   Sent To B
Notes
2003-02-13 00:00:00DENIED, EMERGENCY SOV, BELOW CEILING.
 NO PIPE SIZES SHOWN ON PLANS.
 SEPERATE PLANS, PERMIT.PES

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-03-12 Cont ID  
Sent By sthyng Date 2003-03-12 Time 15:25 Rev Time 0.00
Received By sthyng Date 2003-03-12 Time 15:25 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-02-12 Cont ID  
Sent By btrobaug Date 2003-02-12 Time 16:38 Rev Time 0.00
Received By btrobaug Date 2003-02-11 Time 16:38 Sent To  
Notes
2003-02-12 00:00:00TO COM BOARD#2./WRT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-02-06 Cont ID  
Sent By dpalmer Date 2003-02-06 Time 17:28 Rev Time 0.00
Received By dpalmer Date 2003-02-06 Time 17:28 Sent To  
Notes
2003-02-06 00:00:00TO COMM BOARD #32.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-20 Cont ID  
Sent By btrobaug Date 2002-12-20 Time 18:40 Rev Time 0.00
Received By btrobaug Date 2002-12-20 Time 18:40 Sent To  
Notes
2002-12-20 00:00:00TO COM BOARD #24./WRT

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-04-03 Cont ID  
Sent By pkrauss Date 2003-04-03 Time 13:58 Rev Time 0.46
Received By pkrauss Date 2003-04-03 Time 13:58 Sent To  
Notes
2003-04-03 00:00:00MECHANICAL PERMIT 03030174

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-02-13 Cont ID  
Sent By pkrauss Date 2003-02-13 Time 14:32 Rev Time 0.35
Received By pkrauss Date 2003-02-13 Time 14:14 Sent To  
Notes
2003-02-13 00:00:00PROVISO ON PLAN

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-02-08 Cont ID  
Sent By pkrauss Date 2003-02-08 Time 08:41 Rev Time 0.45
Received By pkrauss Date 2003-02-08 Time 08:40 Sent To  
Notes
2003-02-08 00:00:00PROVISO:
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION & WALK-IN COOLER.
 PROVIDE PLANS & MANUFACTURER SUBMITTAL
 DATA WITH PERMIT APPLICATION.
  
 1. PROVIDE SUBMITTAL/INSTALLATION
 INSTRUCTIONS ON THE FIREWRAP TO BE
 INSTALLED.
  
 2. GREASE DUCT TERMINATION SHALL NOT BE
 LOCATED WHERE "PROTECTED" OPENS ARE
 REQUIRED.EXTERIOR OPENINGS SHALL NOT
 BE LOCATED WITHIN 3 FT OF SUCH
 TERMINATIONS.
  
 3. SHALL BE A MINIMUM OF 10 FT ABOVE
 ADJOINING GRADE LEVEL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-01-10 Cont ID  
Sent By pkrauss Date 2003-01-10 Time 14:13 Rev Time 0.45
Received By pkrauss Date 2002-12-24 Time 07:59 Sent To  
Notes
2003-01-10 00:00:00DENIED:
  
 PLEASE INDICATE ON PLAN THE LOCATION
 OF THE FRESH AIR INTAKE.AS PER 2001
 FBC(M) 401.5.1, OUTSIDE AIR INTAKE
 OPENINGS SHALL BE LOCATED A MINIMUM OF
 10 FT FROM ANY HAZARDOUS OR NOXIOUS
 CONTAMINANT, SUCH AS VENTS, STREETS,
 ALLEYS, PARKING LOTS & LOADING DOCKS.
  
 CLARIFY NOTE ON PLAN "CONNECT TO HEAT
 HOOD DUCT", THIS APPEARS TO BE TIED INTO
 TOILET EXHAUST?
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 AS PER NFPA 4-4.4.3.
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 GREASE DUCT, FIRE SUPRESSION & WALK-IN
 COOLER/FREEZER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-02-13 Cont ID  
Sent By sthyng Date 2003-03-12 Time 15:25 Rev Time 1.00
Received By pschmitz Date   Time   Sent To B
Notes
2003-02-13 00:00:00REVISIONS FOR PLBG, APPROVED,GAS DENIED.

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-02-07 Cont ID  
Sent By kstevens Date 2003-02-07 Time 18:31 Rev Time 0.75
Received By kstevens Date 2003-02-07 Time 18:31 Sent To  
Notes
2003-02-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 1) ROUTE PLANS TO DEPT. OF BUSINESS
 REGULATION FOR REVIEW AND APPROVAL.
 PLANS TO BE STAMPED AND WORKSHEET ATT-
 ACHED PRIOR TO RESUBMITTING TO CITY FOR
 REVIEW.
 2) SHT A4.0 HOOD DRAIN SHALL NOT BE PVC.
 PIPE DRIECT TO VENT AND INSTALL A VALVE.
 3) SHT A4.0 RPZ BACKFLOW SHALL BE MAXI-
 MUM OF 4' AFF FOR TESTING AND SERVICING
 4) FROM PREVIOUS REVIEW: SHT A4.0 FLOOR
 PLAN AND SANITARY RISER DIAGRAM, DISH-
 WASHER SHALL DRAIN TO SANITARY. UTILITY
 ORD.
 5) FROM PREVIOUS REVIEW: PLEASE PROVIDE
 DETAILS FOR HDCP TOILET ROOMS PER SEC.
 11-4.22 AND ALL SUBSECTIONS. CLEAR FLOOR
 SPACE NOT SHOWN OR 5' TURNING SPACE.
 6) FROM PREVIOUS REVIEW: GREASE TRAP
 DETAIL ON SHT A4.0 IS NOT APPROVED. SEE
 ATTACHED SHEET FOR CITY UTILITY APPROVED
 DETAIL.
 7) FOR GAS PERMIT APPLICATION THESE
 REQUIREMENTS ARE NOT ADDRESSED FROM PRE-
 VIOUS REVIEW:
 A. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 B. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 8) PLEASE SUBMIT A FLOOR PLAN THAT HAS
 MEASUREMENTS FOR TOILET ROOMS.
 9) PAGES ON PLANS DO NOT MATCH INDEX ON
 COVER SHEET. WHEN RESUBMITTING PLANS
 PLEASE SUBMIT TWO FULL SETS WITH PAGES
 SHOWN ON INDEX. REMOVE ALL REVISED
 SHEETS AND INSERT NEW SHEETS. SUBMIT SET
 OF OLD SHEETS TO COMPARE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-01-06 Cont ID  
Sent By kstevens Date 2003-01-06 Time 18:15 Rev Time 1.25
Received By kstevens Date 2003-01-06 Time 18:14 Sent To  
Notes
2003-01-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 1) PLEASE CONTACT RODNEY COMPO, INVIRON-
 MENTAL COMPLIANCE TO SIZE GREASE TRAP.
 UTILITY DEPT WASTE ORD. #2938-96. PH #
 (561) 837-4074
 2) SHT A4.0 HOOD DRAIN, SAFE WASTE NOT
 APPROVED. FLOOR SINK REQUIRED WITH VENT,
 OR RUN SEPARATE LINE FROM MAIN VENTED
 LINE TO FLOOR SINK.
 3) PLEASE SUBMIT INFORMATION FOR UTILITY
 FAN DRAIN.
 4) SHT A4.0 GREASE TRAP DETAIL, SEE
 ATTACHED SHEET FOR CITY WEST PALM BEACH
 STANDARD FOR GREASE TRAPS. NOTE: 2 WAY
 CLEANOUTS REQUIRED ENTERING AND EXITING
 GREASE TRAP. SEE WALL AND BOTTOM THICK-
 NESS ECT.
 5) RPZ BACKFLOW REQUIRED ON WATER SERV-
 ICE TO SPACE.
 6) SHT A4.0 WATER RISER DIAGRAM, WATER
 HAMMERS REQUIRED BY SEC 604.9 SHALL BE
 SHOWN AND LOCATED NEAR FIXTURE. (ICE
 MAKER - DISHWASHER - QUICK CLOSING VAL-
 VES).
 7) SHT A4.0 WATER HEATER DETAIL, THERMAL
 EXPANSION CONTROL IS REQUIRED PER SEC.
 607.3.2
 8) SEPARATE GAS PERMIT REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED FOR
 PERMIT APPLICATION.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 E. EMERGENCY HOOD SHUT DOWN SHUT OFF
 9) SHT A4.0 DISHWASHER SHALL DRAIN TO
 SANITARY PER UTILITY DEPT ORDINANCE.
 10) PLEASE PROVIDE DETAILS FOR HDCP
 TOILET ROOMS PER SEC 11-4.22 AND ALL
 SUBSECTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2003-01-23 Cont ID  
Sent By lsmith Date 2003-01-23 Time 12:34 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***