| Plan Review Stops For Permit 02121233 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2003-02-07 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2003-02-13 |
Time |
07:39 |
Rev Time |
0.75 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-01-17 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2003-01-17 |
Time |
13:52 |
Rev Time |
1.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2003-01-17 00:00:00 | ************FAILED************** | | | | | | 1. FIRE SPRINKLER PERMIT REQUIRED | | | 2. ALL SUBS MUST APPLY FOR SEPARATE | | | PERMITS. | | | 3. NEED HEALTH DEPT. SIGN OFF | | | 4. BUILDING CLASSIFICATION IS "M" PER | | | FBC 310.1. 34 SEATS RESTAURANT (UNDER | | | 50). | | | 5. GET HEALTH DEPARTMENT APPROVAL. | | | | | | | | | | | | AANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 659-8096 EXT. 8394 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2003-05-28 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-05-28 |
Time |
10:25 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2003-05-28 |
Time |
10:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2003-05-27 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-05-27 |
Time |
12:51 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2003-05-27 |
Time |
12:51 |
Sent To |
|
|
| Notes |
| 2003-05-27 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | THERE ARE 12 CIRCUITS IN PANEL "A" AND | | | 6 CIRCUITS IN PANEL"B"SCHEDULES THAT | | | ARE EITHER DUPLICATED OR DO NOT | | | CORRELATE WITH THE CIRCUITS NUMBERS ON | | | THE DRAWING AT THE CIRCUIT LOCATION. | | | | | | PLEASE CORRELATE THE SCHEDULES WITH | | | ACTUAL JOB CONDITIONS AND RESUBMIT FOR | | | REVIEW. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2003-05-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-05-05 |
Time |
12:36 |
Rev Time |
1.25 |
| Received By |
dpalmer |
Date |
2003-05-05 |
Time |
12:36 |
Sent To |
|
|
| Notes |
| 2003-05-05 00:00:00 | ************ UNSAT ***************** | | | | | | 1)NOTE: PLEASE CORRELATE LOADS/PANELS/ | | | AND DISC`S. | | | PLEASE INCREASE SERVICE TO MEET LOAD | | | SERVED. | | | SHOWS 204A`S ON 150A FUSES AND 200A DISC | | | . | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2003-02-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-13 |
Time |
07:50 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-02-13 |
Time |
07:50 |
Sent To |
|
|
| Notes |
| 2003-02-13 00:00:00 | **********PROVISO/NOTES **************** | | | | | | 1)NOTE: PLEASE PROVIDE LOAD CALCULATIONS | | | ON EXISTING 1000A MAIN. | | | PLEASE SHOW EXSITING WITH NEW, PLEASE | | | SUBMIT THE ABOVE INFORMATION FOR REVIEW | | | BEFORE ANY ELECTRICAL INSPECTION IS | | | CALLED IN. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2003-02-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-07 |
Time |
13:18 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-02-07 |
Time |
13:18 |
Sent To |
|
|
| Notes |
| 2003-02-07 00:00:00 | ************* NOTES *********** | | | | | | PROVIDE LOAD CALCS ON MAIN DISC BEFORE | | | ROUGH. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-01-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-01-06 |
Time |
11:28 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-01-06 |
Time |
11:16 |
Sent To |
|
|
| Notes |
| 2003-01-06 00:00:00 | *********** UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS | | | FOR EM/EXT LTS. PLEASE ALSO SHOW PER | | | 700-12E FOR CIRCUITING. | | | | | | 2)NOTE: PLEASE NOTE CIRCUIT FOR SIGN | | | SHOWN AS STEAM TABLE ON PANEL "B". | | | | | | 3)NOTE: PLEASE PROVIDE AIC RATING FOR | | | NEW DISC`S SHOWN ON RISER DIAGRAM. | | | 110-9/215-5 | | | | | | 4)NOTE: PLEASE CLARIFY EQUIPMENT GROUND- | | | ING METHOD BETWEEN MAIN DISC`S AND PANEL | | | -S. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2003-02-07 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-02-07 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-02-07 |
Time |
10:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2003-01-02 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-01-02 |
Time |
19:32 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-01-02 |
Time |
19:32 |
Sent To |
|
|
| Notes |
| 2003-01-02 00:00:00 | 1) PLEASE INDICATE HOW MANY EMPLOYEES | | | ARE EXPECTED TO BE PRESENT DURING | | | NORMAL BUSINESS HOURS. | | | | | | 2) COULD NOT LOCATE ANY FIRE ALARM | | | EQUIPMENT CONTAINED WITHIN TENANT | | | SPACE. | | | | | | 3) DOOR SCHEDULE MAKES REFERENCE TO | | | DEADBOLT LOCKS. PLEASE ADVISE IF THESE | | | ARE SINGLE CYLINDER OR DOUBLE CYLINDER | | | LOCKS. LOCKING DEVICES ON EXIT DOORS | | | THAT REQUIRE THE USE OF A KEY ARE | | | PROHIBITED. | | | | | | 4) COULD NOT LOCATE ANY FIRE ALARM | | | EQUIPMENT WITHIN TENANT SPACE. | | | | | | 5) PLEASE INDICATE LOCATIONS OF | | | PORTABLE FIRE EXTINGUISHERS. | | | | | | 6) IT APPEARS THAT ONLY ONE EMERGENCY | | | LIGHT FIXTURE IS PRESENT WITHIN THE | | | SPACE. THIS DOES NOT APPEAR TO BE | | | ACCEPTABLE. | | | | | | 7) COMPLETE PLANS AND PERMIT FOR HOOD, | | | DUCT, AND EXTINGUISHING SYSTEM PLANNED | | | FOR USE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2003-02-13 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2003-02-13 |
Time |
07:39 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
B |
|
| Notes |
| 2003-02-13 00:00:00 | DENIED, EMERGENCY SOV, BELOW CEILING. | | | NO PIPE SIZES SHOWN ON PLANS. | | | SEPERATE PLANS, PERMIT.PES |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2003-03-12 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-12 |
Time |
15:25 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-12 |
Time |
15:25 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-02-12 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-02-12 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2003-02-11 |
Time |
16:38 |
Sent To |
|
|
| Notes |
| 2003-02-12 00:00:00 | TO COM BOARD#2./WRT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-02-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-06 |
Time |
17:28 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2003-02-06 |
Time |
17:28 |
Sent To |
|
|
| Notes |
| 2003-02-06 00:00:00 | TO COMM BOARD #32. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-12-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-20 |
Time |
18:40 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-12-20 |
Time |
18:40 |
Sent To |
|
|
| Notes |
| 2002-12-20 00:00:00 | TO COM BOARD #24./WRT |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2003-04-03 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-04-03 |
Time |
13:58 |
Rev Time |
0.46 |
| Received By |
pkrauss |
Date |
2003-04-03 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2003-04-03 00:00:00 | MECHANICAL PERMIT 03030174 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2003-02-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-02-13 |
Time |
14:32 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2003-02-13 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2003-02-13 00:00:00 | PROVISO ON PLAN |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2003-02-08 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-02-08 |
Time |
08:41 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2003-02-08 |
Time |
08:40 |
Sent To |
|
|
| Notes |
| 2003-02-08 00:00:00 | PROVISO: | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | FIRE SUPRESSION & WALK-IN COOLER. | | | PROVIDE PLANS & MANUFACTURER SUBMITTAL | | | DATA WITH PERMIT APPLICATION. | | | | | | 1. PROVIDE SUBMITTAL/INSTALLATION | | | INSTRUCTIONS ON THE FIREWRAP TO BE | | | INSTALLED. | | | | | | 2. GREASE DUCT TERMINATION SHALL NOT BE | | | LOCATED WHERE "PROTECTED" OPENS ARE | | | REQUIRED.EXTERIOR OPENINGS SHALL NOT | | | BE LOCATED WITHIN 3 FT OF SUCH | | | TERMINATIONS. | | | | | | 3. SHALL BE A MINIMUM OF 10 FT ABOVE | | | ADJOINING GRADE LEVEL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2003-01-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-01-10 |
Time |
14:13 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-12-24 |
Time |
07:59 |
Sent To |
|
|
| Notes |
| 2003-01-10 00:00:00 | DENIED: | | | | | | PLEASE INDICATE ON PLAN THE LOCATION | | | OF THE FRESH AIR INTAKE.AS PER 2001 | | | FBC(M) 401.5.1, OUTSIDE AIR INTAKE | | | OPENINGS SHALL BE LOCATED A MINIMUM OF | | | 10 FT FROM ANY HAZARDOUS OR NOXIOUS | | | CONTAMINANT, SUCH AS VENTS, STREETS, | | | ALLEYS, PARKING LOTS & LOADING DOCKS. | | | | | | CLARIFY NOTE ON PLAN "CONNECT TO HEAT | | | HOOD DUCT", THIS APPEARS TO BE TIED INTO | | | TOILET EXHAUST? | | | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | SHALL HAVE NOTIFICATION TO ALARM/STROBE | | | AS PER NFPA 4-4.4.3. | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | GREASE DUCT, FIRE SUPRESSION & WALK-IN | | | COOLER/FREEZER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2003-02-13 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-12 |
Time |
15:25 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
B |
|
| Notes |
| 2003-02-13 00:00:00 | REVISIONS FOR PLBG, APPROVED,GAS DENIED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2003-02-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-02-07 |
Time |
18:31 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2003-02-07 |
Time |
18:31 |
Sent To |
|
|
| Notes |
| 2003-02-07 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 11 | | | | | | 1) ROUTE PLANS TO DEPT. OF BUSINESS | | | REGULATION FOR REVIEW AND APPROVAL. | | | PLANS TO BE STAMPED AND WORKSHEET ATT- | | | ACHED PRIOR TO RESUBMITTING TO CITY FOR | | | REVIEW. | | | 2) SHT A4.0 HOOD DRAIN SHALL NOT BE PVC. | | | PIPE DRIECT TO VENT AND INSTALL A VALVE. | | | 3) SHT A4.0 RPZ BACKFLOW SHALL BE MAXI- | | | MUM OF 4' AFF FOR TESTING AND SERVICING | | | 4) FROM PREVIOUS REVIEW: SHT A4.0 FLOOR | | | PLAN AND SANITARY RISER DIAGRAM, DISH- | | | WASHER SHALL DRAIN TO SANITARY. UTILITY | | | ORD. | | | 5) FROM PREVIOUS REVIEW: PLEASE PROVIDE | | | DETAILS FOR HDCP TOILET ROOMS PER SEC. | | | 11-4.22 AND ALL SUBSECTIONS. CLEAR FLOOR | | | SPACE NOT SHOWN OR 5' TURNING SPACE. | | | 6) FROM PREVIOUS REVIEW: GREASE TRAP | | | DETAIL ON SHT A4.0 IS NOT APPROVED. SEE | | | ATTACHED SHEET FOR CITY UTILITY APPROVED | | | DETAIL. | | | 7) FOR GAS PERMIT APPLICATION THESE | | | REQUIREMENTS ARE NOT ADDRESSED FROM PRE- | | | VIOUS REVIEW: | | | A. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2 | | | B. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | 8) PLEASE SUBMIT A FLOOR PLAN THAT HAS | | | MEASUREMENTS FOR TOILET ROOMS. | | | 9) PAGES ON PLANS DO NOT MATCH INDEX ON | | | COVER SHEET. WHEN RESUBMITTING PLANS | | | PLEASE SUBMIT TWO FULL SETS WITH PAGES | | | SHOWN ON INDEX. REMOVE ALL REVISED | | | SHEETS AND INSERT NEW SHEETS. SUBMIT SET | | | OF OLD SHEETS TO COMPARE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-01-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-01-06 |
Time |
18:15 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2003-01-06 |
Time |
18:14 |
Sent To |
|
|
| Notes |
| 2003-01-06 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 11 | | | | | | 1) PLEASE CONTACT RODNEY COMPO, INVIRON- | | | MENTAL COMPLIANCE TO SIZE GREASE TRAP. | | | UTILITY DEPT WASTE ORD. #2938-96. PH # | | | (561) 837-4074 | | | 2) SHT A4.0 HOOD DRAIN, SAFE WASTE NOT | | | APPROVED. FLOOR SINK REQUIRED WITH VENT, | | | OR RUN SEPARATE LINE FROM MAIN VENTED | | | LINE TO FLOOR SINK. | | | 3) PLEASE SUBMIT INFORMATION FOR UTILITY | | | FAN DRAIN. | | | 4) SHT A4.0 GREASE TRAP DETAIL, SEE | | | ATTACHED SHEET FOR CITY WEST PALM BEACH | | | STANDARD FOR GREASE TRAPS. NOTE: 2 WAY | | | CLEANOUTS REQUIRED ENTERING AND EXITING | | | GREASE TRAP. SEE WALL AND BOTTOM THICK- | | | NESS ECT. | | | 5) RPZ BACKFLOW REQUIRED ON WATER SERV- | | | ICE TO SPACE. | | | 6) SHT A4.0 WATER RISER DIAGRAM, WATER | | | HAMMERS REQUIRED BY SEC 604.9 SHALL BE | | | SHOWN AND LOCATED NEAR FIXTURE. (ICE | | | MAKER - DISHWASHER - QUICK CLOSING VAL- | | | VES). | | | 7) SHT A4.0 WATER HEATER DETAIL, THERMAL | | | EXPANSION CONTROL IS REQUIRED PER SEC. | | | 607.3.2 | | | 8) SEPARATE GAS PERMIT REQUIRED. THE | | | FOLLOWING INFORMATION IS REQUIRED FOR | | | PERMIT APPLICATION. | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | C. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES (A)(3). | | | D. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2 | | | E. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | 9) SHT A4.0 DISHWASHER SHALL DRAIN TO | | | SANITARY PER UTILITY DEPT ORDINANCE. | | | 10) PLEASE PROVIDE DETAILS FOR HDCP | | | TOILET ROOMS PER SEC 11-4.22 AND ALL | | | SUBSECTIONS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2003-01-23 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2003-01-23 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|